984 Programmable Logic Controllers and 800-Series Input/Output Modules, pages 81 to 90

Pages 81 to 90 of 123

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Modicon B807, Modicon B865, AEG B807, Gould B807, Schneider B807, AEG B865, Gould B865 and Schneider B865

Page 81

Specifications Motion Absolute Positioning Range Speed Range Digital Servo Loop Position Loop Update Velocity Loop Update Commutation Update Potentiometer Adjustments Feedback Resolver Max. Speed Resolution System Accuracy Typical Worst Case Position Repeatability Encoder (-110 only, two channels) Type Voltage Impedance Frequency Nominal Maximum Input Multiplier Maximum Speed System Accuracy Source Power Supplied by Module (Encoder may be powered externally)

232 bits; in., mm, or other units 232 to 1; counts/sec, in/sec, mm/sec, RPM, etc. 1 msec 0.5 msec 0.25 msec None; parameters set in software Modicon "T" type brushless Used for position, velocity and commutation 6,000 RPM, motor/drive dependent 65535 (16-bit) counts/revolution (maximum) ± 10 arcmin ± 15 arcmin ± 3 arcmin Encoders supplied by customer. Used for position and velocity Differential or single end 5 ... 24 volt ± 20% >500 Ω @ 5V nominal 200 KHz 500 KHz 4X Encoder dependent, 2 MHz internal pulse rate max. Encoder dependent; 0.5 arcmin maximum 400 mA @ 5 Vdc ± 10% and/or 200 mA @ 12 Vdc ± 10%

Drive Enable Output Drive Fault Input

3-phase bipolar commutated current command compatible with all Modicon Cyberline drives or Bipolar current or velocity command (± 10 V, 3 mA max., 12 bit resolution) for DC or hydraulic drives Form "C" relay contact, 30 Vdc @ 0.5 A resistive max. True high with internal pullup, TTL compatible

I/O Digital Inputs Digital Outputs Analog Output Analog Input

7 (24 Vdc, ± 20 %) 3 (24 Vdc, ± 20 %, 150 mA max. each) ± 10 V, 3 mA max., 12 bit resolution ± 10 V, 10 bit resolution

Communications Port Baud Rate Connector Backplane

RS-232 serial, Modbus slave 300 ... 9600 baud, software selectable (9600 default) DB9, female I/O bus, 6 input/6 output registers

Servo Output

Power Requirements External Power Supply I/O Rack Power +5.0 V +4.3 V -5.0 V Physical Space Required Weight

3-82

AS-B885-1xx

24 Vdc ± 20% @ .375 A max. plus output current draw 25 mA 0 mA 0 mA 1 slot 2 lbs (.9 kg)

Page 82

Specification

AS-B984-100/101

Mode of Operation Working Voltage Response Time Inputs Outputs Input Number of Inputs Number of Groups Source Resistance ON Level (<1M Source Impedence) OFF Level (0 Source Impedence) ON Condition Threshold Input Wetting Current Outputs Number of Outputs Number of Groups Min. ON State Output Voltage ON Current

True high 20 ... 28 Vdc

Max. OFF State Leakage Min. Load Current Diagnostic Information Power Required +5 Vdc +4.3 Vdc -5 Vdc External Power Required

Dimensions Space Required Weight Terminal Connector AS-B984-100 Terminal Numbering and Wire Connections

100 µsec max (no filtering) 1 msec max. 16 1 1000 Ω 19.2 Vdc 6 Vdc 18 Vdc 6 mA minimum at 24 Vdc 8 1 19.2 Vdc Max. 1 A per channel Max. 8 A per module 1 mA 100 mA Open Load, Short to * Ground or Supply, Current limit, Over temperature 0 mA 0 mA 0 mA CPU 20 ... 30 Vdc, 2A (Excluding field load current) Output 20 ... 30 Vdc, 10A

B984 Discrete High Speed Logic Solver Module The Modicon B984-100 Discrete High Speed Logic Solver offers the power of a 984 PLC with the response of an intelligent I/O module. With a total system throughput of less than one millisecond, the module provides the capability to control high speed applications not possible with conventional PLCs. The full 984 basic instruction set makes the module compatible with existing 984 application and programming software, and 4K user logic plus 2K registers provide ample space for application programs. The B984-100 is fully compatible with the rest of the 984 Family. It services its own dedicated I/O and communicates with the host PLC via the I/O bus. The B984 module and the host PLC pass four or eight 16-bit registers bi-directionally each time the host PLC scans its logic. A built-in Modbus port on the B984 allows connection to programmers, operator interfaces, local area networks, and host computers. Inputs on the B984 have programmable filtering to allow for quick response and maximum system reliability. Outputs provide fault diagnostic information which is annunciated in the B984 and is available to the host PLC. Multiple B984 modules may be used in any control system using 800-Series I/O. They can be inserted in any slot, and are limited only by the I/O bits available in the system.

