The text of a manual · part 23 of 25
Modicon 800 Series Discrete I/O Modules User Guide, pages 221 to 230
Pages 221 to 230 of 241
The original document is the PDF (12 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B804, Modicon B805, Modicon B807, Modicon B824, Modicon B825, Modicon B828, Modicon B865, AEG B804, and 21 more models
Page 221
39.6 Specifications B882--032 Specifications Description
24 Vdc diagnostic output
Type of Operation
True high
Number of Points
32
Operating Voltage
19.2 ... 28 Vdc
Number of Groups
4
Outputs/group
8
On State Voltage Drop
0.5 Vdc maximum @ 1 A
Off State Leakage
1.0 mA maximum @ 28.0 Vdc
Minimum Load
100 mA
ON State Voltage Drop
0.5 Vdc maximum @ 1 A
OFF State Leakage
1.0 mA maximum @ 28.0 Vdc
Minimum Load
100 mA
Maximum Continuous Current
Surge Current per output
1.0 A per group
6.0 A per module
24.0 A peak
7.5 A for 0.5 ms maximum
10 pulses/s with 1.0 A dc
Load Inductance
1 H maximum with no external diode suppression
Load Capacitance Flags (B882 Only)
Maximum Response Time Power Required
1000 mf maximum Open Load
100 mA or less
Over Current
3.5 A or greater
Over Voltage
31 Vdc or greater
Over Temperature
140°C or greater
OFF ® ON
1 ms with a resistive load
ON ® OFF
1 ms with a resistive load
+5 V
300 mA*
+4.3 V
10 mA
--5 V
0 mA
* When all outputs are ON, +5 V = 300mA. When all outputs are OFF, +5 V = 200 mA. External Power Supply
GM--DISC--800
With nominal voltage of 24 Vdc required to power the field side of the B882**
B882--032 24 Vdc Diagnostic Output
219
Page 222
Terminal Connector
AS--8535--000
** The external power supply must provide power to the field side loads and the field side electronics. The amperage sizing requirements of this supply have three components: 160 mA/group maximum (all channels ON), plus steady state load current of all outputs capable of being ON simultaneously, plus the inrush current of all outputs capable of being switched simultaneously.
220 B882--032 24 Vdc Diagnostic Output
GM--DISC--800
Page 223
Chapter 40 B882--116 24 Vdc Output
GM--DISC--800
V
Overview
V
Field Connections
V
Configuration
V
Switch Settings
V
Specifications
B882--116 24 Vdc Output
221
Page 224
40.1 Overview The B882-116 24 Vdc (16-point) Output Module monitors field points for both open and short circuit fault conditions. The module is designed for safety applications whereby it monitors essential field wiring. Two test modes are available: pulse test mode, and no pulse test mode. In no pulse test mode, the module detects open circuits only when the output point is OFF, and short circuits only when the point is ON. Leakage current in the OFF state is less than 3 mA. Trip current to detect a short circuit is greater than 1 A. In pulse test mode, the module pulses the output to the opposite of the command state to determine the complete status of the output load. Pulse timing is: 500 ms opposite state pulse once every second. Note: Average currents in output circuits are changed by no more than 0.1% by full test mode.
40.1.1
Simplified Schematic
2.5 mA CURRENT SOURCE
Figure 97 B882--116 Simplified Schematic
This leakage current is actually the 2.5 mA test current source. It cannot be turned OFF.
222 B882--116 24 Vdc Output
GM--DISC--800
Page 225
40.2 Field Connections User connections are made to a standard screw terminal strip and the rigid wiring system permits module insertion or removal without disturbing the wiring.
40.2.1
Output Connections IF OUTPUT NOT USED
24 Vdc
Figure 98 B882--116 Terminal Numbering and Output Connections
Note: Dummy load pin is only used to prevent an open circuit fault from being returned from an unused output.
GM--DISC--800
B882--116 24 Vdc Output
223
Page 226
40.3 Configuration This module appears as a B882 module when configured - i.e., the module requires either four 16-bit words - two 3x input registers and two 4x holding registers or 32 discrete 0x outputs and 32 discrete 1x inputs. The first holding register contains the command state programmed by the user. The input registers contains the faults detected. If an open circuit fault is detected on output point three, then a one is displayed in the 3x register at position three. If a short fault is detected on output point three, then a one is displayed in register 3x + 1 at position three. A one indicates a detected fault, whereas, a zero indicates normal operation of that output point. The module uses only three of the four configured 16-bit words. A point that is shorted disables the output current flow. Once a fault is detected the operation follows the flow chart in Figure 99 if the module is in the pulse test mode of operation. If not in pulse test mode then reported faults are cleared when a command changes it to the opposite state, in either case the detection of a short will force the point off. Caution: The module will not work correctly with a J810 Remote I/O Processor.
224 B882--116 24 Vdc Output
GM--DISC--800
Page 227
B882 Pulsed Operation. No Faults Reported.
Commanded Off. Point Shorted,or Open or Hardware Failure On. Module Reports Fault.
Command On. Point Shorted, or Open or Hardware Failure OFF. Module Drives Point Off. Fault Reported.
