Page 11

984 PLCs – Individual Product Descriptions

Wide-ranging Functionality and Physical Characteristics Modicon 984 PLCs are designed as a compatible family, yet the individual products in the family offer a wide range of functionality and physical attributes. This means you can use the right PLC for the right job, no matter what the application. The PLCs are available in three basic physical configurations: compact, chassis-mount, and slot-mount. For information on compact controllers and Micro and 984-120 Compact PLCs, see Section 2. Slot-mount PLCs use an advanced microprocessor architecture that incorporates system and power components into single, compact modules. These modules mount in the primary 800Series I/O subracks. They include the 984-38x series, 984-48x series, 984-685 series, and 984-785 series PLCs. These models cover small to large control applications with logic solve times ranging from 1.0 ... 5 milliseconds/K of user logic. Slot-mount PLCs are the perfect choice for small to large applications such as machine or process control. Chassis-mount PLCs are housed in a rugged four or seven-slot chassis. These PLCs comprise a set of modular system boards that are individually installed in slots in the chassis. Chassismount PLCs include the 984A, 984B, and 984X models. These models cover mid-range to extra large control applications with high performance logic solve times of about 0.75 milliseconds/K of user logic.

General 984 Environmental Specifications Ambient Temperature Humidity Shock Vibration RFI/EMI Emission RFI/EMI Susceptibility UL Listing CSA Listing

3-12

0 ... 600C 32 ... 1400F 0 ... 95% noncondensing 10 G's for 11 msec .625 @ 50-500 Hz Complies with applicable FCC requirements ML-STD-461B CS02-Conducted RS03-Radiated E54088 LR32678

Page 12

984 Slot-Mount PLCs

PLC Components

How to Choose the Right PLC

All Modicon slot-mount PLCs are designed for quick replacement. Every slot-mount PLC includes an integrated power supply, central processing unit, local I/O processor, and communication ports.

There are four series of 984 slot-mount PLCs. Each series is designed for specific input/output configurations and performance requirements: Model

System Configuration and Functionality

Some slot mount PLCs support optional processors that further enhance the system functionality.

984-38x 984-48x 984-685

Hot Standby and Modbus Plus Redundancy

984-785

Local I/O only. Local I/O with built-in remote I/O. Local I/O with optional remote I/O. Option processing. More memory Local I/O with optional remote I/O. Option processing. Most memory.

All slot-mount controllers include onboard executive and user memory.

The 984-685 and 984-785 slot-mount PLCs support several option processing features that can increase the functionality and performance of your system. If your application requires fault tolerance and high availability, you should consider adding the S911-800 Hot Standby module. If you need multiple, independent Modbus Plus networks, you should consider the S985-800. This optional Modbus Plus module can also be used in redundant cable Modbus Plus configurations. This optional processor is further described in Section 7: Networking.

Each series has several PLCs to choose from. Communication and performance features separate the different models. A higher number in the series indicates greater performance, both in communication functions and speed of logic solve. Each series offers up to three types of communication features. The following chart shows the three options within each series and what type of application best fits the PLCs. (The 48x, 685, and 785 series have two or three communication ports). Communication Features

Applications

1 Modbus Port

RS 232-based communication network for communicating with programming panels, man/machine interfaces, and host computers. 2 Modbus Ports RS 232-based communication network as above. Multiple ports allow simultaneous access to multiple hosts. 1 Modbus Port, Allows both RS 232-based communication 1 Modbus Plus Port (Modbus) and high speed, peer-to-peer or: networking between multiple PLCs, man 2 Modbus Ports, machine interfaces, and host computers. 1 Modbus Plus Port Good for applications requiring high data throughput. To decide which slot-mount PLC best fits your needs: 1. Choose the series that best fits your application’s input/ output configuration and memory requirements. 2. Pick a PLC within that series, based on communication and performance requirements. If you need additional assistance, contact your local representative or distributor.