1 slot 2 lbs (0.9 kg) Included AS-B984-100 Mechanical Keying for Housings TOP

BOTTOM

(When facing housing, place pins in holes shown by black circles.) MAX WIRE SIZE IS ONE 14 AWG WIRE; TWO 18 PIN CONNECTORS

*AS-B984-101 does not support open load detection.

3-83

Page 83

Housings

800-Series Housings are used to hold the PLC, Option Processors, Power Supplies, I/O Interfaces, and I/O Modules. The two styles of housing available are Primary and Secondary. The primary housing is the first housing in an I/O drop. All other housings in the I/O drops are secondary housings. Housings are connected via Signal and Power cables. There are three sizes of housing available: 10 inch (part numbers begin H810), 19 inch (part numbers begin H819) and 27 inch (part numbers begin H827). The 10 inch housing has four module slots, the 19 inch housings have seven module slots, and the 27 inch housings have eleven module slots. I/O slots in an H810, H819, or H827 require a field wire terminal connector where wiring to the field sensing/switching devices is made. Once wired, the terminal blocks remain intact while I/O modules are replaced for service. Terminal blocks can be detached without disturbing field wiring if you ever need to replace a housing. W801 signal cables used to pass OURBUS data between housings in a drop have the following lengths: 2 ft. (0.6 m), 6 ft. (1.8 m), and 12 ft. (3.6 m). Total cable length in a drop must not exceed 20 ft. (6 m). W802 and W808 power cables pass power from a housing with a power supply to a housing without a power supply. W804 cables pass power signals to a housing with an auxiliary power supply. These three cables are also available in the following lengths: 2 ft. (0.6 m), 6 ft. (1.8 m), and 12 ft. (3.6 m). For more information on cables, see Cabling section, page 2-86. Primary Housings In a local I/O drop, you can choose either the H810-208, H810209, H819-209, or H827-209. The 984-38x and 48x may use the H810-208 (10 inch) housing. The PLC occupies the first (left-most) slot, with the other three slots left for I/O modules. The H810-208 cannot be connected to secondary housings. The 984-38x, 48x, and 68x series PLCs may use either the H810-209 (10 inch), the H819-209 (19 inch) or the H827-209 (27 inch) PLC housings. The PLC must occupy the first (left-most) slot. Option processors (68x, 78x only) or local I/O modules may occupy any other available slots in the housing. Additional local I/O housings connect to the PLC housings through Signal and Power cables. These cables plug into connectors located at the lower left of the Primary housing. In a remote I/O drop, the primary housing is the first housing and contains the remote I/O interface. You can choose either the H810-208, H819-103 and H827-103 housings, or H810-209, H819-209 and H827-209 primary housings. H819-209, H827-209, and H810-209 Primary Housings The H819-209, H827-209, and H810-209 housings are primary housings for slot-mount PLCs and remote 800 Series I/O drops. The H819 contains seven slots that house a slot mount PLC or a P890/P892 Remote I/O Interface, and up to six I/O modules. The H827 contains 11 slots that house a slot-mount PLC or a P890/P892 Remote I/O Interface and up to 10 I/O modules.

3-84

The H810 contains 4 slots that house a slot mount PLC or a P890/P892 remote I/O interface, and up to 3 I/O modules. The H810 supports 685, 785 controllers and option modules. The H810, H819 and H827 may be mounted on a wall or inside a protective NEMA cabinet. The H819 may also be mounted in a 19 inch standard rack; special mounting flanges are provided for a rack-mount installation. The H8xx-209 housings are designed so that all control, power, and/or drop interface devices must be located in slot one. H819-103 and H827-103 Primary Housings The H819-103 and H827-103 housings are primary housings for remote 800-Series I/O drops. The H819 contains seven slots that house an I/O power supply, an RIO interface device, and up to four I/O modules. The H827 contains eleven slots that house an I/O power supply, an RIO interface device, and up to eight I/O modules. Both the H819 and H827 may be mounted on a wall or inside a protective NEMA cabinet. The H819 may also be mounted in a 19 inch standard rack; special mounting flanges are provided for a rack mount installation. The first 1.5 slots contain a P802 or P810 primary power supply. The next 1.5 slots contain either a J890 or J892 RIO Interface. The first (left-most) slot in the housing contains the 984-38x/48x or P89x. The remaining three slots are for I/O modules.

