Page 51
Specification
Specification
AS-B806-124
Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point
24 Vac output 32 20 ... 28 Vac / 47 ... 63 Hz 2 16
Description Number of Points Operating Voltage
1 A continuous 15 A one cycle 8A 16 A 2 mA (max.)
Number of Groups Inputs per Group Max. Input Voltage Continuous Surge ON Conditions OFF Conditions
Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector Fusing
AS-B806-124 Terminal Numbering and Wire Connections
8.3 ms @ 60 Hz 8.3 ms @ 60 Hz 210 mA 1 mA 0 mA 1 slot 2.49 lbs (1.13 kg) AS-8535-000 None
AS-B806-124 Mechanical Keying for Housings
Wetting Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connection
AS-B807-132 115 Vac
125 Vdc
115 Vac hi-density input 32 80 ... 130 Vac/ 47 ... 63 Hz 4 8
125 Vdc input 32 115 ...140 Vdc cont. 4 8
130 Vac 200 Vac for 1 cycle 80 ... 130 Vac (Z<1kΩ) 115 ...140 Vdc 0 ... 35 Vac (Z=0 Ω) 0 ... 20 Vdc 0 ... 130 Vac (Z>40 kΩ) 6 mA (typical) @ 115 Vac 6 ms 12 ms
1.2 ms 55ms
80 mA 2 mA 0 mA
80 mA 2 mA 0 mA
1 slot 2 lbs (0.91 kg) AS-8535-000
1 slot 2 lbs (0.91 kg) AS-8535-000
AS-B807-132 Terminal Numbering and Wire Connections
AS-B807-132 Mechanical Keying for Housings TOP
TOP
BOTTOM BOTTOM
(Optional)
(When facing housing, place pins in holes shown by black circles.)
3-52
(When facing housing, place pins in holes shown by black circles.)
Page 52
Specification
AS-B808-016
Specification
AS-B809-016
Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point
230 Vac output 16 160 ... 260 Vac / 47 ... 63 Hz 2 8
Description Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous 300 Vac for 10 sec. Surge ON Conditions OFF Conditions Wetting Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
230 Vac input 16 160 ... 260 Vac / 47 ... 63 Hz 2 8
Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector Fusing
AS-B808-016 Terminal Numbering and Wire Connections
2 A continuous 50 A one cycle 6A 12 A 8 mA (max) @ 230 Vac 8.3 ms 8.3 ms 76 mA 480 mA 0 mA 1 slot 2.75 lbs (1.25 kg) AS-8534-000 One per group
AS-B808-016 Mechanical Keying for Housings
AS-B809-016 Terminal Numbering and Wire Connections
260 Vac 400 Vac for 1 cycle 112 ... 148 Vac (RS=1 Kmax) 0 ... 90 Vac (Z=0 Ω) 8.5 mA (typical) @ 230 Vac 7 ms (5 ms typical) 18 ms (12 ms typical) 42 mA 1 mA 15 mA 1 slot 2.38 lbs (1.08 kg) AS-8534-000
AS-B809-016 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
(When facing housing, place pins in holes shown by black circles.)
3-53
Page 53
Specification Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V External Power Supply Dimensions Space Required Weight Terminal Connector Fusing
AS-B820-008 Terminal Numbering and Wire Connections
AS-B820-008
Specification
AS-B821-108
10 ... 60 Vdc (True High) output 8 10 ... 60 Vdc 4 2
Description Type of Operation Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous Surge Wetting Current
10 ... 60 Vdc input True High 8 10 ... 60 Vdc 4 2
2A 6A 12 A 5 mA (max.) @ 60 Vdc 1 ms (.1 ms typical) 1 ms (.1 ms typical) 90 mA 80 mA 0 mA 10 ... 60 Vdc, 200 mA @ 60 Vdc (Excluding field load current) 1 slot 2.55 lbs (1.16 kg) AS-8534-000 One per group
AS-B820-008 Mechanical Keying for Housings
Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V External Power Supply Dimensions Space Required Weight Terminal Connector
AS-B821-108 Terminal Numbering and Wire Connections
10 ... 60 Vdc 80 Vdc for 10 msec 2 mA (max.) @ 10 Vdc 5 mA (max.) @ 24 Vdc 10 mA (max.) @ 48 Vdc 12 mA (max.) @ 60 Vdc 11 ms 11 ms 27 mA 1 mA 10 mA 10 ... 60 Vdc, 200 mA @ 60 Vdc 1 slot 2.11 lbs (0.96 kg) AS-8534-000
AS-B821-108 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
(When facing housing, place pins in holes shown by black circles.)
