The text of a manual · part 3 of 13
984 Programmable Logic Controllers and 800-Series Input/Output Modules, pages 21 to 30
Pages 21 to 30 of 123
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B807, Modicon B865, AEG B807, Gould B807, Schneider B807, AEG B865, Gould B865 and Schneider B865
Page 21
S908 Remote I/O Processor
Remote I/O is the portion of the controller's I/O that is typically installed away from the PLC housing and that requires an interface module to communicate with the I/O processor at the CPU. Communication to the primary housing at each drop is accomplished through coaxial cable. A remote I/O system may consist of single or multiple housings at each drop. The S908 Remote I/O Processor Option Module provides remote I/O capability to the 984-685/785 controller lines. Using the S908 Remote I/O Processor, these controllers can address up to 31 remote drops of 800-Series I/O. In addition, each drop can support two ASCII communication ports (maximum of 32 ports available). S908 processors are available with either one or two coaxial cable connectors for single or dual cable configurations. Use of the S908 Remote I/O Processor requires installation of an AS-E908-131 or AS-E908-016 plug-in executive cartridge. The E908-131 supports 31 remote I/O drops with 512 bits in and 512 bits out per drop. The E908-016 supports 16 remote I/O drops with 1024 bits in and 1024 bits out per drop. The S908 Remote I/O Processor occupies one option slot in a 984-685/785 controller. A 785 upgrade kit is available to support a 16 drop Quantum I/O S908 network. The AM-E785-QK0 kit includes: 785 downloadable executive, #SW-E785-Q00 S908 16 drop cartridge, #AS-Q908-016 This 785 upgrade kit supports up to 16 drops of 800-Series I/O and Quantum I/O. Each drop must be either 800-Series I/O or Quantum I/O. A combination of 800-Series I/O and Quantum I/O is not supported within a drop. The local drop supports only 800-Series I/O. Modsoft 2.2 or greater is required to utilize the features of the AM-E785-QKO kit.
Remote I/O (Single Cable)
Up to Five Housings
Up to Five Housings S908 Remote I/O Network
3-22
Up to Five Housings Up to 31 Drops
Page 22
S908 Technical Specifications Part Number AS-S908-110 AS-S908-120 AS-E908-131 AS-E908-016 AM-E785-QK0
Configuration Information Supervisory PLCs Communication Rate Ports S908-110 S908-120
Remote I/O Processor, Single Cable Remote I/O Processor, Dual Cable Executive Cartridge, 31 drops, 512 bits in and out per drop Executive Cartridge, 16 drops, 1024 bits in and out per drop 785 upgrade kit to support 16 drop Quantum S908 network. AM-E785-QK0 includes: SW-E785-Q00 785 Executive Software AS-Q908-016 S908 Cartridge to support 16 800-Series I/O and Quantum I/O drops Modsoft 2.2 or greater required.
Remote I/O (Dual Cable)
Up to Five Housings
Up to Five Housings
Up to Five Housings
S908 Remote I/O Network
Up to 31 Drops
984-685/785 1.5 Mbit/s One F-type coaxial Two F-type coaxial
Power Supply Power Supply Power Draw +5.0 Vdc +4.3 Vdc -5.0 Vdc
1500 mA 0 mA 0 mA
Environmental Operating Temperature Relative Humidity Shock Resistance
0 ... 60°C 0 ... 95% non-condensing 10G (11 ms)
Space requirements Weight
1 option slot in H8xx-209 subrack 2 lbs (.9 kg)
984-685, 785
3-23
Page 23
S911-800 Hot Standby Systems For Slot-Mount PLCs
If your application requires fault tolerance and high availability, consider the hot standby option, available on 984-685 and 785 PLCs. A hot standby system provides backup control in case of a failure. Two identically-configured 984 PLCs communicate with each other via S911 Hot Standby Modules located in each PLC. Each PLC also has a loadable hot standby instruction block (HSBY), programmed into its user logic, which communicates status information between the two PLCs. One of the PLCs in the hot standby system operates as the primary PLC. It reads input data from the remote input/output drops, executes ladder logic, and sends output commands back to the drops. The primary PLC continuously updates the standby PLC with system status information at the end of each logic solve. In normal conditions, the standby PLC does not perform control functions; it merely processes status information. However, if the primary PLC fails, the standby PLC assumes primary control functions within 48 milliseconds of the failure. To configure an S911 Hot Standby System, you need, in addition to PLCs and input/output drops: •
