The text of a manual · part 7 of 13
984 Programmable Logic Controllers and 800-Series Input/Output Modules, pages 61 to 70
Pages 61 to 70 of 123
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B807, Modicon B865, AEG B807, Gould B807, Schneider B807, AEG B865, Gould B865 and Schneider B865
Page 61
Specification
AS-B849-016
Specification
AS-B853-016
Description Number of Points Operating Voltage
48 Vac / DC input 16 41 ... 53 Vac / 47 ... 63 Hz; 39 ... 58 Vdc 2 8
Description Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous Surge 280 V for 10 ms ON Conditions w/Inp Z of 1 K max. OFF Conditions < 130 Vac w/Inp Z > 40 K < 150 Vac w/Inp Z > 80 K Wetting Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V Dimensions Space Required Weight Terminal Connector
115 Vac 16 80 ... 130 Vac / 47 ... 63 Hz; 2 8
Number of Groups Inputs per Group Max. Input Voltage Continuous Surge ON Conditions OFF Conditions Wetting Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V External Power Supply Dimensions Space Required Weight Terminal Connector
AS-B849-016 Terminal Numbering and Wire Connections
53 Vac / 58 Vdc 63 Vac / 70 Vdc for 10 sec 110 V for 10 ms > 41 Vac or 39 Vdc w/Inp Z of 1 K max. < 15 Vac / 20 Vdc < 53 Vac w/Inp Z > 25 K < 58 Vac w/Inp Z > 50 K 6.5 mA (typical) @ 48 Vdc 6 ms 18 ms 40 mA 1 mA 15 mA 48 Vac/DC, 200 mA 1 slot 2.75 lbs (1.25 kg) AS-8534-000
AS-B849-016 Mechanical Keying for Housings
AS-B853-016 Terminal Numbering and Wire Connections
130 Vac 150 Vac > 80 Vac < 35 Vac 6 mA (typical) @ 125 Vdc 6 ms 18 ms 40 mA 1 mA 15 mA 1 slot 2.75 lbs (1.25 kg) AS-8534-000
AS-B853-016 Mechanical Keying for Housings
TOP TOP
BOTTOM BOTTOM
(When facing housing, place pins in holes shown by black circles.)
3-62
(When facing housing, place pins in holes shown by black circles.)
Page 62
Specification Description Mode of Operation Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continous Surge ON Conditions OFF Conditions Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V External Power Supply Dimensions Space Required Weight Terminal Connector Agency
AS-B855-016 Terminal Numbering and Wire Connections
AS-B855-016
Specification
AS-B863-032
12 Vdc intrinsically safe input True Low 16 11.4 ... 12.6 Vdc 1 16
Description Type of Operation Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous Surge ON Conditions OFF Conditions Wetting Current Max Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V 5V External Power Supply Dimensions Space Required Weight Terminal Connector
24 Vdc hi-density monitored input True High 32 18 ... 30 Vdc 2 16
12 Vdc (± 5%) 500 Vdc for 3 ms ≤ 100 Ω total impedance >100,000 Ω; 0 Vdc 1 ms 5 ms 80 mA 1 mA 1.5 mA 12 Vdc±5%, 1 A minimum 1 slot 2.4 lbs (1.1 kg) AS-8535-000 Factory mutual 3610 (Requires use of key pins and MD-8741-000 barrier strip, included with module)
AS-B855-016 Mechanical Keying for Housings
AS-B863-032 Terminal Numbering and Wire Connections
30 Vdc 40 Vdc for 10ms 8 ... 11 kΩ 6 ... 8 kΩ 2 mA (typical) @ 24 Vdc 10 ms 10 ms 250 mA 0 mA 0 mA 24±6 Vdc, 20 mA 1 slot 2.31 lbs (1.05 kg) AS-8535-000
AS-B863-032 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
(When facing housing, place pins in holes shown by black circles.)