3-53
Page 54
Specification
AS-B824-016
Specification
AS-B825-016
Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point
24 Vdc (True High) output 16 20 ... 28 Vdc 2 8
Description Type of Operation Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous Surge ON Conditions OFF Conditions Wetting Current Max Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V External Power Supply Dimensions Space Required Weight Terminal Connector
24 Vdc input True High 16 20 ... 28 Vdc 1 16
Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V External Power Supply Dimensions Space Required Weight Terminal Connector Fusing
AS-B824-016 Terminal Numbering and Wire Connections
2 A continuous 5 A for 10 ms 6A 12 A 1 mA (max.) @ 24 Vdc 1 ms 1 ms 32 mA 260 mA 0 mA 24± 4 Vdc, 175 mA (Excluding field load current) 1 slot 2.75 lbs (1.25 kg) AS-8534-000 One per group
AS-B824-016 Mechanical Keying for Housings
11 ms (2.5 ms typical) 11 ms (2.5 ms typical) 27 mA 2 mA 15 mA 24±4 Vdc, 200 mA 1 slot 2.75 lbs (1.25 kg) AS-8534-000
AS-B825-016 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
3-54
AS-B825-016 Terminal Numbering and Wire Connections
30 Vdc 500 Vdc for 3 ms < 1000 Ω > 25,000 Ω 6 mA (typical) @ 24 Vdc
(When facing housing, place pins in holes shown by black circles.)
Page 55
Specification
AS-B826-032
Specification
AS-B827-032
Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point
24 Vdc True High output 32 20 ... 28 Vdc 1 32
Description Type of Operation Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous Surge ON Conditions OFF Conditions Wetting Current Max Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V External Power Supply Dimensions Space Required Weight Terminal Connector
24 Vdc hi-density input True High 32 20 ... 28 Vdc 1 32
Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V External Power Supply Dimensions Space Required Weight Terminal Connector Fuse
AS-B826-032 Terminal Numbering and Wire Connections
0.25 A 2.5 A for .5 ms 8A 8A 0.1 mA (typical) @ 24 Vdc 1 ms 1 ms 90 mA 1 mA 0 mA 24 Vdc, 600 mA (Excluding field load current) 1 slot 2.55 lbs (1.16 kg) AS-8535-000 One per group
AS-B826-032 Mechanical Keying for Housings
AS-B827-032 Terminal Numbering and Wire Connections
30 Vdc 40 Vdc for 10ms 8 ... 11 kΩ 6 ... 8 kΩ 6 mA (typical) @ 24 Vdc 1 ms 1 ms 30 mA 1 mA 0 mA 24± 6 Vdc, 70 mA 1 slot 2.31 lbs (1.05 kg) AS-8535-000
AS-B827-032 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
(When facing housing, place pins in holes shown by black circles.)
3-55
Page 56
Specification
AS-B828-016
Specification
AS-B829-116
Description Number of Points Operating Voltage Number of Groups Outputs per Group OFF Current Max. per Point
5 V TTL output 16 5 V TTL 1 16
Description Type of Operation Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous Surge Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V External Power Supply Dimensions Space Required Weight Terminal Connector
5 V TTL input TTL 16 5 V TTL 1 16
Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V External Power Supply Dimensions Space Required Weight Terminal Connector Fusing
AS-B828-016 Terminal Numbering and Wire Connections
75 mA max. (sinking) 100 mA for 10 ms 1 ms 1 ms 32 mA 220 mA 0 mA 5.0± .25 Vdc, 325 mA (Excluding field load current) 1 slot 2.33 lbs (1.06 kg) AS-8534-000 One per group
AS-B828-016 Mechanical Keying for Housings
1 ms 1 ms 27 mA 1 mA 0 mA 5.0 ±.25 Vdc, 325 mA 1 slot 2.26 lbs (1.03 kg) AS-8534-000
AS-B829-116 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
3-56
AS-B829-116 Terminal Numbering and Wire Connections
8 Vdc 15 Vdc for 10 ms
(When facing housing, place pins in holes shown by black circles.)
Page 57
Specification Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V External Power Supply Dimensions Space Required Weight Terminal Connector Fusing
AS-B832-016 Terminal Numbering and Wire Connections
AS-B832-016
Specification
AS-B833-016
24 Vdc True Low output 16 20 ... 28 Vdc 2 8
Description Type of Operation Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous Surge ON Conditions OFF Conditions Wetting Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V External Power Supply
24 Vdc True Low input True Low 16 20 ... 28 Vdc 2 8
250 mA 1A for 10 ms 2A 4A 0.5 mA (typical) @ 24 Vdc 1 ms 1 ms 32 mA 235 mA 0 mA 24± 4 Vdc, 600 mA 1 slot 2.75 lbs (1.25 kg) AS-8534-000 One per module
AS-B832-016 Mechanical Keying for Housings
Dimensions Space Required Weight Terminal Connector Fusing
AS-B833-016 Terminal Numbering and Wire Connections
30 Vdc 500 Vdc for 3 ms < 200 Ω > 10,000 Ω 6 mA (typical) @ 24 Vdc 11 ms 11 ms 27 mA 2 mA 0 mA 24 ± 4 Vdc, 300 mA (Excluding field load current) 1 slot 2.75 lbs (1.25 kg) AS-8534-000 One per module
AS-B833-016 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
(When facing housing, place pins in holes shown by black circles.)