PLC Detects Fault. Alarms Operator.
PLC Detects Fault. Alarms Operator.
Physical Fault Cleared.* Module Reports No Fault. (within 1 s)
Operator or PLC Commands Point Off.
Physical Fault Cleared.
Return to Normal Pulsed Operation. No Faults Reported.
Module Continues to Report Fault and Keeps Point OFF.
Operator or Program Commands Point Off. Module Clears Reported Fault. * REPLACE MODULE IF PHYSICAL FAULT IS WITHIN MODULE. Return to Normal Pulsed Operation. No Faults Reported.
Figure 99 Full Fault Test Mode Only Flow Chart
MSB
PHYSICAL OUTPUTS
MSB
LSB
UNUSED OUTPUTS
LSB
4x
12345678
9 10 11 12 13 14 15 16
4x + 1
12345678
9 10 11 12 13 14 15 16
3x
12345678
9 10 11 12 13 14 15 16
3x + 1
12345678
9 10 11 12 13 14 15 16
OPEN CIRCUIT
SHORT CIRCUIT
Figure 100 Data Registers
GM--DISC--800
B882--116 24 Vdc Output
225
Page 228
Module Mode Behavior Partial Test Mode
Full (PULSE) Test Mode
Use with high speed field devices
Yes
Not Recommended
Finds opens when OFF
Yes
Yes
Finds opens when ON
No
Yes
Reaction to OPEN fault*
No Change
Point OFF
To clear open fault, clear physical fault, then
See Note 1
Write 0
Finds shorts when OFF
No
Yes
Finds shorts when ON
Yes
Yes
Reaction to short fault*
Point OFF
Point OFF
To clear short fault,clear physical fault, then
See Note 2
Write 0
* In all cases faults are reported to the PLC via register entries for corresponding point and type of fault(s). In addition, the fault lamp for the corresponding group will blink until fault indication is cleared. Any points with detected short faults will be turned off independent of the command state from the PLC. Note 1: In partial test mode an open fault indication will be cleared by writing a 1 to the output point independent of the actual status of the output wiring. Note 2: In partial test mode a short fault indication will be cleared by writing a 0 to the output point independent of the actual status of the output wiring.
226 B882--116 24 Vdc Output
GM--DISC--800
Page 229
40.4 Switch Settings A two-position DIP switch located on the rear of the module is used to select one of two test modes on a group basis. No pulse test mode detects open circuits only when the output is OFF, and shorts circuits only when the point is ON. Pulse test mode pulses the output to the opposite of the command state to determine the status of the output load. Each individual switch relates to each group of eight output points. For example, DIP switch position #1 when set to ON enables pulse test fault sensing for group 1 (points 1 ... 8). When a fault is detected the corresponding FAULT LED flashes independent of the test mode. When the switch is in the OFF position then no pulse test is performed. PULSE TEST SWITCH 2 POSITION DIP SWITCH TOP OF MODULE
1 2
PCB
1 ON LEFT UP
0 OFF RIGHT DOWN
SWITCHES SW1=0 =1
FUNCTIONS GROUP 1, PULSE TEST ENABLED GROUP1, NO TEST
SW2=0 =1
GROUP 2, PULSE TEST ENABLED GROUP2, NO TEST
Figure 101 Pulse Test DIP--Switch Settings
Note: When using binary and BCD format, remember that output 16 is the LSB of word one and word two is ignored by the module.
GM--DISC--800
B882--116 24 Vdc Output
227
Page 230
40.5 Specifications B882-116 24 Vdc Output Specifications Description
24 Vdc output
Number of Points
16
Number of Groups
2
Outputs per Group
8
Working Voltage
19.2 ... 30.0 Vdc
Note: 24 V field supply must be rated to supply output load current +.5 A for the module, +5 A surge rating. This 5 A surge rating is required to correctly detect short circuits. Group input power fusing is recommened. Fuse should be rated for expected load current plus 5 A Slo- -Blow. Caution: When field supply drops from 24 ... 0 V an output current of up to 15 mA may be generated to points that are off. Output fault flags reported when field supply is below 19.2 V may be incorrect.
On State Voltage Drop
0.5 Vdc maximum @ 0.5 A
Off State Leakage Current
3.0 mA maximum at 30.0 Vdc Maximum allowable load resistance 6 kW
Note: 3 mA x 6 kW = 18 V - i.e. leakage current produces enough voltage on a 6 kW load resistor to simulate a valid input signal. Inrush Current Continuous Current
1.0 A peak for 0.1 ms at 4 pulses/s while carrying 0.5 A dc Maximum
0.5 A
Maximum/group
4.0 A
Maximum/module
8.0 A
Minimum Load Current
10 mA
Maximum Load Inductance
0.5 H @ 0.5 A, 4 Hz switching
Maximum Load Capacitance
4 mF @ 4 Hz maximum switching frequency
Power Required
+5 V
350 mA maximum all outputs ON
+4.3 V
10 mA
--5 V
0 mA (not used)
Terminal Connector
228 B882--116 24 Vdc Output
AS--8535--000 GM--DISC--800