The text of a manual · part 1 of 13
984 Programmable Logic Controllers and 800-Series Input/Output Modules, pages 1 to 10
Pages 1 to 10 of 123
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B807, Modicon B865, AEG B807, Gould B807, Schneider B807, AEG B865, Gould B865 and Schneider B865
Page 1
3
984 Programmable Logic Controllers and 800-Series Input/Output Modules
3-1
Page 2
Benefits of a Full Range, High Performance Family of PLCs
When selecting a PLC system to meet your automation strategy, you have three main goals: 1. Minimize investment to get your system up and running. Many costs are not apparent during system specification, but appear in training, start-up, and upgrades. With a compatible family, you not only reduce costs, you speed system start-up, giving you a faster return on investment.
The Modicon 984 Family helps achieve your goals by offering a full range of high performance, compatible control products. They are full range, providing control solutions for applications requiring 1.5k to 64k of logic memory and 256 to 16,384 discrete I/O points. They provide high performance: 984s solve logic faster than any other full range of programmable logic controllers. They are compatible: 984s share common I/O modules, base instruction sets, programmers, and programming software.
2. Minimize risk of obsolescence when your automation needs change. Because 984 PLCs are a compatible family, you can upgrade the PLC without having to reprogram logic, rewire input/output systems, and retrain your personnel. 3. Maximize system performance. High performance, high quality PLCs ensure high quality systems that efficiently produce high quality products.
3-3
Page 3
Family Compatibility
A family of compatible PLCs reduces some of the “hidden” costs of automating. These are the costs that really add up throughout the life cycle of your automation system, costs incurred when there are delays in training your staff, starting-up your system, or upgrading. Reduce Training Costs To implement a successful control system, programmers, control engineers, and installation personnel must thoroughly understand the system. Training is necessary, but not always productive. Training costs accumulate when you consider the cost of initial training (courses and related expenses), time away from productive work, and the time it takes to become proficient. With Schneider Automation's Modicon 984 Family, your personnel learn only one base instruction set, one system architecture, and one set of programming software. They apply the same skills to the full range of 984 sizes. They become experts at designing, programming, installing, and maintaining the system. You invest in all the costs associated with training just once. This adds up to significant savings. Speed System Start-up Our 984 products have common features to help you save the time and money associated with designing, installing, programming, and debugging a new control system. With the 984's software libraries, you program and debug commonly used functions once. Our software tools allow your engineers to develop libraries of programs for control, diagnostics, alarming, and recipe loading. You can easily incorporate these libraries into new systems, saving development and start-up time. The quicker the start-up, the quicker you produce products, giving you a faster return on investment.
3-4
Easier System Upgrades As your system grows, the control system must also grow. You may need to enhance the system to provide better diagnostics, improve report generation, or monitor and control more I/O. System growth requires more memory, more I/O or both, which can mean replacing the PLC, reprogramming the logic, and even replacing the I/O system. All 984s share common software and base instruction sets. If you need a larger 984 controller, you can load all or part of the existing program into the new 984. Then you install additional I/O, program additional logic, and your system is up and running. Most 984s can accommodate growing memory requirements through modular memory upgrades. This feature eliminates some controller replacements, giving you significant savings when you must add memory to a system. Thus, the 984 Family reduces your risk during initial system specification and reduces development time and equipment costs associated with upgrades.
Page 4
Invest in the Family Concept Without Compromising Performance
An automation strategy built on a compatible family means you make the most of your investment. A strategy built on a high performance family means you operate at peak efficiency, with predictable control. Combine performance and compatibility and you produce higher quality products. Here are some of the high-performance features of the Modicon 984 Family. Fast Scan Optimizes Machine Throughput With scans ranging from .75 ... 5 ms/k, our 984s solve logic faster than any other full family of PLCs. A high-speed remote I/O network communicates at 1.5 megabits per second. Fast logic solving and fast I/O servicing optimize machine or process throughput for better system performance. Powerful Instructions Support Applications Throughout the Plant The 984 has a powerful, full-function instruction set. Its enhanced instructions handle applications like machine control, process control, material handling, report generation, and diagnostics. Process Control Function Library (PCFL) firmware tool further expands the process control capabilities of the 984. Versatile Software Speeds Development Our Modsoft software allows you to program, edit, document, and archive 984 programs using a standard IBM compatible personal computer. On-line and off-line programming features include annotated listings, mnemonic programming, program merge, and more.
