The text of a manual · part 1 of 13

984 Programmable Logic Controllers and 800-Series Input/Output Modules, pages 1 to 10

Pages 1 to 10 of 123

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Modicon B807, Modicon B865, AEG B807, Gould B807, Schneider B807, AEG B865, Gould B865 and Schneider B865

Page 1

3

984 Programmable Logic Controllers and 800-Series Input/Output Modules

3-1

Page 2

Benefits of a Full Range, High Performance Family of PLCs

When selecting a PLC system to meet your automation strategy, you have three main goals: 1. Minimize investment to get your system up and running. Many costs are not apparent during system specification, but appear in training, start-up, and upgrades. With a compatible family, you not only reduce costs, you speed system start-up, giving you a faster return on investment.

The Modicon 984 Family helps achieve your goals by offering a full range of high performance, compatible control products. They are full range, providing control solutions for applications requiring 1.5k to 64k of logic memory and 256 to 16,384 discrete I/O points. They provide high performance: 984s solve logic faster than any other full range of programmable logic controllers. They are compatible: 984s share common I/O modules, base instruction sets, programmers, and programming software.

2. Minimize risk of obsolescence when your automation needs change. Because 984 PLCs are a compatible family, you can upgrade the PLC without having to reprogram logic, rewire input/output systems, and retrain your personnel. 3. Maximize system performance. High performance, high quality PLCs ensure high quality systems that efficiently produce high quality products.

3-3

Page 3

Family Compatibility

A family of compatible PLCs reduces some of the “hidden” costs of automating. These are the costs that really add up throughout the life cycle of your automation system, costs incurred when there are delays in training your staff, starting-up your system, or upgrading. Reduce Training Costs To implement a successful control system, programmers, control engineers, and installation personnel must thoroughly understand the system. Training is necessary, but not always productive. Training costs accumulate when you consider the cost of initial training (courses and related expenses), time away from productive work, and the time it takes to become proficient. With Schneider Automation's Modicon 984 Family, your personnel learn only one base instruction set, one system architecture, and one set of programming software. They apply the same skills to the full range of 984 sizes. They become experts at designing, programming, installing, and maintaining the system. You invest in all the costs associated with training just once. This adds up to significant savings. Speed System Start-up Our 984 products have common features to help you save the time and money associated with designing, installing, programming, and debugging a new control system. With the 984's software libraries, you program and debug commonly used functions once. Our software tools allow your engineers to develop libraries of programs for control, diagnostics, alarming, and recipe loading. You can easily incorporate these libraries into new systems, saving development and start-up time. The quicker the start-up, the quicker you produce products, giving you a faster return on investment.

3-4

Easier System Upgrades As your system grows, the control system must also grow. You may need to enhance the system to provide better diagnostics, improve report generation, or monitor and control more I/O. System growth requires more memory, more I/O or both, which can mean replacing the PLC, reprogramming the logic, and even replacing the I/O system. All 984s share common software and base instruction sets. If you need a larger 984 controller, you can load all or part of the existing program into the new 984. Then you install additional I/O, program additional logic, and your system is up and running. Most 984s can accommodate growing memory requirements through modular memory upgrades. This feature eliminates some controller replacements, giving you significant savings when you must add memory to a system. Thus, the 984 Family reduces your risk during initial system specification and reduces development time and equipment costs associated with upgrades.

Page 4

Invest in the Family Concept Without Compromising Performance

An automation strategy built on a compatible family means you make the most of your investment. A strategy built on a high performance family means you operate at peak efficiency, with predictable control. Combine performance and compatibility and you produce higher quality products. Here are some of the high-performance features of the Modicon 984 Family. Fast Scan Optimizes Machine Throughput With scans ranging from .75 ... 5 ms/k, our 984s solve logic faster than any other full family of PLCs. A high-speed remote I/O network communicates at 1.5 megabits per second. Fast logic solving and fast I/O servicing optimize machine or process throughput for better system performance. Powerful Instructions Support Applications Throughout the Plant The 984 has a powerful, full-function instruction set. Its enhanced instructions handle applications like machine control, process control, material handling, report generation, and diagnostics. Process Control Function Library (PCFL) firmware tool further expands the process control capabilities of the 984. Versatile Software Speeds Development Our Modsoft software allows you to program, edit, document, and archive 984 programs using a standard IBM compatible personal computer. On-line and off-line programming features include annotated listings, mnemonic programming, program merge, and more.

