Page 31

984B

984B / S908 Single Cable Remote I/O Network

The 984B PLC is designed for applications that need a high performance PLC with large memory requirements. You can enhance the controller's user logic memory capacity with up to 96k of extended data memory. The 984B's S908 Remote Input/Output Processor supports up to 32 drops of 800-Series remote I/O. You can choose to add option processing to your 984B system. You can configure a Hot Standby system by adding the R911000 Hot Standby system. You can also increase your system speed and processing power by adding up to three C986 CoProcessors. Communication options are described in Section 7: Networking.

3-32

Up to 32 drops

Page 32

984B Technical Specifications

984B / S908 Dual Cable Remote I/O Network

Architecture Memory User Logic Registers Extended Memory Registers Total I/O Capacity Max. Discrete I/O Max. Analog I/O Total I/O Bits Local I/O Capacity Remote I/O Capacity Max. I/O Bits per Drop Max. # Drops Total I/O Bits Max. # ASCII Ports Internal Coils Logic Solve Speed Communication Ports Electrical Power Supply Input Voltage I/O Power Capacity Environmental Temperature Humidity Shock Resistance Dimensions (WxHxD) 4-slot Chassis 7-slot Chassis

32k 9999 up to 96k 42 ... 138k

64k 9999 up to 96k 74 ... 138k

8192 In / 8192 Out 2048 In / 2048 Out 32,768 In/32,768 Out N/A 1024 In/1024 Out 32 32,768 In /32,768 Out 32 8192 .75 ms/k 3 Modbus 1 Simple ASCII In/Out

115 Vac 230 Vac N/A 0 ... 60°C 0 ... 95% non-condensing 10 G (11 ms) 11.6 x 19.2 x 10.2 in (295 x 488 x 259 mm) 17.3 x 19.2 x 10.2 in (440 x 448 x 259 mm)

Weight Up to 32 drops

4-slot Chassis 7-slot Chassis

46 lbs (21 kg) 55 lbs (25 kg)

3-33

Page 33

984X

Local I/O Configuration

The 984X PLC is designed for applications requiring a high performance PLC with medium memory requirements. The 984X supports one drop of local 800 Series I/O and up to 6 remote 800-Series I/O drops. The ability to communicate to remote I/O is facilitated by the S908 communications protocol, a functionality which is built into the mainframe. This feature supports a single cable network with up to six drops of remote I/O. The 984X also supports as many as two option modules. You can configure a Hot Standby system by adding the R911-000 Hot Standby Processor or you can increase your system speed and processing power by adding as many as two C986 CoProcessors. Communications options are described in Section 7: Networking.

3-34

Page 34

984X Technical Specifications

Remote I/O Configuration Architecture

Memory User Logic Registers Total I/O Capacity Max. Discrete I/O Max. Analog I/O Local I/O Capacity Total I/O Bits Total I/O Racks Remote I/O Capacity Max. I/O Bits per Drop Max. # Drops Total I/O Bits Max. # ASCII Ports Internal Coils Logic Solve Speed Communication Ports Electrical Power Supply Input Voltage I/O Power Capacity Environmental Temperature Humidity Shock Resistance Dimensions (WxHxD) 4-slot Chassis

8K 1920 10K 2048 any mix 224 In/224 Out 512 In /512 Out 5 512 In/512 Out 6 3584 In/3584 Out 12 2048 .75 ms/k 2 Modbus

115 Vac 230 Vac N/A 0 ... 60°C 0 ... 95% (non-condensing) 10 G (11 ms) 11.6 x 19.2 x 10.2 in (295 x 488 x 259 mm)

Weight 4-slot Chassis

46 lbs (21 kg)

Up to 32 drops

3-35

Page 35

ModConnect AT2-984 or AT4-984 PLC for AT bus/EISA Personal Computers and EISA Workstations