3-13

Page 13

984-38x Series

The 984-38x series of PLCs is designed for small-to-mid-range local applications with up to two racks of local I/O holding up to 21 I/O modules. There are three models in the 984-38x series: PC-E984-381, PC-E984-385, and PC-D984-385. They differ in their communication abilities and power supply voltage, as shown in the table below. Each PLC includes onboard executive and user memory.

984-38x Differentiating Features Model No.

1 Modbus Port

1 Modbus Plus Port

√

PC-E984-381

3-14

2 Modbus Ports

Time-of-Day Clock

Logic Solve Speed (ms/k)

√

3

PC-E984-385

√

√

√

3

PC-D984-385

√

√

√

3

Page 14

Local I/O

Up to Two Housings Max.

984-38x Series Technical Specifications

PC-E984-381 Architecture Memory User logic Registers Total I/O Capacity Max. discrete I/O Max. analog I/O Local I/O Capacity Total I/O bits Total I/O racks Remote I/O Capacity Internal Coils (Includes Disc I/O) Performance Communication ports Electrical Power Supply Input voltage

I/O power capacity Environmental Temperature Humidity Shock resistance Physical Dimensions WxHxD Space Requirements

PC-E984-385

PC-D984-385

16k 1920 18k

16k 1920 18k

16k 1920 18k

512 any mix 32 In/32 Out

512 any mix 32 In/32 Out

512 any mix 32 In/32 Out

512 In/512 Out 2 NA

512 In/512 Out 2 NA

512 In/512 Out 2 NA

2048 3 ms/k 2 Modbus

2048 3 ms/k 1 Modbus 1 Modbus Plus

2048 3 ms/k 1 Modbus 1 Modbus Plus

115 Vac 230 Vac 24 Vdc 3 amps

115 Vac 230 Vac 24 Vdc 3 amps

125 Vdc

0 ... 60˚C 0 ... 95% 10G (11 ms)

0 ... 60˚C 0 ... 95% 10G (11 ms)

0 ... 60˚C 0 ... 95% 10G (11 ms)

2.54 x 10.5 x 8 in (39.4 x 266 x 203 mm) Slot 1 in H8xx-20x

2.54 x 10.5 x 8 in (39.4 x 266 x 203mm) Slot 1 in H8xx-20x

2.54 x 10.5 x 8 in (39.4 x 266 x 203mm) Slot 1 in H8xx-20x

24 Vdc 3 amps

3-15

Page 15

984-48x Series

The 984-48x PLCs are designed for small-to-mid-range, local and remote applications. They support two racks of local 800Series I/O and up to six drops of remote I/O. The ability to communicate to remote I/O is facilitated by the S908 communications network, a functionality which is built into the mainframe. This feature supports a single cable with up to six drops of remote I/O. There are three models in the 984-48x series, the PC-E984-480, PC-K984-485, and PC-E984-485. They differ in their communication abilities and support for a key switch, as shown in the table below. Each PLC includes onboard executive and user memory.

984-48x Differentiating Features

Model No PC-E984-480 PC-K984-485 PC-E984-485

1 Modbus Port

2 Modbus Ports

1 Modbus Plus Port

Logic Solve Speed (ms/k)

Key Switch

√ √

3 3 3

√

√ √ √

Remote I/O (Single Cable)

Local I/O

Up to Two Housings Max.

Up to Five Housings Up to Two Housings Max.

3-16

S908 Remote I/O Network

Up to Five Housings Up to 6 Drops Up to 5,000 Feet

Page 16

984-48x Technical Specifications PC-E984-480 Architecture Memory User logic Registers Total I/O Capacity Max. discrete I/O Max. analog I/O Local I/O Capacity Total I/O bits Total I/O racks Remote I/O Capacity Max. I/O bits per drop Max. # drops Total I/O bits Max. # ASCII ports Internal Coils (Includes Disc. I/O) Performance Communication ports Key Switch Electrical Power Supply Input voltage I/O power capacity Environmental Temperature Humidity Shock resistance Physical Dimensions WxHxD Space Requirements housing Weight