Page 84

800 Series Housing Technical Specifications Description AS-H819-209 AS-H827-209 AS-H819-103 AS-H827-103 AS-H819-100 AS-H827-100 AS-H810-208 AS-H810-209 AS-H810-100

Primary Housing, 19" Primary Housing, 27" Primary Housing, 19" Primary Housing, 27" Secondary Housing, 19" Secondary Housing, 27" Primary Housing, 10" w/OURBUS only Primary, 10" w/System Bus and OURBUS for 685, 785 controllers Secondary, 10" w/OURBUS only

Maximum Available I/O Slots AS-H819-209 6 AS-H827-209 10 AS-H819-103 4 AS-H827-103 8 AS-H819-100 7 AS-H827-100 11 AS-H810-xxx 3 Earth Connection Earth ground screw on lower edge of subrack Environmental Operating Temperature 0 ... 60°C Relative Humidity 0 ... 95% (non-condensing) Shock Resistance 10 G for 10 ms Physical Space Requirement (W x H x D) AS-H810 ... xxx 10.25 x 13.5 x 8.9 in (261 x 343 x 255 mm) AS-H819 ... xxx 17.5 x 13.5 x 8.9 in (444 x 343 x 225 mm) AS-H827 ... xxx 27.1 x 13.5 x 8.9 in (688 x 343 x 225 mm) Weight AS-H810 ... xxx 10 lbs (4.6 kg) AS-H819 ... xxx 15 lbs (6.8 kg) AS-H827 ... xxx 20 lbs (9.1 kg)

H810-208 Primary Housing The H810-208 is a primary subrack for local 984-38x and 48x systems, or remote I/O drops using P89x interfaces. This rack is used stand-alone and cannot be connected to secondary subracks. The H810-208 is designed to be mounted on a wall or in a standard NEMA enclosure. Secondary Housings All housings in a local or remote I/O drop, except the primary housing, must be secondary housings. Incoming power and signal cables connect on the top of the housing. Outgoing power and signal cables connect on the bottom. Secondary housings available are the H810-100, H819-100 and H827-100 secondary housings. H810-100, H819-100 and H827-100 Secondary Housings The H810-100, H819-100 and H827-100 housings are secondary housings for local or remote 800 Series I/O drops. The H819 contains 7 slots that may house I/O modules. The H827 contains 11 slots that may house I/O modules. The H810 contains 4 slots that may house I/O modules. If auxiliary I/O power is required, the power supply must be located in the first slot. The H810, H819 and the H827 may be mounted on a wall or inside a protective NEMA cabinet. The H819 may also be mounted in a 19 inch standard rack; special mounting flanges are provided for a rack mount installation. Because they are used only as secondary housings, the H810100, H819-100 and H827-100 housings must never contain an RIO interface device.

3-85

Page 85

800-Series I/O Cabling

Two cables, a signal and a power cable, are required to interconnect the primary housing and the secondary housing(s) in an 800 I/O drop. The signal cable, in effect, extends the OURBUS to the secondary housing(s) and the power cable provides power to the modules within the secondary housing(s).

I/O Cable Configurations w/H8xx-209 Primary Housing

The total distance between the PLC housing and the farthest secondary housing must not exceed twenty feet. Any combination of cable lengths is allowed, as long as the twenty foot limitation is observed. When an auxiliary power supply is added to a secondary housing, the power cable entering that housing must be a W804 power cable. This cable prevents the auxiliary or booster power supply from interfering with the main power supply in the PLC or another auxiliary power supply. The following figure shows an auxiliary power supply added to a secondary housing and the corresponding cabling. When a 984X controller is used with local I/O, a special cable, W929, connects the controller to the first housing. This housing must be a secondary-type housing, H8xx-100, and must contain an auxiliary power supply. The following table shows the available cables. The “xxx” at the end of the part numbers should be replaced with appropriate numbers from the right side of the table when ordering cables.

