Page 71

Specification

AS-B881-508

Specification

AS-B882-032

Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V External Power Supply Dimensions Space Required Weight Terminal Connector

125 Vdc True High output 8 5 ... 140 Vdc 8 1

Description Number of Points Operating Voltage Number of Groups Outputs per Group ON Current Max. per Point Max. per Group Max. per Module Leakage Current Max. Response Time OFF to ON ON to OFF Power Required +5 V +4.3 V -5 V External Power Supply

24 Vdc diagnostic output 32 20 ... 28 Vdc 4 8

AS-B881-508 Terminal Numbering and Wire Connections

4.0 A 29 A < 30 mA < 75 µs < 100 µs 300 mA 0 mA 0 mA 5 ... 140 Vdc 1 slot 2.4 lbs (1.1 kg) AS-8535-000

Dimensions Space Required Weight Terminal Connector Fusing

AS-B881-508 Mechanical Keying for Housings

1 ms 1 ms 300 mA 10 mA 0 mA 24± 4 Vdc, 600 mA (Excluding field load current) 1 slot 2.42 lbs (1.1 kg) AS-8535-000 Electronic, one-per point

AS-B882-032 Mechanical Keying for Housings

TOP

TOP

BOTTOM

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-72

AS-B882-032 Terminal Numbering and Wire Connections

1A 6A 24 A 1 mA max. @ 28 Vdc

(When facing housing, place pins in holes shown by black circles.)

Page 72

Specification

AS-B882-116

Description

24 Vdc Supervised wire output Detects open or short circuits on each I/O point and reports fault to PLC 16 19.2 to 30.0 Vdc 2 8

Number of Points Working Voltage Number of Groups Outputs per Group Continuous Current Max. Per Point Max. Per Group Max. Per Module Off State Leakage Current On State Voltage Drop Inrush Current Power Required +5 Vdc +4.3 Vdc -5 Vdc External Power Supply Dimensions Space Required Weight Terminal Connector Fusing

0.5 A 4.0 A 8.0 A 3 mA max. at 30 Vdc, max. allowable load resistance is 6K Ω 0.5 Vdc maximum at 0.5A 1.0A peak for 0.1 ms at 4 pulses per second while carrying 0.5A DC minimum load current 10 mA 350 mA maximum all outputs ON 10 mA 0 mA (not used) Nominal 24 Vdc at external load current plus 0.5 amps. Supply must be capable of pulse current of external load plus 5 amps. 1 slot 2 lbs (0.91 kg) AS-8535-000 No internal fusing

*For additional details, consult user guide #GM-DISC-800.

AS-B882-116 Terminal Numbering and Wire Connections

AS-B882-116 Mechanical Keying for Housings TOP

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-73

Page 73

B882-239 High Speed Counter Module The B882-239 High Speed Counter Module has two identical and independent counters for applications that require counting or comparisons. Because the module handles the counting within its own internal logic, the PLC is free to do other tasks.

Specifications

AS-B882-239

Number of Counters Number of Auxiliary Inputs Number of Outputs Number of Groups Input Voltage Range Input Current

2 6 6 1 0-32 Vdc 8.1 mA with 32 Vdc supply 5 mA with 28 Vdc supply 1.0 Vdc (max.) @ 0.5 A 0.3 Vdc (typ.) @ 0.5 A 0.4 Vdc (max.) @ 0.1 A 0.2 Vdc (typ.) @ 0.1 A 1.0 mA (max.) @ 32 Vdc 0.5 A continuous per output 1.5 A fusing per group

Each counter counts to 9999, and the two counters can be cascaded to count to 99,999,999. Each counter counts up to 30,000 pulses per second. The module has two modes of operation, high frequency and low frequency, so its maximum count rate varies from 350 Hz (low frequency) to 30 KHz (high frequency).