3-5

Page 5

984 Functional Overview

How the Control System Works Every 984 control system consists of a PLC linked to input and output modules on the shop floor. These I/O modules are wired to field sensing and switching devices, linking them directly to your application. The 984 controls your application based on data received from the input/output modules connected to devices on the plant floor. Input modules accept electrical signals from field sensing devices and convert them into acceptable voltage levels for CPU processing. Output modules receive electrical signals from the CPU and convert them into voltage or current levels necessary to activate switching devices on the plant floor. The 984's central processing unit solves user logic at very fast, regular intervals, making control predictable. The logic determines what actions to take, based on data received from the input modules. The resulting changes in output states are forwarded to the field. System Memory All 984 memory is based on CMOS technology with battery backup to maintain integrity during power loss. A Memory Protect switch on the controller prevents unauthorized alteration of the user program. Long-life lithium batteries support all memory for up to one year in case of power loss. A 984 system has two types of memory: executive firmware and user logic. Executive firmware resides in nonvolatile memory. User logic, configuration data, and system status data reside in volatile Random Access Memory (RAM) backed up by batteries. User logic is your application; it’s the custom logic you program to control your Application. You use configuration data to define system set-up; it resides in a data table. The input/output status is stored in state RAM. This representation of the current electrical status of the I/O devices is updated each time the PLC scans the user logic. Input/Output Systems Software All 984 PLCs may be programmed with ladder logic, a simple, intuitive, and graphic programming technique. Modicon adds more functionality to its programming in the form of special function blocks. These simple blocks take care of many of the complex programming tasks you require for your application including arithmetic, data transfer, matrix, and bit operations. For more detailed information, Section 6 - Software .

3-6

The application logic that is stored in and solved by the PLC is implemented on the plant floor by input and output modules. I/O modules are field-wired to sensing or switching devices and linked to the PLC over an I/O bus to create a complete control system. I/O subsystems may be local, located together with or in close proximity to the PLC, or remote, located at distances up to 15,000 feet (4.5 km) from the PLC, depending on the cable type. Local I/O communicates to the PLC across a housing backplane or local cables. Up to 5 housings may be connected to any remote I/O drop. Remote I/O communicates through a remote I/O interface installed at each I/O location.

Page 6

Communications Peripheral devices, such as programming panels or host computers, may be connected directly to a 984 PLC through built-in Modbus ports, standard on every 984 PLC. Modbus is an RS 232 based communication protocol used for data acquisition, program editing, and archiving operations. Most 984s include communication ports to link up to Modbus Plus. Modbus Plus is a peer-to-peer, token-bus network with a speed of one megabit per second. Modbus Plus supports data application and programming operations. For more information on communications, refer to the Section 7 - Networking. Most 984 PLCs also have ports to support ASCII communications. For more information on ASCII communications, refer to the I/O portion of this Section.

Ladder logic is a simple and intuitive language that offers power for some of the most complex functions.

3-7

Page 7

Range of 984 Performance

Modicon 984 Family of Programmable Controllers

Controller

Type

User Memory

Data Memory

Discrete I/O Points (Max.)

Register I/O (Max.)