S911 Hot Standby Processors in each PLC
•
S908 Remote Input/Output Processors in each PLC
•
W911 cable (in 6 ft., 12 ft., or 30 ft. lengths)
•
Redundancy terminator kit
•
Two 75 ohm self-terminating connectors
• One MA-0186-000 coaxial line splitter
Ordering Information
For ordering Hot Standby systems, single part numbers are available combining appropriate components: – Two S911 Processor Boards – One W911 Cable – One Redundancy Terminator Kit (AS-911T-KIT) – HSBY Function Block Software AS-911K-806 AS-911K-812 AS-911K-830
3-24
Kit with 6 foot W911 Cable Kit with 12 foot W911 Cable Kit with 30 foot W911 Cable
984 / S911 Single Cable Hot Standby System
Page 24
S911-800 Hot Standby Technical Specifications
984 / S911 Dual Cable Hot Standby System
Configuration Information PLCs that use S911-800
984-685/785
Part #, HSBY Function Block for 984-685, 785
SW-AP98-RXA
Data Exchange Rate Worst Case Switchover Time Power Source Power Draw +5 V +4.3 V 5V
1500 mA 0 mA 0 mA
Environmental Operating Temperature Relative Humidity Shock Resistance
0 ... 60°C 0 ... 95% non-condensing 10G (11 ms)
Physical Space Requirements Max. Distance between PLCs Weight
5 megabits/sec 13 ... 48 milliseconds 984-68x/78x power supply
One option slot in H8xx-209 subrack 30 ft (9 m) 4.5 lbs (2 kg)
3-25
Page 25
C996 Integrated Control Processor
The C996 Integrated Control Processor, or DOS CoPro, is a DOS-compatible computer which provides the power to solve problems that are difficult or inefficient to do in ladder logic, by extending the processing capabilities of the 984-685 and 984785 slot-mount PLCs. This makes the DOS CoPro option perfect for complex tasks such as floating point arithmetic, serial communications, data concentration, miscellaneous network interfaces, operator interfaces, and more. Using DOS, you may adapt many standard applications and increase the performance of the 984 system. The C996 contains 1024 bytes of RAM memory, two serial (RS232) ports, a floppy drive interface, and a keyboard interface. Two (AM-C996-802) or four (AM-C996-804) standard 1/2 size XT slots are available for option boards, such as video adapters, network interface cards and the like. One instruction integrates computing power into the control system. The CoPro's simple interface to the ladder logic program is a software function block, CALL. The M996 mass storage device provides extensive, non-volatile data storage for the C996 CoPro. The storage device is packaged in a shock resistant enclosure to minimize internal vibration. A 40 Mbyte hard disk drive, interface card, and 1.44 Mbyte floppy disk drive are included, as well as a cable to connect the mass storage device to the CoPro.
3-26
Page 26
The AM-C996-80x DOS CoProcessor provides DOS compatible coprocessing and interface capability to 984, 685 and 785 controllers.
Call Function Block Ladder Logic Interface to C Language Tasks
3-27
Page 27
C996 Technical Specifications
Software
Description C996 CoPro Components C996 CoPro M996
Cables (Modicon P/N)
Option module for the 984-685, 785
AM-C996-802 1.5 slots AM-C996-804 2 slots AS-M996-001 Mass Storage Includes: • 40 Megabyte hard disk • 3.5 floppy disk (1.4 megabyte capacity) • W996 comm cable • AC power cable AS-W950-006 (C996 to Modem, 6 ft.) AS-W951-012 (C996 to IBM XT, 12 ft) AS-W952-012 (C996 to IBM AT, 12 ft) AS-W488-006 (C996 to IEEE-488, 6 ft) AS-W996-006 (C996 to M996, 6 ft) PA-0407-000 (Floppy, 3 ft)
984 Family Compatibility C996s Per 984 Controller C996-802 C996-804 S908 S911 S985 984-785, 685 two maximum 1.5 slots, 6.3 Watts 2 slots, 6.3 Watts 1 slot, 7.5 Watts 1 slot, 5.8 Watts 1 slot, 5.0 Watts 1.5 slots Total Power, 40 Watts max.
Total option power for two C996-804s must not exceed 25 Watts.