3-5
Page 5
984 Functional Overview
How the Control System Works Every 984 control system consists of a PLC linked to input and output modules on the shop floor. These I/O modules are wired to field sensing and switching devices, linking them directly to your application. The 984 controls your application based on data received from the input/output modules connected to devices on the plant floor. Input modules accept electrical signals from field sensing devices and convert them into acceptable voltage levels for CPU processing. Output modules receive electrical signals from the CPU and convert them into voltage or current levels necessary to activate switching devices on the plant floor. The 984's central processing unit solves user logic at very fast, regular intervals, making control predictable. The logic determines what actions to take, based on data received from the input modules. The resulting changes in output states are forwarded to the field. System Memory All 984 memory is based on CMOS technology with battery backup to maintain integrity during power loss. A Memory Protect switch on the controller prevents unauthorized alteration of the user program. Long-life lithium batteries support all memory for up to one year in case of power loss. A 984 system has two types of memory: executive firmware and user logic. Executive firmware resides in nonvolatile memory. User logic, configuration data, and system status data reside in volatile Random Access Memory (RAM) backed up by batteries. User logic is your application; it’s the custom logic you program to control your Application. You use configuration data to define system set-up; it resides in a data table. The input/output status is stored in state RAM. This representation of the current electrical status of the I/O devices is updated each time the PLC scans the user logic. Input/Output Systems Software All 984 PLCs may be programmed with ladder logic, a simple, intuitive, and graphic programming technique. Modicon adds more functionality to its programming in the form of special function blocks. These simple blocks take care of many of the complex programming tasks you require for your application including arithmetic, data transfer, matrix, and bit operations. For more detailed information, Section 6 - Software .
3-6
The application logic that is stored in and solved by the PLC is implemented on the plant floor by input and output modules. I/O modules are field-wired to sensing or switching devices and linked to the PLC over an I/O bus to create a complete control system. I/O subsystems may be local, located together with or in close proximity to the PLC, or remote, located at distances up to 15,000 feet (4.5 km) from the PLC, depending on the cable type. Local I/O communicates to the PLC across a housing backplane or local cables. Up to 5 housings may be connected to any remote I/O drop. Remote I/O communicates through a remote I/O interface installed at each I/O location.
Page 6
Communications Peripheral devices, such as programming panels or host computers, may be connected directly to a 984 PLC through built-in Modbus ports, standard on every 984 PLC. Modbus is an RS 232 based communication protocol used for data acquisition, program editing, and archiving operations. Most 984s include communication ports to link up to Modbus Plus. Modbus Plus is a peer-to-peer, token-bus network with a speed of one megabit per second. Modbus Plus supports data application and programming operations. For more information on communications, refer to the Section 7 - Networking. Most 984 PLCs also have ports to support ASCII communications. For more information on ASCII communications, refer to the I/O portion of this Section.
Ladder logic is a simple and intuitive language that offers power for some of the most complex functions.
3-7
Page 7
Range of 984 Performance
Modicon 984 Family of Programmable Controllers
Controller
Type
User Memory
Data Memory
Discrete I/O Points (Max.)
Register I/O (Max.)