Local Drops

Local Housings

Remote Drops

Scan Time

Modbus ModbusPorts Plus Ports

PC-A984-120

Compact

1.5k

2k

256

32/32

1

4

0

5ms/k

1

0

PC-A984-130

Compact

4k

2k

256

32/32

1

4

0

5ms/k

1

0

PC-A984-131

Compact

4k

2k

256

32/32

1

4

0

5ms/k

2

0

PC-A984-141

Compact

8k

2k

256

32/32

1

4

0

5ms/k

2

0

PC-A984-145

Compact

8k

2k

256

32/32

1

4

0

5ms/k

1

1

PC-E984-241

Compact

8k

2k

256

32/32

1

4

0

2.5ms/k

2†, PC-E984-245

Compact

8k

2k

256

32/32

1

4

0

2.5ms/k

1†

1

PC-E984-251

Compact

16k

24k

256

32/32

1

4

0

2.5ms/k

2†, PC-E984-255

Compact

16k

24k

256

32/32

1

4

0

2.5ms/k

1†

1

PC-E984-381

Slot Mount

16k

2k

512

32/32

1

2

0

3ms/k

2

0

PC-E984-385

Slot Mount

16k

2k

512

32/32

1

2

0

3ms/k

1

1

PC-D984-385

Slot Mount

16k

2k

512

32/32

1

2

0

3ms/k

1

1

PC-E984-480

Slot Mount

16k

2k

2048

224/224

1

2

6

3ms/k

2

0

PC-K984-485

Slot Mount

16k

2k

2048

224/224

1

2

6

3ms/k

1

1

PC-E984-485

Slot Mount

16k

2k

2048

224/224

1

2

6

3ms/k

1

1

PC-E984-685

Slot Mount

16k

10k

8192/8192

1088/1088

1

5

16/31

1ms/k

2

1

PC-D984-785

Slot Mount

32/48k

64/32k

16384/16384

1088/1088

1

5

16/31

1ms/k

2

1

PC-K984-785

Slot Mount

32/48k

64/32k

16384/16384

1088/1088

1

5

16/31

1ms/k

2

1

PC-E984-785

Slot Mount

32/48k

64/32k

16384/16384

1088/1088

1

5

16/31

1ms/k

2

1

P1-984X-008

Chassis Mount

8k

2k

2048

224/224

1

5

6

.75ms/k

2

Optional

Px-984A-xxx

Chassis Mount

16/32k

2k

2048

2032

0, 32

.75ms/k

3

Optional

Px-984B-xxx

Chassis Mount 32/64/128k

10k

8192/8192

2048/2048

0, 32

.75ms/k

3

Optional

AM-0984-AT2

PC/AT bus

16k

2k

2048

224/224

0, 7

1.5ms/k

0

*2

AM-0984-AT4

PC/AT & EISA

32k

32k

2048

1024/1024

0, 16

1.5ms/k

0

*2

AM-0984-MC0

Micro Channel

16k

2k

3584/3584

224/224

0, 7

1.5ms/k

0

1

AM-0984-VM0

VME bus

12k

10k

3584/3584

224/224

0, 7

1.5ms/k

0

1

AM-0984-VM4

VME bus

32k

32k

16384/16384

1024/1024

0, 16

1.5ms/k

0

*2

* Two redundant ports on one controller – one network. † Supports XMIT block, Modbus Master

3-8

Page 8

Optional Processors Increase Performance

Many 984 PLCs support option modules that further extend the flexibility and performance of your control system. The options available include networking with Modbus and Modbus Plus; support for distributed control and hot-standby configurations; and coprocessing. The following chart identifies the options and the PLCs that support them.

Options

Model

Modbus

Modbus Plus

CoPro

Modbus Modem

Hot Standby

Modbus Plus Redundancy

PC-A984-120 PC-A984-130

X X

PC-A984-131

X

PC-A984-141

X

PC-A984-145

X

PC-E984-241

X

PC-E984-245

X

PC-E984-251

X

PC-E984-255

X

PC-E984-381

X

PC-E984-385

X

X

X

PC-D984-385

X

X

X

PC-E984-480

X

PC-K984-485

X

X

X

PC-E984-485

X

X

PC-E984-685

X

X

X

X

X

X

PC-D984-785

X

X

X

X

X

X

PC-K984-785

X

X

X

X

X

X

PC-E984-785

X

X

X

X

X

X

P1-984X-008

X

X

X

X

X

Px-984A-xxx

X

X

X

X

X

Px-984B-xxx

X

X

X

X

X

X X X X

X X

AM-0984-AT2

X

X

AM-0984-AT4

X

X

AM-0984-MC0

X

AM-0984-VM0

X

AM-0984-VM4

X

X

Note: For information on the communication options, see the Communication Section. For information on remote input/output processing, see the section on Configuring A Remote I/O System in the 800 Series I/O section. For other options, see the appropriate PLC description.