Output ON Voltage

Because the module acts independently of the PLC, it counts the high speed pulses from the field independently of the PLC scan. The counter automatically reports its current count to the PLC every scan. Where high performance is required, the module’s own outputs can trigger independently of the controller scan.

Max. Count Frequency High Frequency Mode Low Frequency Mode Reset Pulse Width Enable Set Up Time High Frequency Mode Low Frequency Mode Range of Signal Values -Log “1” Neg. Threshold -Log “0” Pos. Threshold -Hysteresis Power Required + 5 Vdc + 4.3 Vdc -5 Vdc Dimensions Space Required Weight Terminal Connector Fusing

The major features of the B882-239 High Speed Counter Module include: • • • • •

Two independent counters (0-32 Vdc, True Low) 0-30 Khz operation with selectable low frequency filter Six auxiliary field inputs (0-32 Vdc, True Low) Six field outputs (0-32 Vdc, True Low) Self-diagnostics

Output OFF Leakage Current Output Load Current

AS-B882-239 Terminal Numbering and Wire Connections

30 KHz 350 Hz 13 µs (min.) 11 µs (max.) 1.3 µs (max.) 1.1 Vdc (min.), 2.2 Vdc (typ.) 3.5 Vdc (max.), 2.7 Vdc (typ.) 0.36 Vdc (min.), 0.49 Vdc (typ.) 188 mA 0 mA 0 mA 1 slot 2.94 lbs (1.34 kg) Included One per group AS-B882-239 Mechanical Keying for Housings

TOP

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-74

Page 74

Specifications

AS-B883-001

Number of Counters Number of Auxiliary Inputs Number of Outputs Voltage Range 5 Vdc 12 Vdc 24 Vdc Transition 5 Vdc 12 Vdc 24 Vdc Output Load Current Max Count Frequency Ramp Time Power Required + 5 Vdc + 4.3 Vdc -5 Vdc Dimensions Space Required Weight Terminal Connector

2 6 3

AS-B883-001 Terminal Numbering and Wire Connections

B883-001 High Speed Counter Module

2.4 to 5.5 Vdc 6 to 16 Vdc 12 to 32 Vdc 0 to 1 1 to 0 2.4 Vdc 1.6 Vdc 5.6 Vdc 4.0 Vdc 11.2 Vdc 8.0 Vdc At 5 Vdc, 140 mA per output 50 kHz 7 V per sec 677 mA 0 mA 0 mA

The Modicon B883-001 High Speed Counter Module is a powerful control tool providing solutions for both simple high speed counting and more involved timing and sampling control applications, all at speeds up to 50 kHz. While programmed directly through a Modicon programmable controller, the High Speed Counter Module is microprocessorbased and operates independent of the PLC. The module provides two counters that can operate separately or jointly, depending on the control system's needs. Counter #1

Counter #2

Bi-direction (up/down) count

Unidirectional up counter

Pulse or Quadrature encoder input modes

1 slot 3.3 lbs (1.49 kg) Included

1 kHz and 1 MHz internal clock

Counts up to 9,999,999

Counts up to 9,999

Two programmable outputs with three modes of operation

Hardwire reset and enable

Hardwire enable and preset

Software reset and enable

Software enable and preset

Programmable match output

AS-B883-001 Mechanical Keying for Housings

TOP

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-75

Page 75

B883-101 and B883-111 CAM Emulator Modules The B883-101 and B883-111 CAM emulator modules are used to automate the operation of metal shaping and cutting presses for any mass production industry such as automobile parts fabrication. The CAM module receives a 12-bit (plus control) parallel position code from an encoder. The module then transmits an 8-bit parallel control code to its discrete outputs based on the received position data. Programming and operation of the CAM module is simple. You load the operating instructions into a CAM module through the PLC via the I/O system. You can define up to 16 output intervals distributed at random among the 8 outputs. The CAM module accepts inputs in binary, binary coded decimal, or Gray code. Once programmed, the module receives, processes, and outputs the position codes at a rate of 4,000 Hz (once every 250 microseconds). If your application requires velocity compensation, choose the B883-111 module. The B883-111 module compensates for changes in velocity.