3-63
Page 63
Specification
AS-B863-132
Specification
AS-B864-001
Description
24 Vdc Supervised wire input Senses & reports broken wire faults for each I/O point to PLC True High 32 4 (8 inputs per group) 9 to 15 mA per group 11 to 15 Vdc 0 to 30 Vdc 19.2 to 30 Vdc 1.8 to 3 mA low state 5.75 to 7.1 mA high state
Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
TTL register ouput 8 channels, 16 data lines 5V TTL NA NA
Type of Operation Number of Points Number of Groups Reference Current Threshold Voltage Working Voltage Reference Voltage Input Current Transition Time ON OFF Max. Response Time OFF to ON ON to OFF Power Required + 5V +4.3V -5V External Power Supply Dimensions Space Required Weight Terminal Connector AS-B863-132 Terminal Numbering and Wire Connections
Vin = 20 Vdc 200 ms minimum Vin = 30 Vdc 25 ms minimum Vin = 20 Vdc 100 ms maximum Vin = 30 Vdc 250 ms maximum 2.0 ms, contact opening and/or closing 100 ms, fault detection time maximum 350 mA 10 mA 0mA (not used) 30 Vdc maximum 1 slot 2 lbs (0.91 kg.) AS-8535-000 AS-B863-132 Mechanical Keying for Housings
11.3 ms 11.3 ms 220 mA 180 mA 0 mA 1 slot 3.99 lbs (1.81 kg) AS-8535-000
AS-B864-001 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
3-64
AS-B864-001 Terminal Numbering and Wire Connections
NA NA NA NA
(When facing housing, place pins in holes shown by black circles.)
Page 64
Specification
B865-001
Specification
AS-B872-100
Description Number of Inputs Operating Voltage Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
TTL register input 8 channels, 16 data lines 5 VTTL
Description Number of Channels Operating Range Max. Loop Supply Voltage Resolution Accuracy Linearity Update Times Isolation Channel to Channel Channel to Case Channel to Module Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
D/A; 4 ... 20 mA 4 4 ... 20 mA 60 Vdc 12 bit ± 0.1% of full scale at 25°C 0 to 60°C, ± 1 LSB <1 ms, all 4 channels
B865-001 Terminal Numbering and Wire Connections
20 ms 20 ms 400 mA 600 mA 0 mA 1 slot 2.75 lbs (1.25 kg) AS-8535-000
B865-001 Mechanical Keying for Housings
AS-B872-100 Terminal Numbering and Wire Connections
1000 V continuous 1000 V continuous 1000 V continuous 475 mA 5 mA 0 mA 1 slot 3 lbs (1.4 kg) AS-8535-000
AS-B872-100 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
(When facing housing, place pins in holes shown by black circles.)
3-65
Page 65
Specification
AS-B872-200
Specification
AS-B873-001
Description
D/A; ± 10 Vdc, ± 5 Vdc, 0 ... 10 Vdc, 0 ... 5 Vdc 4
Description Number of Channels Operating Range Voltage/Current Impedance
A/D: 4 ... 20 mA; 1 ... 5 Vdc 4
Number of Channels Operating Range Voltage Resolution Accuracy Linearity Update Times Isolation Channel to Channel Channel to Case Channel to Module Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
AS-B872-200 Terminal Numbering and Wire Connections
-10 to 10 Vdc; -5 to 5 Vdc; 0 ... 5 Vdc, 0 ... 10 Vdc, selectable per channel 12 bit ± 0.1% at 25°C ± 0.17% at 0-60°C 0 to 60°C, ±1 LSB <1 ms, all 4 channels 1000 V continuous 1000 V continuous 1000 V continuous 750 mA 5 mA 0 mA
Resolution Accuracy Linearity Update Time Isolation Channel to Channel Channel to Module Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
1 ... 5 Vdc / 4 ... 20 mA 1 MΩ (voltage mode) 250 Ω (current mode) 12 bit 7 mV ± .05% of full scale @ 25°C 400 ms for 4 channels 250 Vac coninuous 300 Vac continuous 300 mA 300 mA 0 mA 1 slot 3.3 lbs (1.5 kg) Included
1 slot 3 lbs (1.4 kg) AS-8535-000
AS-B872-200 Mechanical Keying for Housings
AS-B873-001 Terminal Numbering and Wire Connections
AS-B873-001 Mechanical Keying for Housings
TOP TOP
BOTTOM BOTTOM
(When facing housing, place pins in holes shown by black circles.)
3-66
(When facing housing, place pins in holes shown by black circles.)