(1) 984-38x/48x, P89x occupy slot 1, slot 2 available for I/O module. (2) 984-68x/78x occupy slot 1 and 2. * Maximum 32 modules per drop (Maximum 2 racks for 984-38x/48x).

800-Series I/O Cables

3-86

Available Lengths 5 ft 6 ft 12 ft

Model

Description

1.5 ft

20 ft

AS-W801-xxx

I/O signal cable between racks

-002

N/A

-006

-012

N/A

AS-W808-xxx

I/O power cable to added rack w/o power supply

-002

-005

N/A

N/A

N/A

AS-W802-xxx

I/O power cable to added rack w/o power supply

N/A

N/A

N/A

-012

N/A

AS-W804-xxx

I/O power cable to added rack with power supply

-002

-005

N/A

-012

N/A

AS-W929-xxx

Local I/O cable for 984X

N/A

N/A

-006

-012

-020

Page 86 read from a scan by OCR; it may hold reading errors

l/O Cable Configurations w/H8xx-103 Primary Housing - - - - 31 2105 be - - 2:7. 1:, - - - - - - -H1 F Wa RC ed ea pe [ad a Oyosojoyoyayoyo i DIDO /O OO ;o Oo RECIFE a a i] EL HSI. 1 ty Tl | Ge La Ale Gee Goll Goll Go Ln Go Lo Oo;oo papoyayoyoyoya DIDJOJOID|O OOOO oO a | F Dee Le La Loe Lo Go Lode Le Ojo jo;osojoyoyoaya i DID|O/OO Oooo VE ES ak ED | Tea] A RR OAoopoapoyoyoyoyoya OOO OOO Oooo yo eiejepe taeda WES WES o - ren! TAT] RAT RAT RA A] ea O]/a;o;ayayoya D/O}O;O;o)/o/0 Ce ee ee * Maximum 32 modules per drop.

3-87

Page 87

800-Series I/O Power Supplies

A local or remote I/O system requires a power supply for the I/O modules and for communications support between the modules and the PLC. In some cases, the power supply is built into the PLC or into the remote I/O interface where, in other cases, the power supply and the I/O interface are separate components. Certain applications will require an auxiliary power supply should the I/O requirements exceed the capacity of the primary supply. Below is a list of 800-Series I/O power supplies, both integrated and auxiliary. To determine the power requirements of your system, you must add together the individual power requirements of the I/O and option modules within your system.

Model

Description

Voltage

I/O Power Available(mA) Slots +5.0V +4.3V

-5.0V

AS-P802-001 AS-P810-000 PC-X984-68x/78x PC-X984-38x/48x AS-P890/892-000 AS-P830-000 AS-P840-000

Remote Primary & Secondary Remote Primary & Secondary Internal Supply for Local I/O Internal Supply for Local I/O Internal Supply for Remote I/O Secondary Remote Primary/Secondary

24 Vdc 115/230 Vac 115/230 Vac, 24 Vdc 115/230 Vac, 24 Vdc 115/230 Vac, 24 Vdc 115/230 Vac, 24 Vdc 115/230 Vac

1.5 1.5 1.5 1 1 1.5 1.5

500 300 5001 2502 2502 5003 500

1

Total max. = 8,000 mA Total max. = 3,000 mA 3 Total max. = 6,000 mA 4 Total max. sum of (+4.3V and +5V) 2

Note: Model PC-X984 is for E984 controllers.

3-88

@ 55°C = 15000 mA @ 60°C = 12000 mA

2500 5000 8000 3000 3000 5000 50004

10100 5000 6000 3000 3000 6000 100004

Page 88

P802 I/O Power Supply

P810 I/O Power Supply

A P802 Power Supply may serve as either a primary or auxiliary power unit in an 800-Series I/O drop. Its input voltage is 24 Vdc.

A P810 Power Supply may serve as either a primary or auxiliary power unit in a 800-Series I/O drop. Its input voltage (115 Vac or 230 Vac) is determined by the way the input terminal block is wired.

The P802 is 1.5 slots wide. When used in a primary housing, it consumes the first 1.5 slots and is followed immediately by a remote I/O interface. When used as an auxiliary power supply, it consumes the first two slots in a secondary housing.

The P810 is 1.5 slots wide. When used in a primary housing, it consumes the first 1.5 slots, and is followed immediately by a remote I/O interface. When used as an auxiliary power supply, it consumes the first two slots in a secondary housing.

