Page 1 of 984 Programmable Logic Controllers and 800-Series Input/Output Modules

Manual · Schneider

984 Programmable Logic Controllers and 800-Series Input/Output Modules

Manual123 pagesPDF 1.2 MB

Catalog chapter on Modicon 984 PLCs and 800-Series I/O modules, including the B807-132 input and B865-001 TTL register input modules.

Download the PDF1.2 MB

Covers · 8 models

The models it covers

Summary

What is in it

Chapter 3 of a Modicon catalog and specifier's guide, covering the Modicon 984 family of programmable logic controllers and the 800-Series input/output modules. It compares 984 models by memory, I/O capacity and scan time, lists the instruction set, and describes slot-mount and chassis-mount PLCs, hot standby and coprocessor options. The I/O part gives specifications for individual modules such as the AS-B807-132 and B865-001, plus housings, cabling, power supplies, remote I/O interfaces and local and remote I/O configuration.

Its parts

  1. Benefits of a Full Range, High Performance Family of PLCs
  2. 984 Functional Overview
  3. Range of 984 Performance
  4. 984 Instruction Set
  5. 984 PLCs – Individual Product Descriptions
  6. 984 Slot-Mount PLCs
  7. 984 Chassis-Mount PLCs
  8. 800-Series Input/Output Modules
  9. Housings
  10. 800-Series I/O Cabling
  11. 800-Series I/O Power Supplies
  12. Remote I/O Drop Interfaces
  13. Configuring A Local I/O System
  14. Configuring a Remote I/O System

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

A catalog section from Schneider Automation on the Modicon 984 programmable logic controllers and the 800-Series input/output modules. Among the 800-Series modules it lists the AS-B807-132 115 Vac hi-density input module and the B865-001 (AS-B865-001) TTL register input module, with terminal wiring and keying drawings. It helps the reader choose a 984 controller and the I/O modules, connectors and housings that go with it.

Read for this summary: pages 1 to 5, 28, 44 to 47, 51 and 63 to 64 of 123.

B807 module
AS-B807-132: 115 Vac hi-density input module p. 51
B865 module
B865-001: TTL register input, 8 channels, 16 data lines, 5 V TTL p. 64
I/O addressing
AS-B807-132: 32/0 I/O bits; AS-B865-001: 16/0 I/O bits p. 46
Terminal connector
AS-B807-132 and B865-001: AS-8535-000, one housing slot each p. 51, 64
Environment
800-Series I/O: 0-60°C (32-140°F), 0-95% humidity non-condensing, shock 10 G's for 11 msec p. 45
ACTIVE light
Green LED on every 800-Series module: steady on means configured and communicating with the 984; off means communication is invalid p. 45
B807 weight
AS-B807-132: 2 lbs (0.91 kg) p. 51
Configuration
Software addressable through the 984's Traffic Cop, any module in any slot; mechanical keying stops wrong-slot insertion p. 45
Surge protection
All 800-Series modules meet IEEE-472-1974 and ANSI C37-90A-1974 surge standards p. 45
Field wiring
Wires land on terminal blocks fixed to the housing, so modules change without disturbing field wiring p. 45
Listings
The catalog states UL Listing E54088 and CSA Listing LR32678 for 800-Series I/O p. 45
Remote I/O
Remote drops up to 15,000 feet (4.5 km) from the PLC depending on cable; up to 5 housings per remote drop p. 5
984 family range
1.5k to 64k of logic memory and 256 to 16,384 discrete I/O points p. 2
Memory backup
984 CMOS memory backed by lithium batteries for up to one year of power loss p. 5

What this manual walks you through

  • How a 984 control system and its I/O work p. 5
  • Choosing an 800-Series I/O module by voltage, points and connector p. 46, 47
  • General 800-Series I/O specifications and diagnostics p. 45
  • AS-B807-132 terminal numbering, wiring and housing keying p. 51
  • B865-001 terminal numbering, wiring and housing keying p. 64
  • 984 chassis-mount PLCs, their housings and option modules p. 28

Good to know

  • If communication with the PLC fails, the module shuts itself down and the PLC sets all inputs to 0. p. 45
  • Keying pins go in the housing holes shown by black circles, viewed facing the housing. p. 51
  • To use option modules with a 984A or 984B, the seven card chassis is required. p. 28

Questions this manual answers

What is the Modicon B807 module?

The AS-B807-132 is an 800-Series 115 Vac hi-density input module that takes 32/0 I/O bits and uses the AS-8535-000 terminal connector. p. 46, 51

What is the Modicon B865-001?

A TTL register input module with 8 channels of 16 data lines at 5 V TTL, taking 16/0 I/O bits. p. 46, 64

What does it mean when the ACTIVE light on an 800-Series module is off?

Communication between the module and the PLC is invalid; the module shuts down and the PLC sets all inputs to 0. p. 45

What temperature range do Modicon 800-Series I/O modules handle?

0-60°C (32-140°F) at 0-95% humidity, non-condensing. p. 45

The whole text · 13 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 10091-100
  11. Pages 101 to 110101-110
  12. Pages 111 to 120111-120
  13. Pages 121 to 123121-123

The file

Size and text

PublisherSchneider Automation
Pages123
PDF1.2 MB
TextText from the PDF itself; 9 pages are scans, read by OCR, which may hold reading errors.

The first pages · 3 of 123

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 123
Page 2
Page 2of 123
Page 3
Page 3of 123

More documents · 1

For the same models