Page 66
Specification
AS-B873-011
Specification
AS-B875-002
Description Number of Channels Operating Range Voltage/Current Impedance Resolution Accuracy Linearity Update Time Isolation Channel to Channel Channel to Module Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
A/D: -10 to 10 Vdc 4
Description Number of Channels Operating Range Voltage/Current Impedance
A/D: 4 ... 20 mA; 1 ... 5 Vdc 8
AS-B873-011 Terminal Numbering and Wire Connections
-10 to 10 Vdc 1 MΩ 13 bit 17 mV ± .05% of full scale @ 25°C 400 ms for 4 channels 250 Vac continuous 300 Vac continuous 300 mA 300 mA 0 mA 1 slot 3.3 lbs (1.5 kg) Included
AS-B873-011 Mechanical Keying for Housings
TOP
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
Resolution Accuracy Linearity Update Time Isolation Channel to Channel Channel to Module Transfer Times Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
AS-B875-002 Terminal Numbering and Wire Connections
1 ... 5 Vdc / 4 ... 20 mA 1 MΩ (voltage mode) 250 Ω (current mode) 12 bit 7 mV ± .05% of full scale @ 25°C 710 ms for 8 channels 250 Vac continuous 300 Vac continuous 300 mA 300 mA 0 mA 1 slot 3.3 lbs (1.5 kg) Included
AS-B875-002 Mechanical Keying for Housings
TOP
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
3-67
Page 67
Specification
AS-B875-012
Specification
AS-B875-102
Description Number of Channels Operating Range Voltage/Current Impedance Resolution Accuracy Linearity Update Time Isolation Channel to Channel Channel to Module Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
A/D: -10 to 10 Vdc 8
Description
-10 to 10 Vdc 1 MΩ 13 bit 17 mV ± .05% of full scale @ 25°C 710 ms for 8 channels
Number of Channels Operating Range Voltage/Current
Fast A/D: ± 10 Vdc; ± 5 Vdc; 0 ... 10 V; 0 ... 5 Vdc; 1 ... 5 Vdc user selectable 4 or 8
250 Vac continuous 300 Vac continuous
Output Impedance
AS-B875-012 Terminal Numbering and Wire Connections
Resolution Accuracy Linearity Update Time
300 mA 300 mA 0 mA 1 slot 3.3 lbs (1.5 kg) Included
AS-B875-012 Mechanical Keying for Housings
AS-B875-102 Terminal Numbering and Wire Connections
30 Vac continuous 1500 Vac for 1 minute 650 mA 975 mA 0 mA 1 slot 4 lbs (1.8 kg) Included AS-B875-102 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
3-68
Isolation Channel to Channel Channel to Module Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
1 ... 5 Vdc / 4 ... 20 mA 0 ... 5 Vdc / 0 ... 20 mA 0 ... 10 V / 0 ... 40 mA -5 ... 5 V / -20 ... 20 mA -10 ... 10 V / -40 ... 40 mA 10 MΩ (voltage mode) 250 Ω (current mode) 12 bit ± 0.1% of full scale @ 25°C ± .02% of full scale @ 25°C 2.4 ms for 4 channels 3.0 ms for 8 channels
(When facing housing, place pins in holes shown by black circles.)
Page 68
Specification
AS-B875-111
Description
A/D: 4 ... 20 mA; 1 ... 5 Vdc; -10 to 10 Vdc; 0 ... 20 mA; -5 to 5 Vdc 8 differential or 16 single-ended (user selectable)
Number of Channels Operating Range Voltage/Current
Output Impedance Resolution Accuracy Linearity Update Time 8 inputs 16 inputs
-5 Vdc to +5 Vdc 0 to 5 Vdc 1 Vdc to 5 Vdc -10 Vdc to +10 Vdc 0 to 10 Vdc -20 mA to +20 mA 0 to 20 mA 4 to 20 mA > 10 MΩ (voltage mode) 250 Ω (current mode) 14 bit ± 0.1% ± .05%
Isolation Channel to Channel Channel to Module Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
30 Vac 1500 Vac for 1 minute 500 mA 900 mA 0 mA 1 slot 3.52 lbs (1.6 kg) AS-8535-000
10 ms 20 ms
AS-B875-111 Terminal Numbering and Wire Connections 8 Differential Inputs
16 Single-Ended Inputs
AS-B875-111 Mechanical Keying for Housings TOP