PC-K984-485

PC-E984-485

16k 1920 18k

16k 1920 18k

16k 1920 18k

2048 any mix 224 In/224 Out

2048 any mix 224 In/224 Out

2048 any mix 224 In/224 Out

512 In/512 Out 2

512 In/512 Out 2

512 In/512 Out 2

512 In/512 Out 6 3584 In/ 3584 Out 12 2048 3 ms/k 2 Modbus No

512 In/512 Out 6 3584 In/ 3584 Out 12 2048 3 ms/k 1 Modbus 1 Modbus Plus Yes

512 In/512 Out 6 3584 In/ 3584 Out 12 2048 3 ms/k 1 Modbus 1 Modbus Plus No

115 Vac 230 Vac 24 Vdc 3 amps

115 Vac 230 Vac 24 Vdc 3 amps

115 Vac 230 Vac 24 Vdc 3 amps

0 ... 60°C 0 ... 95% 10 G (11 ms)

0 ... 60°C 0 ... 95% 10 G (11 ms)

0 ... 60°C 0 ... 95% 10 G (11 ms)

2.54 x 10.5 x 8 in (39.4 x 266 x 203 mm) Slot 1 in H8xx-20x housing 6.6 lbs (3.0 kg)

2.54 x 10.5 x 8 in (39.4 x 266 x 203 mm) Slot 1 in H8xx-20x housing 6.6 lbs (3.0 kg)

2.54 x 10.5 x 8 in (39.4 x 266 x 203 mm) Slot 1 in H8xx-20x 6.6 lbs (3.0 kg)

3-17

Page 17

984-685

The 984-685 PLC handles mid-range to large applications. It supports five racks of local 800 series I/O and up to 31 drops of remote I/O. For remote I/O, an optional S908 processor is required. The S908 processor supports either single or redundant cable configurations. If you are configuring a remote I/O system, you must also add an S908 Remote I/O Processor (Part No. AS-S908-110 or AS-S908-120 for single/dual cable configurations) and a remote I/O Executive Cartridge (Part # AS-E908-016 or AS-E908-031). The 984-685 supports the S911-800 Hot Standby optional processor that increases the performance and functionality of your system. The 984-685 includes onboard executive and user memory.

984-685 Differentiating Features

Model No PC-E984-685

1 Modbus Port

Local I/O

2 Modbus Ports

1 Modbus Plus Port

Logic Solve Speed (ms/k)

√

√

1

Up to Five Housings Max.

3-18

Page 18

984-685 Technical Specifications PC-E984-685

Remote I/O (Single Cable)

Architecture Memory User logic Registers Total I/O Capacity Max. Discrete I/O Max. Analog I/O Local I/O Capacity Total I/O Bits Total I/O Racks Remote I/O Capacity Max. I/O Bits per Drop Max. # Drops Total I/O Bits Max. # ASCII Ports Internal Coils (Includes Disc. I/O) Performance Communication Ports

16k 9999 26k

Up to Five Housings

8192 In/8192 Out 1088 In/1088 Out 1024 In/1024 Out 5 512 In/512 Out or 1024 In/1024 Out 31 16 16,384 32 8192 1 ms/k 2 Modbus 1 Modbus Plus

Up to Five Housings S908 Remote I/O Network

I/O Power Capacity Environmental Temperature Humidity Shock Resistance

115 Vac 230 Vac 24 Vdc 8 amps

Up to 31 Drops

Remote I/O (Dual Cable)

Electrical Power Supply Input Voltage

Up to Five Housings

Up to Five Housings

0 ... 60°C 0 ... 95% 10 G (11 ms)

Physical Dimensions WxHxD (39.4 x 266 x 203 mm) Space Requirements Weight

2.54 x 10.5 x 8 in Slots 1 and 2 in H8xx-209 housing 8.6 lbs (3.6 kg)

