Page 41

C986 Technical Specifications Configuration Information PLCs with C986 Option Power Source Architecture

984A, 984B, 984X Mainframe power supply

Processor Chip Math Coprocessor Chip Operating System Language Memory

80186 8087 VRTX multi-tasking op. sys. "C" programming language

Program & Data Data Environmental

256 kbyte battery-backed RAM 512 kbyte dynamic RAM

Operating Temperature Storage Temperature Relative Humidity Shock Resistance Physical

0 ... 60°C -40 to 80°C 0 ... 95% (non-condensing) 10G (11 ms)

Space Requirements Weight

1 option slot in chassis 4.6 lbs (2.1 kg)

984 System with C986 CoPro

3-42

Page 42 read from a scan by OCR; it may hold reading errors

800-Series Input/Output Modules ice, elt hah Livro PUL BEC ata

"alah gt Se a

3-43

Page 43

3-44

Page 44

Overview

The Modicon 800-Series input/output modules offer one of the industry’s widest ranges of I/O modules. Their dependability has been proven in thousands of applications worldwide. With over 50 modules to choose from, you can select the most costeffective module for field device requirements. The Modicon I/O Family offers discrete, analog, special purpose and intelligent modules to meet the most demanding I/O and process control needs: •

Discrete In – which convert signals coming from field input devices such as pushbuttons, limit and proximity switches, or photo sensors into signals that can be used by the PLC.

•

Discrete Out – which convert signals generated by the PLC into output signals used to control field devices such as motor starters, relays, lamps, or solenoids.

•

Analog In – which convert analog signals coming from field input devices such as pressure, level, temperature, or weight sensors into numerical data that can be used by the PLC.

•

Analog Out – which convert numerical data generated by the PLC into analog output signals to be used by field devices, such as heaters, valves, pumps, instrumentation, or drives.

•

Special Purpose – which handle unique signal requirements. Examples include high speed counter, CAM Emulator, RTD, and Thermocouple Modules.

• Intelligent – designed for unique field applications that require bi-directional (in/out) capabilities and on-board processing power. Examples include an ASCII/BASIC Module and a high speed logic solver.

3-45

Page 45

Benefits

True Industrial Grade Design for High Reliability 800-Series modules meet domestic and international safety standards. Isolation voltage between outputs and the I/O bus and between output groups is: 1500 Vac at 47-63 Hz for 60 seconds without breakdown 2500 Vdc for 60 seconds without breakdown All modules have surge protection that meets IEEE-472-1974 and ANSI C37-90A-1974 standards - which helps ensure their operation when subjected to the surge spikes normally encountered in industrial environments. Solid mechanical packaging ensures that modules withstand the rigors of industrial environments. Easy to Configure, Wire, and Maintain All 800-Series I/O modules are software addressable via the 984’s Traffic Cop software. Designed for efficient system configuration, it allows any module to be configured in any slot, regardless of the module type. Furthermore, it recognizes incorrect module placement and prevents PLC misoperation. A mechanical keying scheme ensures that modules cannot be inserted in the wrong slot. 800-Series I/O modules can be changed without disturbing field wiring because wires are connected to rigid mounted terminal blocks on the housing. Modules slide in and out easily so changing modules is safe and quick. Built-in diagnostic indicators let maintenance personnel quickly determine module status. For example, every 800Series I/O module has an ACTIVE light which is a green LED located at the center of the front panel. When an I/O module’s ACTIVE LED is on constantly, it indicates that the module has been properly configured and that communications between it and the 984 PLC are healthy. When communications between the module and the PLC are invalid for any reason, the ACTIVE LED on the module goes OFF. If communication fails, the module automatically shuts down, and the PLC sets all inputs to 0. When communication is restored, the ACTIVE LED goes back ON. This ACTIVE LED is mapped into a register within the PLC for remote diagnosis and annunciation.

3-46

General 800-Series I/O Specifications Environmental Specifications Ambient Temperature 0-60°C 32-140°F Humidity 0-95% non-condensing Shock 10 G’s for 11 msec Vibration .625 @ 50-500 Hz RFI/EMI Emission Complies with applicable FCC requirements RFI/EMI Susceptibilility ML-STD-461B CS02-Conducted RS03-Radiated UL Listing E54088 CSA Listing LR32678

Page 46

Broad Range of Module Types

Discrete In

Voltage 115 Vac 115 Vac 115 Vac 115 Vac 230 Vac 230 Vac 24 Vdc Supr. Wire 24 Vdc (TH) 24 Vdc (TH) 24 Vdc (TL) 24 Vdc (LATCH) 24 Vdc* 10-60 Vdc (TH) 24 Vac/DC 48 Vac/DC 115 Vac 5 V TTL TTL Register 12 Vdc Intr. Safe