Specifications

AS-B883-101/111

Number of Inputs Number of Outputs Supply Voltage Internal Signal Loading

12 8 Max. 7 Vdc RTH = 10 kΩs VTH = 0.925 x VDD, (VDD = 5 Vdc ± 5%) 20 to 28 Vdc 32 Vdc max for 10 ms 0.6 Vdc max at 200 mA one channel on Max. 2.5 A per channel 0.5 ms at 5% duty cycle Max. 0.75 mA at 28.8 Vdc Typ. 0.1 mA Max. 20 ms Max. 32 ms

Working Voltage Peak Voltage ON State Voltage Drop Inrush Current OFF State Leakage Current Response Time Transition Time Power Required +5 Vdc +4.3 Vdc –5 Vdc Dimensions Space Required Weight Terminal Connector

AS-B883-101/111 Terminal Numbering and Wire Connections

1000 mA 0 mA 0 mA 1 slot 3.98 lbs (1.81 kg) Included

AS-B883-101/111 Mechanical Keying for Housings

TOP

37 Pin ‘D’ Male Connector BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-76

Page 76

B883-200 Thermocouple Input Module

Specifications

AS-B883-200

Description

Thermocouple input Type B,E,J,K,R,S,T,N or linear mV 10 200 Vdc/Vac (peak) 1°C, 1°F, 10 mV 0.1°C, 0.1°F, 1 mV 100 ms per selected channel 1 sec. max. all channels 13 sec. max. 2 Min. max.

Inputs per Module Max. Common Mode Voltage Resolution Under Program Control Update Time Power-up Time Warm-up Time Power Required +5 Vdc +4.3 Vdc -5 Vdc Dimensions Space Required Weight Terminal Connector

AS-B883-200 Terminal Numbering and Wire Connections

400 mA 5 mA 0 mA

The Modicon B883-200 Thermocouple Input Module is a smart I/O module that multiplexes up to ten thermocouples into three consecutive input registers of the control system. Each B883-200 module provides reference junction temperature compensation, open circuit detection, and linearization for ten thermocouples. Also built-in are self-calibration, internal diagnostics, and 800-Series bus diagnostics. Any mix of type B, E, J, K, R, S, T, or N thermocouple operations or simple -20 to +80 mV input operations may be set by the user under program control. For thermocouple inputs, the PLC can access individual temperature readings in degrees Centigrade, Fahrenheit, or in compensated millivolts. Each time the PLC scans the B883-200 module, it receives the specified temperature or millivolt reading along with open-circuit and module health data. The thermocouple wire is terminated on a special isothermal connector assembly on the housing. Each B883-200 module uses three consecutive input registers and three output registers.

1 slot 4 lbs (1.8 kg) Included

AS-B883-200 Mechanical Keying for Housings

TOP

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-77

Page 77

B883-201 RTD Input Module The Modicon B883-201 Resistance Temperature Detector (RTD) module is a smart I/O module that multiplexes up to eight twoor three-wire RTDs into three consecutive input registers of a control system. Each B883-201 module provides linearization for any mix of 8 RTDs. Also built-in are self-calibration, internal diagnostics, and 800-Series bus diagnostics. American standard platinum, European standard platinum per DIN, or linear resistance input can be selected by the user under program control. When an RTD is selected, the PLC can access each individual temperature reading in Centigrade, Fahrenheit, or in compensated millivolts. Each time the PLC scans the B883-201 module, it receives the specified temperature or millivolt reading along with open-circuit and module health data.

Specifications

AS-B883-201

Description

RTD input American or European 100 Ω Platinum 8 7 Vdc/Vac (peak) 1°C, 1°F, 10 Ω 0.1°C, 0.1°F, 1 Ω 125 ms per selected channel 1 sec. max. all channels 13 sec. max. 2 min. max.