Local Drops
Local Housings
Remote Drops
Scan Time
Modbus ModbusPorts Plus Ports
PC-A984-120
Compact
1.5k
2k
256
32/32
1
4
0
5ms/k
1
0
PC-A984-130
Compact
4k
2k
256
32/32
1
4
0
5ms/k
1
0
PC-A984-131
Compact
4k
2k
256
32/32
1
4
0
5ms/k
2
0
PC-A984-141
Compact
8k
2k
256
32/32
1
4
0
5ms/k
2
0
PC-A984-145
Compact
8k
2k
256
32/32
1
4
0
5ms/k
1
1
PC-E984-241
Compact
8k
2k
256
32/32
1
4
0
2.5ms/k
2†, PC-E984-245
Compact
8k
2k
256
32/32
1
4
0
2.5ms/k
1†
1
PC-E984-251
Compact
16k
24k
256
32/32
1
4
0
2.5ms/k
2†, PC-E984-255
Compact
16k
24k
256
32/32
1
4
0
2.5ms/k
1†
1
PC-E984-381
Slot Mount
16k
2k
512
32/32
1
2
0
3ms/k
2
0
PC-E984-385
Slot Mount
16k
2k
512
32/32
1
2
0
3ms/k
1
1
PC-D984-385
Slot Mount
16k
2k
512
32/32
1
2
0
3ms/k
1
1
PC-E984-480
Slot Mount
16k
2k
2048
224/224
1
2
6
3ms/k
2
0
PC-K984-485
Slot Mount
16k
2k
2048
224/224
1
2
6
3ms/k
1
1
PC-E984-485
Slot Mount
16k
2k
2048
224/224
1
2
6
3ms/k
1
1
PC-E984-685
Slot Mount
16k
10k
8192/8192
1088/1088
1
5
16/31
1ms/k
2
1
PC-D984-785
Slot Mount
32/48k
64/32k
16384/16384
1088/1088
1
5
16/31
1ms/k
2
1
PC-K984-785
Slot Mount
32/48k
64/32k
16384/16384
1088/1088
1
5
16/31
1ms/k
2
1
PC-E984-785
Slot Mount
32/48k
64/32k
16384/16384
1088/1088
1
5
16/31
1ms/k
2
1
P1-984X-008
Chassis Mount
8k
2k
2048
224/224
1
5
6
.75ms/k
2
Optional
Px-984A-xxx
Chassis Mount
16/32k
2k
2048
2032
0, 32
.75ms/k
3
Optional
Px-984B-xxx
Chassis Mount 32/64/128k
10k
8192/8192
2048/2048
0, 32
.75ms/k
3
Optional
AM-0984-AT2
PC/AT bus
16k
2k
2048
224/224
0, 7
1.5ms/k
0
*2
AM-0984-AT4
PC/AT & EISA
32k
32k
2048
1024/1024
0, 16
1.5ms/k
0
*2
AM-0984-MC0
Micro Channel
16k
2k
3584/3584
224/224
0, 7
1.5ms/k
0
1
AM-0984-VM0
VME bus
12k
10k
3584/3584
224/224
0, 7
1.5ms/k
0
1
AM-0984-VM4
VME bus
32k
32k
16384/16384
1024/1024
0, 16
1.5ms/k
0
*2
* Two redundant ports on one controller – one network. † Supports XMIT block, Modbus Master
3-8
Page 8
Optional Processors Increase Performance
Many 984 PLCs support option modules that further extend the flexibility and performance of your control system. The options available include networking with Modbus and Modbus Plus; support for distributed control and hot-standby configurations; and coprocessing. The following chart identifies the options and the PLCs that support them.
Options
Model
Modbus
Modbus Plus
CoPro
Modbus Modem
Hot Standby
Modbus Plus Redundancy
PC-A984-120 PC-A984-130
X X
PC-A984-131
X
PC-A984-141
X
PC-A984-145
X
PC-E984-241
X
PC-E984-245
X
PC-E984-251
X
PC-E984-255
X
PC-E984-381
X
PC-E984-385
X
X
X
PC-D984-385
X
X
X
PC-E984-480
X
PC-K984-485
X
X
X
PC-E984-485
X
X
PC-E984-685
X
X
X
X
X
X
PC-D984-785
X
X
X
X
X
X
PC-K984-785
X
X
X
X
X
X
PC-E984-785
X
X
X
X
X
X
P1-984X-008
X
X
X
X
X
Px-984A-xxx
X
X
X
X
X
Px-984B-xxx
X
X
X
X
X
X X X X
X X
AM-0984-AT2
X
X
AM-0984-AT4
X
X
AM-0984-MC0
X
AM-0984-VM0
X
AM-0984-VM4
X
X
Note: For information on the communication options, see the Communication Section. For information on remote input/output processing, see the section on Configuring A Remote I/O System in the 800 Series I/O section. For other options, see the appropriate PLC description.