3-9

Page 9

984 Instruction Set

Slot-Mount Included

Chassis-Mount

Optional Loadables

Included

Optional Loadables

Category

Instructions

Contacts

NO, NC, Pos Trans, Neg Trans

X

Coils

Normal, Latch

X

X

Timers

1.0, 0.1, 0.01 Sec

X

X

Counters

Up/Down

X

X

Arithmetic (4-digit)

Add, Sub, Mult, Div

X

X

Sq Root, Process Sq Root,

X

X X

X

Log, Anti-log Arithmetic (Dbl Prec)

Add, Sub, Mult, Div

X

Arithmetic (Fl Pt)

Add, Sub, Mult, Div, Comp,

X

Sq Root, Log, Natural Log, Exponential Trig

Sin, Cos, Tan, Arcsin,

X

Arccos, Arctan Math Conv.

Fl Pt->Int, Int->Fl Pt, Deg->Rad,

X

Deg->Rad, Change Sign Move

Reg->Table, Table->Reg,

X

X

Table->Table, Block Move, Search, First In, First Out Table->Block, Block->Table

X

Subroutines

Jump to Sub, Lavel, Return

X

Drum Sequencer

Drum, Input Compare

Matrix

And, Or, XOR, Somplement,

X X

X

X

X X

Compare Bit

Bit Modify, Bit Sense, Bit Rotate

X

ASCII

Read, Write

X1

X

Diagnostics

Status

X

X

Event Alarm Recording Scan Ops

Skip Network(s), Constant Sweep,

X X

X X

Single Sweep, Segment Scheduler Other

PID

X

X

Checksum

X2

X2

Modbus Plus (MSTR)

X3

X3

Custom Loadable

X

Option Processor

Hot Standby (HSBY)

X4

Support

C996 DOS CoPro (CALL)

X4

C986 CoPro (CALL) Process Control

A_IN, ALARM, A_OUT, AVER,

Function Library

CALC, EQN, DELAY, FNGEN,

(PCFL)

INTEG, LIMIT, L_LAG, LIM_V,

X X5

MODE, ONOFF, PID, RAMP, RMPLN, RATE, SEL 16 Bit Math

TEST, AD16, SU16, MU16, DV16, ITOF, FTOI

X5

1. Available in controllers which support remote I/O capability (984-48x, 685, 785) 2. Available in controllers without built-in Modbus Plus support 3. Available in controllers with built-in or optional Modbus Plus support (these controllers do not support Checksum function) 4. Available in controllers which support option processors (984-685, 785) 5. Available in the 685 and 785 only.

3-10

X

Page 10

Compact Category Contacts

Instructions NO, NC, Pos Trans,

Included X

ModConnect

Optional Loadables

Included X

Optional Loadables

Neg Trans Coils

Normal, Latch

X

X

Timers

1.0, 0.1, 0.01 Sec

X

X

Counters

Up/Down

X

X

Arithmetic (4-digit)

Add, Sub, Mult, Div

X

X

Sq Root, Process Sq Root,

X

X

Log, Anti-log Arithmetic (Dbl Prec)

Add, Sub, Mult, Div

X

X

Arithmetic (Fl Pt)

Add, Sub, Mult, Div,

X

X

X

X

X

X

X

X

X

X

X

X

Comp, Sq Root, Log, Natural Log, Exponential Trig

Sin, Cos, Tan, Arcsin, Arccos, Arctan

Math Conv.

Fl Pt->Int, Int->Fl Pt, Deg->Rad, Rad->Deg, Change Sign

Move

Reg->Table, Table->Reg, Table->Table, Block Move, Search, First In, First Out Table->Block, Block->Table

Subroutines

Jump to Sub, Lavel, Return

Drum Sequencer

Drum, Input Compare

Matrix

And, Or, XOR,

Bit

Bit Modify, Bit Sense,

X

X

X

X

X

X

Complement, Compare Bit Rotate ASCII

Read, Write

Diagnostics

Status

X X

Event Alarm Recording Scan Ops

Skip Network(s),

X X

X

X

X

PID

X

X

Checksum

X1

Modbus Plus (MSTR)

X2

Constant Sweep, Single Sweep, Segment Scheduler Other

Custom Loadable Option Processor Support

X X

X

Hot Standby (HSBY) C996 DOS CoPro (CALL) C986 CoPro (CALL)

1. Available in controllers without built-in Modbus Plus support 2. Available in controllers with built-in or optional Modbus Plus support (these controllers do not support Checksum function)

3-11