Inputs per Module Max. Common Mode Voltage Resolution Under Program Control Update Time Power-up Time Warm-up Time Power Required +5 Vdc +4.3 Vdc -5 Vdc Dimensions Space Required Weight Terminal Connector

640 mA 5 mA 0 mA 1 slot 4 lbs (1.8 kg) AS-8535-000

Each B883-201 uses three consecutive input registers and three output registers. These registers are assigned to the same slot within the channel.

AS-B883-201 Terminal Numbering and Wire Connections

AS-B883-201 Mechanical Keying for Housings

TOP

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-78

Page 78

Specifications

AS-B884-002

B884-002 PID Module

Analog Inputs Input Range Common-mode Rejection Max. Common-mode Voltage Normal Mode Rejection Accuracy (at 25° C)

4, current/voltage 4 ... 20 mA, 1 ... 5 Vdc, 0 ... 10 Vdc > -90 db, 50/60 Hz 180 Vdc/Vac peak 60 db 0.05% typ, +0.02% max

The B884-002 PID Module provides two completely independent and separate Proportional Integral Derivative (PID) loops. You can configure the PID loops for control strategies including open loop, closed loop, PID, PID on error squared, and cascade control.

Thermocouple Inputs Types Common-mode Rejection Max. Common-mode Voltage Normal Mode Rejection Repeatability (constant temp.) Frequency Inputs

2 B,E,J,K,N,R,S,T > -120 db, 50/60 Hz 180 Vdc/Vac peak 60 db +0.5° F, +0.3° C in 24 hours 1, sine wave/magnetic pick-up (bipolar) and rectangular wave (unipolar)

Input Voltage Range Unipolar Bipolar

2 Vpp to 50 Vpp 10 mVpp to 360 Vpp

Discrete inputs Input Voltage ON Threshold OFF Threshold Min. Turn On Current

2 24 Vdc, potential isolated 5.0 Vdc or more 0.8 Vdc or less 5 mA

Analog outputs Output Range Common-mode Rejection Max. Common-mode Voltage Accuracy (at 25° C) Output Setting Time

2, current voltage 4 ... 20 mA, 1 ... 5 Vdc, 0 ... 10 Vdc > -120 db, 50/60 Hz 180 Vdc/Vac peak 0.2% max, 0.05% typ < 10 ms

Discrete Outputs Output Voltage Output Current OFF State Leakage Loop Solve Time Power Required +5 Vdc +4.3 Vdc -5 Vdc External Power Supply

2 24 Vdc, potential isolated 250 mA, 1 V drop max 0.1 mA max 150 ms 50 mA 2 mA 0 mA 24± 4 Vdc, 330 mA

Dimensions Space Required Weight Terminal Connector

1 slot 4 lbs (1.81kg) Included

You configure the PID module using a configuration program (Part # SW-B8DD-3DA) on an IBM or compatible personal computer. You can download the data either through the PLC or directly to the modules, where it is stored in a non-volatile EEPROM memory. To ensure the highest accuracy and reliability, the module has fully floating, isolated, and protected inputs and outputs. The module has seven independently configured analog inputs (4 voltage/current, 2 thermocouple, 1 frequency), two analog outputs, two discrete inputs, and two discrete outputs. Each loop is assigned two voltage and one thermocouple inputs. There is no need for any analog adjustments such as trimpots for zero, offset, or span, which results in superior accuracy, stability, and reliability.