Up to Five Housings

Up to Five Housings

S908 Remote I/O Network

Up to 31 Drops

3-19

Page 19

984-785 Series

The most powerful of Modicon slot-mount PLCs, the 984-785 series, handles mid-range to large applications. For remote I/O, an optional S908 processor is required. The S908 processor supports either single or redundant cable configurations. If you are configuring a remote I/O system, you must also add an S908 Remote I/O Processor (Part # AS-S908-110 or AS-S908120 for single/dual cable configurations) and a Remote I/O cartridge (Part # AS-E908-131 or AS-E908-016). The 984-785 series supports the S911-800 Hot Standby optional processor which increases the performance and functionality of your system. The three models in the series, the PC-D984-785, PC-K984-785, and the PC-E984-785, differ in their power requirements and support for a key switch, as indicated in the following table. A 785 series upgrade kit is available to support a 16 drop Quantum I/O, S908 network.

984-785 Differentiating Features

Local I/O

Model No.

2 Modbus Ports

1 Modbus Plus Port

Key Switch

PC-D984-785 PC-K984-785 PC-E984-785

√ √ √

√ √ √

√ √

Up to Five Housings Max.

3-20

Page 20

984-785 Technical Specifications* PC-D984-785 Architecture Memory User Logic Registers Extended Memory Total I/O Capacity Max. Discrete I/O Max. Analog I/O Local I/O Capacity Total I/O Bits Total I/O Racks Remote I/O Capacity Max. I/O Bits per Drop Max. # Drops Total I/O Bits Max. # ASCII Ports Internal Coils (Includes Disc. I/O) Performance Communication Ports Key Switch

32k 64k 96k 192k

48k 32k 24k 104k

32k 64k 96k 192k

Physical Dimensions, W x H x D Space Requirements Weight

48k 32k 24k 104k

32k 64k 96k 192k

48k 32k 24k 104k

16384 In/16384 Out 1088 In/1088 Out

16384 In/16384 Out 1088 In/1088 Out

1024 In/1024 Out 5

1024 In/1024 Out 5

1024 In/1024 Out 5

512 In/512 Out or 1024 In/1024 Out 31 16 65535 any mix 32 65535 1 ms/k 2 Modbus 1 Modbus Plus Yes

512 In/512 Out or 1024 In/1024 Out 31 16 65535 any mix 32 65535 1 ms/k 2 Modbus 1 Modbus Plus Yes

512 In/512 Out or 1024 In/1024 Out 31 16 65535 any mix 32 65535 1 ms/k 2 Modbus 1 Modbus Plus No

115 Vac 230 Vac 24 Vdc 8 amps

115 Vac 230 Vac 24 Vdc 8 amps

0 ... 60°C 0 ... 95% 10 G (11 ms)

0 ... 60°C 0 ... 95% 10 G (11 ms)

0 ... 60°C 0 ... 95% 10 G (11 ms)

2.54 x 10.5 x 8 in (39.4 x 266 x 203 mm) Slots 1 and 2 in H8xx-209 housing 8.6 lbs (3.6 kg)

2.54 x 10.5 x 8 in (39.4 x 266 x 203 mm) Slots 1 and 2 in H8xx-209 housing 8.6 lbs (3.6 kg)

2.54 x 10.5 x 8 in (39.4 x 266 x 203 mm) Slots 1 and 2 in H8xx-209 housing 8.6 lbs (3.6 kg)

125 Vdc

Environmental Temperature Humidity Shock Resistance

PC-E984-785

16384 In/16384 Out 1088 In/1088 Out

Electrical Power Supply Input Voltage

I/O power capacity

PC-K984-785

24 Vdc 8 amps

7 amps

* A 785 upgrade kit (AM-E785-QK0) is available for 16 drop Quantum I/O, S908 network. See the S908 section on page 2-22 for details.

Remote I/O (Single Cable)

Up to Five Housings

Up to Five Housings S908 Remote I/O Network

Remote I/O

Up to Five Housings

Up to Five Housings Up to 31 Drops

Up to Five

Up to Five

S908 Remote I/O Network

Up to 31 Drops 3-21