Hardware CPU Optional Math Coprocessor Memory C996 LED Indicators
Battery
Communications Ports
3-28
80286 at 8 MHz 80287 at 5.3 MHz 1 Megabyte of Dynamic RAM Ready Status 1 (user definable) Battery Low Operational Life: 1 year Shelf Life: 5 years Front panel accessible Battery Lithium AA Cell 2 serial ports RS-232 Baud rate 150-9600 software selectable Default 9600/8 bit/no parity
BIOS: Operating System Required Software
Device Driver Programming Language Compiler Documentation C996 Installation Manual C996 Software Manual
Award Software ver. 3.04 or higher MS-DOS or IBM-PC DOS ver. 3.3 Modicon P/N SW-AP98-CXA Includes: • IBM/P190 CALL Function Block • C996 Utilities Software • C996 "C" Libraries • Immediate Call Block routines C996 SYS 70k (included in config. sys.) C Programming Language "User-supplied" Microsoft C ver. 5.1 GX-C996-002 GX-C996-001
Expandability IBM-XT Card Requirements Expansion Slots C996-802 2 XT slots C996-804 4 XT slots Max. Size (H x D) 4.2 in x 5.5 in Power Consumption for XT Cards: Maximum Per Card 1.25 A (6.2W) Maximum Cumulative Power C996-802 1.8 A (9W) C996-804 3.6 A (18W) Environmental Operating Temperature Storage Temperature Relative Humidity Shock Resistance Space Requirements: C996-802 C996-804 Weight C996-802 C996-804
0 to 60°C -40° to 80°C 0 to 95% (non-condensing) 10G (11ms) 1.5 system bus slots in H8xx-209 housing (fits with CPU) 2 system bus slots in H8xx-209 housing 3.5 lbs (1.6 kg) 4.5 lbs (2.0 kg)
Page 28
984 Chassis-Mount PLCs
Chassis-mount PLCs are the perfect choice for mid-to-large sized applications which require fast logic solving. The three models of 984 chassis mount PLCs include the 984A, 984B, and 984X. Maximum Performance for Time Critical Applications If your application is time critical, choose chassis-mount PLCs. They have logic solve times of .75 milliseconds per k of user logic, one of the fastest logic solve times in the industry. A special Segment Scheduler lets you program time critical sections of user logic so their logic solve times are even faster. Controller Housings Modules that make up a 984 chassis-mount PLC can be housed in either a four or seven card chassis. 984 chassismount systems that use the four-slot chassis come with a P930 Power Supply. Systems that use the seven-slot chassis use the P933 Power Supply. Option Modules The chassis-mount PLCs can support up to three option modules. To use option modules with a 984A or 984B PLC, you must use the seven card chassis. Option modules include: Communication Options • S978 Dual Modbus Modem • S985 Modbus Plus Interface
Optional Processors • R911 Hot Standby Processor • C986 Control Processor (CoPro)
The 984X chassis supports only two option modules. The 984X is only available in a four-card chassis. The R911-000 Hot Standby Processor is useful in applications that require fault tolerance and high availability. It allows you to have a backup control system immediately available in case of failure. The C986 Control Processor, or CoPro, extends the processing capabilities of the PLC by offloading complex logic from the PLC. This way you can increase system speed through multiprocessing and flexible multi-tasking capabilities. The S985 Modbus Plus interface provides connectivity to a Modbus Plus peer-to-peer communication network for data transfer and remote programming capabilities. The S985 also supports Modbus Plus cable redundancy. The S978 Dual Modbus Modem provides two modems to connect the 984 in a twisted-pair Modbus network.
3-29
Page 29
984A
984A / S908 Single Cable Remote I/O Network
The 984A PLC is designed for applications that need a high performance PLC with medium memory requirements and remote input/output control. The 984A's S908 Remote Input/Output Processor supports up to 32 drops of 800 Series remote I/O. The 984A does not support local I/O configurations. You can choose to add option processing to your 984A system. You can configure a Hot Standby system by adding the R911000 Hot Standby system. You can also increase your system speed and processing power by adding up to three C986 CoProcessors. Communication options are described in Section 7: Networking.
3-30
Up to 32 drops
Page 30
984A / S908 Dual Cable Remote I/O Network
984A Technical Specifications Architecture Memory User logic Registers Total I/O Capacity Max. Discrete I/O Max. Analog I/O Total I/O Bits Local I/O Capacity Remote I/O Capacity Max. I/O Bits per Drop Max. # Drops Total I/O Bits Max. # ASCII Ports Internal Coils Logic Solve Time Communication Ports Electrical Power Supply Input Voltage I/O Power Capacity Environmental Temperature Humidity Shock Resistance Dimensions (WxHxD) 4-slot Chassis 7-slot Chassis Weight 4-slot Chassis 7-slot Chassis
6k 920 8k
32k 1920 34k
2048 any mix 1920 32,768 N/A 1024 In/1024 Out 32 32,768 any mix 32 2048 .75 ms/k 3 Modbus, 1 Simple ASCII Output
115 Vac 230 Vac N/A 0 ... 60°C 0 ... 95% non-condensing 10 G (11 ms) 11.6 x 19.2 x 10.2 in (295 x 488 x 259 mm) 17.3 x 19.2 x 10.2 in (440 x 448 x 259 mm) 46 lbs (21 kg) 55 lbs (25 kg)
Up to 32 drops
3-31