AS-B884-002 Terminal Numbering and Wire Connections

AS-B884-002 Mechanical Keying for Housings

TOP

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-79

Page 79

B885-002 ASCII / BASIC Module The B885-002 ASCII / BASIC Module runs user-written BASIC programs independently of the controller’s memory logic and scan. It also performs READ and WRITE commands to and from serial devices connected to either of the module’s two RS 232/422 ports (jumper selectable). In addition, its real-time clock/calendar allows the module to run a BASIC program or flag and return a value to the PLC at a user specified date and time. The module provides report generation, interactive operator interface, high level math, peripheral communications, and data storage. Using a dumb terminal or an IBM personal computer with Emulator Software (Part # SW-E885-1DA), you program the module’s 53K of user memory. If you need more memory, you may provide an additional 32K of user EPROM. You can designate part of the memory as retentive variable memory to store formulas or other process parameters.

Specifications Data Exchange Module to PLC Module to Terminal Transmission Rate

AS-B885-002 Via OURBUS, 6 input registers, 6 output registers Via 2 ports, RS 232C or RS 422 110, 300, 600, 1200, 2400, 4800, 9600, 19200 baud software selectable

Power Required +5 Vdc +4.3 Vdc -5 Vdc

RS 422 mode 500 mA 1760 mA 0 mA

Dimensions Space Required Weight Terminal Connector

1 slot 3 lbs (1.4 kg) Included

AS-B885-002 Terminal Numbering and Wire Connections

Pin # Direction Signal 1 2 3 4 5 6 7 12 13 14 15 16 17 18

N/A OUT IN OUT IN IN N/A OUT OUT OUT OUT IN IN OUT

19

IN

20 21 25

OUT IN IN

Protective ground RS232 Send data RS232. Receive data RS232 Request to send RS232 Clear to send RS232 Data set ready RS232 & RS422 Common RS422 Request to send high RS422 Request to send low RS422 Send data high RS422 Send data low RS422 Clear to send low RS422 Clear to send high +5V (Current limited, 5mA by 1K) Select input-RS422 high/ RS232 low RS232 Data terminal ready RS422 Receive data high RS422 Receive data low

RS 232 mode 400 mA 1000 mA 0 mA

AS-B885-002 Mechanical Keying for Housings

TOP

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-80

Page 80

B885-101 and B885-111 Motion Modules Modicon B885-1xx Motion Modules are high performance, single axis servo motion controllers contained in a single-width 800-Series I/O module. They are designed to plug directly into the I/O rack of the Modicon 984 PLC, although they are capable of standalone operation. They can control brushless and brush-type servo motors, as well as hydraulics. The modules use Schneider Automation's patented Direct Numerical Processing (DNP) technology. Advanced digital brushless motion control eliminates potentiometer adjustments and analog velocity loops for optimal control. The B885-101 module uses a resolver to provide feedback for the position, velocity, and commutation of the motor. Essentially, a rotary brushless transformer that provides absolute position information to the motion module, the resolver gives the module a high degree of noise immunity.

The PLC communicates with the motion modules through six input and six output registers with the control instructions providing a powerful, smooth and fast link between the two. Adjustable command buffering and direct register to function bits provide added communication speed for high response functions. Motion programs, developed using MMDS, are either stored directly in the flash memory of the motion module or as registers in the PLC. The Modicon Motion Development Software (MMDS) is an online/off-line, menu driven package (Part # SW-MMDS-1DB) for the IBM-AT or compatible computers. It enables the user to set up, program, operate and diagnose operation of the motion module. The program and file manipulation features are a versatile system for application management. The MMDS communicates via a computer serial port to the Modbus port on the motion module.

The B885-111 module additionally has two quadrature encoder interfaces for extra position and velocity feedback. Control communication interface to the B885-1xx modules can be either through the 800 I/O system backplane or the Modbus/RS-232 serial port. The module is designed to work directly with the Modicon Cyberline 1000 series brushless servo amplifiers as well as those of third-party vendors.

AS-B885-1xx Mechanical Keying for Housings

AS-B885-111 Encoder Feedback Signal Wiring to Breakout Module

AS-B885-1xx Terminal Numbering and Wire Connections

TOP

BOTTOM

(When facing housing, place pins in holes shown by black circles.)

3-81