Number of Points 32 16 16 8 16 16 32 32 16 16 16 32 8 16 16 16 16 16 16

Number per Common 8 8 1 1 8 1 8 32 8 8 8 16 2 8 8 8 8, 1

Required Addressing I/O Bits Module # 32/0 AS-B807-132 16/0 AS-B805-016 16/0 AS-B817-116 8/0 AS-B803-008 16/0 AS-B809-016 16/0 AS-B817-216 64/0 AS-B863-132 32/0 AS-B827-032 16/0 AS-B825-016 16/0 AS-B833-016 16/16 AS-B881-001 16/0 AS-B863-032 8/0 AS-B821-108 16/0 AS-B837-016 16/0 AS-B849-016 16/0 AS-B853-016 16/0 AS-B829-116 16/0 AS-B865-001 16/0 AS-B855-016

Required Connector AS-8535-000 AS-8534-000 AS-8535-000 AS-8534-000 AS-8534-000 AS-8535-000 AS-8535-000 AS-8535-000 AS-8534-000 AS-8534-000 AS-8534-000 AS-8535-000 AS-8534-000 AS-8534-000 AS-8534-000 AS-8534-000 AS-8534-000 AS-8535-000 AS-8535-000

With over 50 modules to choose from, the Modicon I/O line offers one of the industry’s broadest range of I/O modules.

*Monitored Input.

Discrete Out

Voltage 115 Vac 115 Vac 115 Vac 115 Vac 115 Vac Protected 48 Vac 24 Vac 230 Vac 24 Vdc Supr. Wire 24 Vdc (TH) 24 Vdc (TH) 24 Vdc (TH) 24 Vdc (TL) 24 Vdc Diagnostic 10-60 Vdc (TH) 12-250 Vdc Relay (NO/NC) Reed Relay (NO/NC) 5 V TTL TTL Register 125 Vdc

Number of Points 32 16 8 8 8 16 32 16 16 32 32 16 16 32 8 16 8 8 16, 8

Number per Common 16 8 1 2 1 8 16 8 8 8 32 8 8 8 2 1 1 1 16, - Required Addressing I/O Bits 0/32 0/16 0/8 0/8 16/16 0/16 0/32 0/16 16/16 0/32 0/32 0/16 0/16 32/32 0/8 0/16 0/8 0/8 0/16 0/128 16/16

Module # AS-B806-032 AS-B804-116 AS-B810-008 AS-B802-008 AS-B881-108 AS-B804-148 AS-B806-124 AS-B808-016 AS-B882-116 AS-B838-032 AS-B826-032 AS-B824-016 AS-B832-016 AS-B882-032 AS-B820-008 AS-B836-016 AS-B814-108 AS-B840-108 AS-B828-016 AS-B864-001 AS-B881-508

Required Connector AS-8535-000 AS-8534-000 AS-8534-000 AS-8534-000 AS-8535-000 AS-8534-000 AS-8535-000 AS-8534-000 AS-8534-000 AS-8535-000 AS-8535-000 AS-8534-000 AS-8534-000 AS-8535-000 AS-8534-000 AS-8535-000 AS-8534-000 AS-8534-000 AS-8534-000 AS-8535-000 AS-8535-000

3-47

Page 47

Analog In

Application/Range Fast A/D: 4-20 mA; +5 V; +10 V; 0-10 V; 0-5 V; 1-5 V

Number of Points

Required Addressing I/O Bits

Module #

Required Connector

8

128/0

AS-B875-102

Included

A/D; 4-20 mA;1-5 V A/D; 4-20 mA;1-5 V A/D; -10 to 10 V A/D; -10 to 10 V Thermocouple, Type B,E,J,K,R, S,T,N, or linear V

8 4 8 4

128/0 64/0 128/0 64/0

AS-B875-002 AS-B873-001 AS-B875-012 AS-B873-011

Included Included Included Included

10

48/48

AS-B883-200

Included

RTD, American or European 100 Ohm Platinum

8

48/48

AS-B883-201

Included

Analog Multiplexer; 16 Voltage In, 1 Output

16

0/16

AS-B846-001

AS-8535-000

Analog Multiplexer, 16 Current In, 1 Output

16

0/16

AS-B846-002

AS-8535-000

A/D; 4-20mA; 1-5 V; -10 to10 V 0-20mA; -5 to 5 V

8/16

128/0 256/0

AS-B875-111

AS-8535-000

User Configurable Analog

8

128/0

AS-B875-200

AS-8535-000

Analog Out

Application/Range D/A: 4-20 mA D/A: ± 10 V; ± 5 V; 0-10 V; 0-5 V

Number of Points 4 4

Required Addressing I/O Bits 0/64 0/64

Module # AS-B872-100 AS-B872-200

Required Connector AS-8535-000 AS-8535-000

Intelligent/Special Purpose Required Addressing I/O Bits 32/32

Module # AS-B882-239

Required Connector Included

48/48

AS-B883-001

Included

48/48

AS-B883-101

Included

CAM emulator with velocity compensation PID: 2 loops, cascadable, standalone, 11 total I/O