3-9
Page 9
984 Instruction Set
Slot-Mount Included
Chassis-Mount
Optional Loadables
Included
Optional Loadables
Category
Instructions
Contacts
NO, NC, Pos Trans, Neg Trans
X
Coils
Normal, Latch
X
X
Timers
1.0, 0.1, 0.01 Sec
X
X
Counters
Up/Down
X
X
Arithmetic (4-digit)
Add, Sub, Mult, Div
X
X
Sq Root, Process Sq Root,
X
X X
X
Log, Anti-log Arithmetic (Dbl Prec)
Add, Sub, Mult, Div
X
Arithmetic (Fl Pt)
Add, Sub, Mult, Div, Comp,
X
Sq Root, Log, Natural Log, Exponential Trig
Sin, Cos, Tan, Arcsin,
X
Arccos, Arctan Math Conv.
Fl Pt->Int, Int->Fl Pt, Deg->Rad,
X
Deg->Rad, Change Sign Move
Reg->Table, Table->Reg,
X
X
Table->Table, Block Move, Search, First In, First Out Table->Block, Block->Table
X
Subroutines
Jump to Sub, Lavel, Return
X
Drum Sequencer
Drum, Input Compare
Matrix
And, Or, XOR, Somplement,
X X
X
X
X X
Compare Bit
Bit Modify, Bit Sense, Bit Rotate
X
ASCII
Read, Write
X1
X
Diagnostics
Status
X
X
Event Alarm Recording Scan Ops
Skip Network(s), Constant Sweep,
X X
X X
Single Sweep, Segment Scheduler Other
PID
X
X
Checksum
X2
X2
Modbus Plus (MSTR)
X3
X3
Custom Loadable
X
Option Processor
Hot Standby (HSBY)
X4
Support
C996 DOS CoPro (CALL)
X4
C986 CoPro (CALL) Process Control
A_IN, ALARM, A_OUT, AVER,
Function Library
CALC, EQN, DELAY, FNGEN,
(PCFL)
INTEG, LIMIT, L_LAG, LIM_V,
X X5
MODE, ONOFF, PID, RAMP, RMPLN, RATE, SEL 16 Bit Math
TEST, AD16, SU16, MU16, DV16, ITOF, FTOI
X5
1. Available in controllers which support remote I/O capability (984-48x, 685, 785) 2. Available in controllers without built-in Modbus Plus support 3. Available in controllers with built-in or optional Modbus Plus support (these controllers do not support Checksum function) 4. Available in controllers which support option processors (984-685, 785) 5. Available in the 685 and 785 only.
3-10
X
Page 10
Compact Category Contacts
Instructions NO, NC, Pos Trans,
Included X
ModConnect
Optional Loadables
Included X
Optional Loadables
Neg Trans Coils
Normal, Latch
X
X
Timers
1.0, 0.1, 0.01 Sec
X
X
Counters
Up/Down
X
X
Arithmetic (4-digit)
Add, Sub, Mult, Div
X
X
Sq Root, Process Sq Root,
X
X
Log, Anti-log Arithmetic (Dbl Prec)
Add, Sub, Mult, Div
X
X
Arithmetic (Fl Pt)
Add, Sub, Mult, Div,
X
X
X
X
X
X
X
X
X
X
X
X
Comp, Sq Root, Log, Natural Log, Exponential Trig
Sin, Cos, Tan, Arcsin, Arccos, Arctan
Math Conv.
Fl Pt->Int, Int->Fl Pt, Deg->Rad, Rad->Deg, Change Sign
Move
Reg->Table, Table->Reg, Table->Table, Block Move, Search, First In, First Out Table->Block, Block->Table
Subroutines
Jump to Sub, Lavel, Return
Drum Sequencer
Drum, Input Compare
Matrix
And, Or, XOR,
Bit
Bit Modify, Bit Sense,
X
X
X
X
X
X
Complement, Compare Bit Rotate ASCII
Read, Write
Diagnostics
Status
X X
Event Alarm Recording Scan Ops
Skip Network(s),
X X
X
X
X
PID
X
X
Checksum
X1
Modbus Plus (MSTR)
X2
Constant Sweep, Single Sweep, Segment Scheduler Other
Custom Loadable Option Processor Support
X X
X
Hot Standby (HSBY) C996 DOS CoPro (CALL) C986 CoPro (CALL)
1. Available in controllers without built-in Modbus Plus support 2. Available in controllers with built-in or optional Modbus Plus support (these controllers do not support Checksum function)
3-11