3-57
Page 58
Specification
AS-B836-016
Specification
AS-B837-016
Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point
12 ... 250 Vdc isolated output 16 12 ... 250 Vdc 16 1
Description Number of Points Operating Voltage Vdc Number of Groups Inputs per Group Max. Input Voltage Continuous Surge ON Conditions
24 Vac/DC input 16 20 ... 27 Vac/47 ... 63 Hz; 19 ... 30
Max. per Module Leakage Current Surge Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector Fusing
AS-B836-016 Terminal Numbering and Wire Connections
0.75 A (typical) @ 250 Vdc 1 A (typical) @ 125 Vdc 1.5 A (typical ) @ 48 Vdc 8A 1mA (max.) @ 12 Vdc 5 A for 10 ms at repetition rate of 1 sec. 1 ms 5 ms 50 mA 603 mA 0 mA 1 slot 2.55 lbs (1.16 kg) AS-8535-000 One per group
AS-B836-016 Mechanical Keying for Housings
OFF Conditions Wetting Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V External Power Supply Dimensions Space Required Weight Terminal Connector
AS-B837-016 Terminal Numbering and Wire Connections
2 8 27 Vac / 30 Vdc 32 Vac / 36 Vdc >20.4 Vac or 19.2 Vdc w/lnp Z of 1 K max. < 6 Vac/ 10 Vdc < 27 Vac w/Inp Z > 15 K < 30 Vac w/Inp Z > 30 K 7.5 mA (typical) @ 24 Vdc 6 ms 18 ms 40 mA 1 mA 15 mA 24 Vac/DC, 300 mA 1 slot 2.75 lbs (1.25 kg) AS-8534-000
AS-B837-016 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
(When facing housing, place pins in holes shown by black circles.)
3-59
Page 59
Specification
AS-B838-032
Specification
AS-B840-108
Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point
24 Vdc True High output 32 20 ... 28 Vdc 4 8
Description Number of Points Operating Voltage
Reed Relay (NO/NC) output 8 0 ... 300 Vdc; 0 ... 230 Vac / 47 ... 63 Hz 8 1
Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V External Power Supply Dimensions Space Required Weight Terminal Connector
AS-B838-032 Terminal Numbering and Wire Connections
0.5 A 2.5 A for .5 ms 4A 12 A 1 mA (typical) @ 30 Vdc 1 ms 1 ms 160 mA 1 mA 0 mA 24 ± 4Vdc, 125 mA (Excluding field load current) 1 slot 2.4 lbs (1.09 kg) AS-8535-000
AS-B838-032 Mechanical Keying for Housings
Max. per Module Switching Capability Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V Dimensions Space Required Weight Terminal Connector Fusing
AS-B840-108 Terminal Numbering and Wire Connections
3 A continous 2 A switching current 24 A 100 vA 6 ms (2 ms typical) 6 ms (2 ms typical) 67 mA 400 mA 0 mA 1 slot 2.62 lbs (1.19 kg) AS-8534-000 One per group
AS-B840-108 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
3-60
Number of Groups Outputs per Group ON Current Max. per Point
(When facing housing, place pins in holes shown by black circles.)
Page 60
Specification
AS-B846-001
Specification
AS-B846-002
Description Number of Channels Address Capacity I/O Range Input Impedance Response Time Switching Behavior
Analog Input Multiplexer 16, potential isolated to each other 1 register out (channel select) -10 to 10 Vdc (voltage) Equal to B873 or B875 3 ms Break before Make, switching time: 3 ms
Description Number of Channels Address Capacity I/O Range Input Impedance Response Time Switching Behavior
Analog Input Multiplexer 16, potential isolated to each other 1 register out (channel select) 4 to 20 mA (current) 250 Ω 3 ms Break before Make, switching time: 3 ms
Power Required +5 Vdc +4.3 Vdc -5 Vdc Dimensions Space Required Weight Terminal Connector
AS-B846-001 Mechanical Keying for Housings
65 mA 1 mA 0 mA 1 slot 2.55 lbs (1.16 kg) AS-8535-000
AS-B846-001 Terminal Numbering and Wire Connections
Power Required +5 Vdc +4.3 Vdc -5 Vdc Dimensions Space Required Weight Terminal Connector
AS-B846-002 Terminal Numbering and Wire Connections
65 mA 1 mA 0 mA 1 slot 2.55 lbs (1.16 kg) AS-8535-000
AS-B846-002 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.) (When facing housing, place pins in holes shown by black circles.)