48/48

AS-B883-111

Included

64/64

AS-B884-002

Included

ASCII/BASIC, 64K RAM, 2 RS232/422 ports

96/96

AS-B885-002

Included

64/64 or 128/128 96/96 96/96

AS-B984-100 AS-B885-100 AS-B885-110

Included Included Included

Description High speed counter, 2 up-counters, 0-30 kHz High speed counter, 2 up/down, 0-50 kHz, Internal clock CAM emulator, absolute encoder input, 8 discrete out

Discrete High Speed Logic Solver Motion Control Module Motion Control Module (with Encoder Feedback)

3-48

Page 48

Individual Module Descriptions Technical Specifications, Mechanical Keying, and Wiring Diagrams

Specification

AS-B802-008

Specification

AS-B803-008

Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point

115 Vac output 8 80 ... 130 Vac / 47 ... 63 Hz 4 2

Description Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous Surge

115 Vac isolated input 8 80 ... 130 Vac / 47 ... 63 Hz 8 1

ON Conditions

80 ... 130 Vac (Z<1kΩ)

OFF Conditions

0 ... 35 Vac (Z=0 Ω) 0 ... 130 Vac (Z>40 kΩ) 7 mA (typical) @ 115 Vac

Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector Fusing

AS-B802-008 Terminal Numbering and Wire Connections

2 A continuous 50 A (max) one cycle 12 A 3 mA (max) @ 115 Vac 8.3 ms @ 60 Hz 8.3 ms @ 60 Hz 76 mA 240 mA 0 mA 1 slot 2.55 lbs (1.16 kg) AS-8534-000 One per group

AS-B802-008 Mechanical Keying for Housings

Wetting Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector

AS-B803-008 Terminal Numbering and Wire Connections

130 Vac 220 Vac for one cycle

6 ms (4 ms typical) 18 ms (12 ms typical) 27 mA 1 mA 2 mA 1 slot 2.11 lbs (0.96 kg) AS-8534-000

AS-B803-008 Mechanical Keying for Housings

TOP

TOP

BOTTOM

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

(When facing housing, place pins in holes shown by black circles.)

3-49

Page 49

Specification

AS-B804-116

Specification

AS-B804-148

Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point

115 Vac output 16 80 ... 130 Vac / 47 ... 63 Hz 2 8

Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point

48 Vac output 16 40 ... 56 Vac / 47 ... 63 Hz 2 8

Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector Fusing

AS-B804-116 Terminal Numbering and Wire Connections

2 A continuous 50 A one cycle 6A 12.0 A 3 mA (max) @ 115 Vac 8.3 ms @ 60 Hz 8.3 ms @ 60 Hz 76 mA 480 mA 0 mA 1 slot 2.75 lbs (1.25 kg) AS-8534-000 One per group

AS-B804-116 Mechanical Keying for Housings

AS-B804-148 Terminal Numbering and Wire Connections

8.3 ms @ 60 Hz 8.3 ms @ 60 Hz 76 mA 480 mA 0 mA 1 slot 2.75 lbs (1.25 kg) AS-8534-000 One per group

AS-B804-148 Mechanical Keying for Housings

TOP

TOP

BOTTOM

BOTTOM

(When facing housing, place pins in holes shown by black

3-50

Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector Fusing

2 A continuous 50 A one cycle 6A 12.0 A 3 mA (max)

(When facing housing, place pins in holes shown by black circles.)

Page 50

Specification

AS-B805-016

Specification

AS-B806-032

Description Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous Surge ON Conditions OFF Conditions

115 Vac input 16 80 ... 130 Vac / 47 ... 63 Hz 2 8

Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point

115 Vac output 32 80 ... 130 Vac / 47 ... 63 Hz 2 16

Wetting Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector

AS-B805-016 Terminal Numbering and Wire Connections

130 Vac 220 Vac for one cycle 80 ... 130 Vac (Z<1kΩ) 0 ... 35 Vac (Z=0 Ω) 0 ... 130 Vac (Z>40 kΩ) 6 mA (typical) @ 115 Vac 6 ms (4 ms typical) 18 ms (11 ms typical) 40 mA 1 mA 14 mA 1 slot 2.2 lbs (1.01 kg) AS-8534-000

AS-B805-016 Mechanical Keying for Housings

Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector Fusing

AS-B806-032 Terminal Numbering and Wire Connections

1 A continuous 15 A one cycle 8A 16 A 2 mA (max) @ 115 Vac 8.3 ms @ 60 Hz 8.3 ms @ 60 Hz 210 mA 1 mA 0 mA 1 slot 2.49 lbs (1.13 kg) AS-8535-000 None

AS-B806-032 Mechanical Keying for Housings

TOP TOP

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-51