The AT-984 is offered in two models, AT2-984 and AT4-984, and both are full functionality 984 PLCs that mount into a single slot of an IBM-AT personal computer, EISA personal computer, EISA RISC workstation or compatible. It acts as a powerful logic coprocessor for the personal computer or workstation by scanning I/O and solving 984 logic programs while the computer handles data processing and man-machine interface requirements. AT-984 Software Support The AT-984 PLC’s NetBIOS interface for DOS and OS/2 is the same interface used on the SA85 AT bus, the SM85 Micro Channel Modbus Plus, and MC-984 Micro Channel controller boards. It supports many existing applications including: • Modicon Modsoft Programming and Documentation Software • Integrated software architecture to speed application development (AT4-984 only) • Peer Cop Process Control Function Library (PCFL) • Modicon FactoryLink Man-Machine Interface Software • Modicon P230 Emulation Software • Modicon MBPSTAT program for monitoring Modbus Plus networks • Other third party programming Panel Software, MMI software, and operating system device drivers for Modbus Plus Software Tools for Developing Custom Applications Included with every AT-984 PLC are sample programs and a C library. They allow the development of custom applications to suit your unique requirements.

3-36

Page 36

AT2-984 Technical Specifications Part Number AM-0984-AT2* AT-984 processor board and support software Architecture Memory User Logic1 Registers2 Total I/O Capacity Max. Discrete I/O Max. Analog I/O Local I/O Capacity Remote I/O Protocol Remote I/O Capacity Max I/O Bits per Drop4 Max. Drops Max Cable Distance Total I/O Bits Max. # ASCII Ports Max Internal Coils3 Performance Communication Ports Time of Day Clock Physical Hardware Software Software Media Documentation Optional Supporting Documentation Host Software Information Operating System C Library AT-984 Boards per Computer Selectable Options Battery LED Indicators Power Size (HxD) Weight Net Shipping Environmental Temperature Operating Storage Humidity Shock

1

16k 1920 18k 2048 any mix 224 in/224 out N/A S908 protocol 512 in/512 out 7 4,000 ft. 3548 in/3548 out 14 2048 1.5 ms/K words 1 Redundant Modbus Plus Port, 1 R10 ± 8.0 sec/day accuracy @ 60°C AT-984 processor board NetBIOS device driver for DOS and OS/2, NETLIB.C C library, TESTXX.C sample programs, MBPSTAT diagnostic 5 1/4 inch, 360k diskettes, 3 1/2 inch, 720k diskette GM-HBDS-001 IBM Host-based Devices Users Guide GM-0984-SYS Systems Manual, GM-MBPL-001 Modbus Plus Network Planning and Installation Guide MS-DOS Ver. 3.1 or higher, OS/2 Ver. 1.3 or higher IBM C V1.1 2 any type; SA85, AT-984 Address, memory, interrupts (DIP switches & jumpers) 2430 coin type lithium None 750 mA typical Standard full-size AT card 4.5 x 13.3 in (114 x 338 mm) 1.0 lbs (.45 kg) 2.0 lbs (.9 kg)

0 ... 60°C -40 to 80°C 0 to 95% (non-condensing) 10 G’s for 11 msec

Deduct approximately 1k words for system overhead

2

Includes analog/register I/O and internal register space

3

Includes discrete I/O and internal coils

4

Each discrete I/O points requires 1 bit, each analog/register point requires 16 bits

* Redundant Modbus Plus Cable

3-37

Page 37

AT4-984 Technical Specifications Part Number AM-0984-AT4*AT-984 processor board and support software Architecture Memory User Logic1 Registers2 Total Logic Solve Time Input/Output I/O Series I/O Capacity Max Discrete I/O3 Max Analog I/O3 Total Drops Remote IOP S908/800:

32k 32,224 64k 1.5 ms/K 800/500/2005 16,384 in/16,384 out 1024 in/1024 out 16 Remote I/O Interface I/O Bits4 Drop Remote I/O Interface I/O Bits4 Drop Cable Distance ASCII Ports:

S908/200:

I/O Modules per Drop 1

Deduct approximately 1k words for system overhead

2

Includes Analog/Register I/O and Internal Register Space

3

Each Analog/Register I/O Point requires 16 bits

J890/J892 P890/P892 1024/1024 J290/J291 256/256 4000 feet 2/Drop 32/System 32

4

Each Discrete I/O Point requires 1 bit. Each Analog/Register I/O Point requires 16 bits 5

500-Series I/O Modules via P45x/J540 Interface (Discrete only)

Communications – Modbus Plus Speed Mode Number of Nodes on One Network Media Distance

1 Megabit per second Peer-to-Peer 64 with one repeater Twisted Pair 1500 ft./section without repeaters 6000 ft./(Max.) between any two nodes with repeaters Two 9-Pin D for cable redundancy

Connectors Instructions Language Instructions Arithmetic Data Transfer

Matrix Bit Operations ASCII Enhanced Instructions

• • • • • • • • • • • • • • • • • • • • • •

Ladder Logic/Function Block Relays – NO, NC, Transitional Timers – 1.0, 0.1, 0.01 sec. Counters – Up, Down 4-digit Add, Sub, Mult, Div 4-digit BCD values Register-to-Table Table-to-Table Block Move First-In, First-Out Search, Status Logical AND, OR, Exclusive OR Compare and Complement Bit Modify, Bit Sense, and Bit Rotate Read and Write Functions up to 32 ASCII Ports Table to Block Double Precision Math: Add, Sub, Mult, Div Floating Point Math: Add, Sub, Mult, Div, Compare, Sq Root Trigonometric Sin, Cos, Tan, Deg to Rad PID2 Skip Constant Scan

* Redundant Modbus Plus Cable

3-38

• • • •

Subroutine MSTR for Modbus Plus CKSUM 16 bit signed/unsigned math Add Div. Sub Int. to Float Mult Float to Integer Test = ,>,< • PCFL Optional Software • FNxx Custom Loadable Loadables • DRUM and ICMP Drum Sequencer Segment Scheduler Segment scheduler – I/O Scan optimization allows selection of I/O update sequence for time-critical applications Diagnostics Power-Up diagnostics: CPU, RAM/ROM, Communications Continuous per Scan: CPU, I/O Module Health, State Table Memory, Detection of error causes an orderly shut-down of the controller and logging of error type Time of Day Clock 1 year battery backed. Accuracy ±8.0 sec./Day 0-60˚ Logic Word Size – 24 Bits Memory – Battery backed for 1 year Environmental Characteristics Ambient Temperature Humidity Shock Vibration RFI/EMI Emission RFI/EMI Susceptibility UL Listing CSA Listing Part Number Description Included

Operating System C Library Selectable Options Battery Indicators Power Size Weight

0-60˚C –40 to 80˚C 0-95% non-condensing 10G's for 11 msec .625 @ 50-500 Hz Complies with applicable FCC requirements ML-STD-461B CS02-Conducted RS03-Radiated Approval Pending Approval Pending AM-0984-AT4 AT-984 Programmable Controller for AT and EISA-bus AT-984 board Media: 5-1/4" 360K 3-1/2" 720K diskettes NETBIOS Drive NETLIB.CC Library TESTXX.C Sample Programs MBPSTAT Diagnostic GM-HBDS-001 Manual, IBM Host Based Devices Users Guide MS-DOS ver. 3.1 or higher Microsoft C 5.1, Large Model DESCview 2.24 Station Address, Memory and Interrupts are all set by dip switches and jumpers 2430 coin type lithium LEDs provided for installation: RIO, Modbus Plus, and Run 750mA Typ, 1.1A Max. Standard AT Card 4.5" high, 13.3" long Net 1.0 lbs Shipping 2.0 lbs