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
3-69
Page 69
List of 5B Packs
Specification
AS-B875-200
Description
A/D; Thermocouples, RTD Strain Gauges, 4 ... 20 mA Various Input Voltage Ranges 4/8 Selectable per channel 12 bit
Number of Channels Operating Range Resolution Accuracy Calibration Accuracy Non-Linearity Gain Drift Zero Drift Update Times Isolation Channel to Channel Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
AS-B875-200 Terminal Numbering and Wire Connections
± .15% at 25° C ± .05% ± .01%/° C ± .002%/° C 4 ms, all 4 channels 1500 V continuous < 600 mA < 10 mA 0 mA 2 slots 3 lbs (1.4 kg) AS-8535-000
AS-B875-200 Mechanical Keying for Housings
TOP
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
3-70
Part Number Description Voltage Input, 4 Hz. AS-5B30001A 0 to +10 mV AS-5B30002A 0 to +50 mV AS-5B30003A 0 to +100 mV AS-5B30004A -10 to +10 mV AS-5B30005A -50 to +50 mV AS-5B30006A -100 to +100 mV AS-5B31001A 0 to +1 V AS-5B31002A 0 to +5 V AS-5B31003A 0 to +10 V AS-5B31004A -1 to +1 V AS-5B31005A -5 to +5 V AS-5B31006A -10 to +10 V Voltage Input, 10KHz. AS-5B40001A 0 to +10 mV AS-5B40002A 0 to +50 mV AS-5B40003A 0 to +100 mV AS-5B40004A -10 to +10 mV AS-5B40005A -50 to +50 mV AS-5B40006A -100 to +100 mV AS-5B41001A 0 to +1 V AS-5B41002A 0 to +5 V AS-5B41003A 0 to +10 V AS-5B41004A -1 to +1 V AS-5B41005A -5 to +5 V AS-5B41006A -10 to +10 V Current Input, 4 Hz. AS-5B32001A 4 to 20 ma AS-5B32002A 0 to 20 ma Thermocouple Input, Linear, 4 Hz. AS-5B47J01A (Type J) 0 to +760°C AS-5B47J02A (Type J) -100 to +300°C AS-5B47J03A (Type J) 0 to +500°C AS-5B47K04A (Type K) 0 to +1000°C AS-5B47K05A (Type K) 0 to +500°C AS-5B47T06A (Type T) -100 to +400°C AS-5B47T07A (Type T) 0 to +200°C AS-5B47E08A (Type E) 0 to +1000°C AS-5B47R09A (Type R) +500 to +1750°C AS-5B47S10A (Type S) +500 to +1750°C AS-5B47B11A (Type B) +500 to +1800°C RTD Input, Isolated, 4 Hz. AS-5B34P01A -100 to +100°C AS-5B34P02A 0 to +100°C AS-5B34P03A 0 to +200°C AS-5B34P04A 0 to +600°C AS-5B34C01A 0 to +120°C, 10 Ω @ 0°C AS-5B34C02A 0 to +120°C, 10 Ω @ 25°C AS-5B34N01A 0 to +300°C Strain Gauge, 10 KHz. AS-5B38002A Full Bridge, 3 mV/V 300 Ω min. AS-5B38004A Half Bridge, 3 mV/V 300 Ω min. AS-5B38005A Full Bridge, 2 mV/V 300 Ω min.
Page 70
Specification
AS-B881-001
Specification
AS-B881-108
Description Type of Operation Number of Points Operating Voltage Number of Groups Inputs per Group Max. Input Voltage Continuous Surge Wetting Current Min. Pulse Width Repetition Rate Power Required +5 V +4.3 V -5 V External Power Supply Dimensions Space Required Weight Terminal Connector Fusing
24 Vdc (LATCH) input True High 16 20 ... 28 Vdc 1 16
Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point
115 Vac protected output 8 80 ... 130 Vac / 47 ... 63 Hz 8 1
AS-B881-001 Terminal Numbering and Wire Connections
30 Vdc 40 Vdc for 10ms 6 mA (typical) @ 24 Vdc 0.5 ms One per second 30 mA 1.1 mA 0 mA 24± 4 Vdc, 310 mA 1 slot 2.75 lbs (1.25 kg) AS-8534-000 One per group
AS-B881-001 Mechanical Keying for Housings
Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V Dimensions Space Required Weight Terminal Connector
AS-B881-108 Terminal Numbering and Wire Connections
2 A continuous 30 A for one cycle 2A 16 A 5 mA max @ 130 Vac 9 ms @ 60 Hz 9 ms @ 60 Hz 285 mA 240 mA 0 mA 1 slot 2.4 lbs (1.1 kg) AS-8535-000
AS-B881-108 Mechanical Keying for Housings
TOP
TOP
BOTTOM
BOTTOM
(When facing housing, place pins in holes shown by black circles.)
(When facing housing, place pins in holes shown by black circles.)
3-71