P802 Terminal Numbering and Input Connections

P810 Terminal Numbering and Input Connections

115 Vac Operation: Jumper installed between terminals 1 & 2 230 Vac Operation: No connection between terminals 1 & 2

AS-P802-001 I/O Power Supply Technical Specifications

AS-P810-000 I/O Power Supply Technical Specifications

Power Supply Input Voltage Output Voltage +5 Vdc +4.3 Vdc -5 Vdc

2.5 A 10.1 A 0.5 A

Power Supply Input Voltage Output Voltage +5 Vdc +4.3 Vdc -5 Vdc

Environmental Operating Temperature Relative Humidity Shock Resistance

0 ... 60°C 0 ... 95% (non-condensing) 10 G (11 ms)

Environmental Operating Temperature Relative Humidity Shock Resistance

Physical Space Requirements

Weight

24 Vdc

1.5 slots in an H8xx-103 Primary housing, or 2 slots in an H8xx-100 Secondary housing 7 lbs (3.2 kg)

Physical Space Requirements

Weight

115/230 Vac 5.0 A 5.0 A 0.3 A 0 ... 60°C 0 ... 95% (non-condensing) 10 G (11 ms) 1.5 slots in an H8xx-103 Primary housing, or 2 slots in an H8xx-100 Secondary housing 7 lbs (3.2 kg)

3-89

Page 89

P830 I/O Power Supply

P840 I/O Power Supply

A P830 Power Supply serves as an auxiliary power unit in an 800-Series I/O drop when the power limitations of the primary power supply are exceeded.

A P840 Power Supply may serve as either a primary or auxiliary power unit in a 800-Series I/O drop. Its input voltage (115 Vac or 230 Vac) is determined by the way you wire the input terminal block.

The P830 is 1.5 slots wide. It must be installed in the two leftmost slots of a secondary housing.

P830 Terminal Numbering and Input Connections

AS-P830-000 I/O Power Supply Technical Specifications Power Supply Input Voltage Output Voltage +5 Vdc +4.3 Vdc -5 Vdc Environmental Operating Temperature Relative Humidity Shock Resistance Physical Space Requirements Weight

3-90

115/230 Vac 24 Vdc 5000 mA 6000 mA 500 mA Total current must not exceed 6000 mA 0 ... 60°C 0 ... 95% (non-condensing) 10 G (11 ms) 2 slots in a secondary subrack 3 lbs (1.4 kg)

The P840 is 1.5 slots wide. When used in a primary housing, it consumes the first 1.5 slots, and is followed immediately by a remote I/O interface. When used as an auxiliary power supply, it consumes the first two slots in a secondary housing.

P840 Terminal Numbering and Input Connections

AS-P840-000 I/O Power Supply Technical Specifications Power Supply Input Voltage 115/230 Vac Output Voltage +5 Vdc 5.0 A1 +4.3 Vdc 10.0 A1 -5 Vdc 0.5 A Environmental Operating Temperature 0 ... 60°C Relative Humidity 0 ... 95% (non-condensing) Shock Resistance 15 G (11 ms) Physical Space Requirements 1.5 slots in an H8xx-103 Primary housing, or 2 slots in an H8xx-100 Secondary housing Weight 7 lbs (3.2 kg) 1 Total max. sum of (+4.3V and +5V) @ 55° C = 15000 mA @ 60° C = 12000 mA

Page 90

Remote I/O Drop Interfaces

At each remote drop is a remote I/O (RIO) interface device that communicates over the coaxial cable with the RIO processor in the PLC. The RIO interface contains a set of switches that you use to set the address for the drop. There are various kinds of RIO interfaces you can use, depending on the I/O Series in the drop and the type of RIO processor in the PLC. According to your application requirements, you may select RIO interfaces that provide the drop with ASCII device support. I/O interfaces are available with a variety of features (See table below). The remote I/O processor can contain an integrated power supply, otherwise, a power supply has to be mounted in the primary housing. An additional power supply can be mounted in any secondary housing if required.

Interfaces Feature

J890

J892

P890

P892

D908

J290

J291

Remote I/O Processing ASCII Communication Integrated Power Supply Distributed Control Dual Cable Option yes no no no yes yes yes no no yes yes no yes no no yes yes yes no no no no no yes yes yes yes no no yes yes no no no no

3-91