Optional Supporting Documentation

GM-0984-SYS Modicon 984 Programmable Controller Systems Manual. GM-MBPL-001 Modicon Modbus Plus Network Planning and Installation Guide

Page 38

R911-000 Hot Standby System for Chassis-Mount PLCs

If your application requires fault tolerance and high availability, consider the hot standby option, available on 984A, 984B, and 984X PLCs. NOTE: The 984X should be configured with remote I/O only when used with the R911 HSP. A hot standby system provides backup control in case of a failure. Two identically-configured 984 PLCs communicate with each other via R911 Hot Standby Modules located in each PLC. Each PLC also has a loadable hot standby instruction block (HSBY), programmed into its user logic, which communicates status information between the two PLCs. One of the PLCs in the hot standby system operates as the primary PLC. It reads input data from the remote input/output drops, executes ladder logic, and sends output commands back to the drops. The primary PLC continuously updates the standby PLC with system status information at the end of each logic solve. In normal conditions, the standby PLC does not perform control functions; it merely processes status information. However, if the primary PLC fails, the standby PLC assumes primary control functions within 48 milliseconds of the failure. To configure an S911 Hot Standby System, you need, in addition to PLCs and input/output drops : •

R911 Hot Standby Processors in each PLC

•

S908 or S929 Remote Input/Output Processors in each PLC

•

W911 cable (6 ft. and 12 ft. lengths)

•

Redundancy terminator kit

•

Two 75 ohm self-terminating connectors

Ordering Information

• One MA-0186-000 coaxial line splitter

For ordering Hot Standby systems, single part numbers are available combining appropriate components: – HSBY Function Block Software – Two R911 Processor Boards – One W911 Cable – One Redundancy Terminator Kit – One MA-0186-000 Coaxial Splitter AS-911K-106 AS-911K-112

Kit with 6 foot W911 Cable Kit with 12 foot W911 Cable

3-39

Page 39

984 / R911 Hot Standby System (Dual Cable is Optional)

R911 Hot Standby Technical Specifications Configuration Information PLCs that use R911 Part #, HSBY Function Block Data Exchange Rate Worst Case Switchover Time Power Source

984A, 984B, 984X SW-AP9X-RXA 10 megabits/sec 13 ... 48 milliseconds Mainframe PLC power supply

Environmental Operating Temperature Relative Humidity Shock Resistance

0 ... 60°C 0 ... 95% (non-condensing) 10G (11 ms)

Physical Space Requirements One option slot in chassis Max. Distance Between PLCs 30 ft (9 m) Weight

3-40

4.5 lbs (2 kg)

Page 40

C986 Integrated Control Processor

The C986 Integrated Control Processor, or CoPro, provides the power to solve problems that are difficult or inefficient to do in ladder logic, by extending the processing capabilities of 984 chassis-mount PLCs (984A, 984B, and 984X). This makes the CoPro option perfect for complex tasks such as floating point arithmetic, serial communications, or data concentration. Using the VRTX Operating System, the CoPro can increase system performance through its multiprocessing and flexible multi-tasking capabilities. The CoPro can handle up to 10 independent tasks simultaneously. It contains a processor and math coprocessor chip as well as 768k RAM to offload the main PLC from data intensive operations. You can expand the processing capabilities of your system three-fold by installing up to three CoPro's in a 984 mainframe (two in a 984X). One instruction integrates computing power into the control system. The CoPro's simple interface to the ladder logic program is a software function block, CALL, which invokes the C986 program's operation. An optional mass storage device provides extensive, nonvolatile data storage for the 984 enhanced with the CoPro. The storage device is packaged in a shock resistant enclosure to minimize internal vibration. This M986 Mass Storage Device includes a 40 Mbyte hard disk drive, 360 kbyte floppy disk drive, and a cable from C986 Integrated Control Processor to the M986 Mass Storage Device.

Call Function Block Ladder Logic Interface to C Language Tasks

3-41