The text of a manual · part 12 of 13
984 Programmable Logic Controllers and 800-Series Input/Output Modules, pages 111 to 120
Pages 111 to 120 of 123
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon B807, Modicon B865, AEG B807, Gould B807, Schneider B807, AEG B865, Gould B865 and Schneider B865
Page 111
Modicon Connectors A series of connectors, installation packs, crimp tools, and blade packs is also available. Connector Installation Description Tool RG-6/U Male F Connector 60-0528-000 52-0488-000 RG-6/U Male BCN Connector N/A 52-0401-000 RG-11/U Male F Connector 60-0530-000 52-0399-000 Self Terminating F Connector, for Non-quad Shielded RG-6/U Drop Cables 52-0411-000 Self-terminating F Connector for RG-6/U Drop Quad Shielded Cables MA-0329-001 Type F, Quad cassette, pack of 10 Part # 52-0400-000
Crimp Tool
Blade Pack
N/A
60-0529-000
0435 09432
N/A
N/A
60-0531-000
Keep in mind, when you plan a remote I/O layout, that the maximum allowable attenuation loss between the PLC and any remote I/O drop is 35 dB. If you use the single cable mode and you want to service a large number of remote drops, you may be forced to use a splitter.
Remote I/O Cable Topologies A linear cable run with a tap to each remote drop is the easiest and most reliable topology. We recommend that you use Modicon Rev. C taps with your installation. We also recommend that you avoid the use of splitter configurations unless you have a compelling application need for such a topology. Several 984 PLCs have optional remote I/O processors that provide two remote I/O cable port connectors, allowing you to implement dual and redundant cabling strategies. In dual mode, two trunk cables are run along separate routes to different sets of remote I/O drops. The dual mode of cabling allows you to support multiple remote I/O drops (up to 32 depending on the PLC) without having to balance cable on two sides of a splitter. In redundant mode, the two trunk cables are run on parallel paths to the same series of remote I/O drops. The redundant cable mode, using a two-port RIO Processor, provides your system with additional communications integrity. Because two cables are run to each drop, a redundant cabling strategy also requires two RIO cable ports on the interface module at each remote I/O drop.
3-112
Page 112
The following tools are designed to help you configure 800 Series remote I/O systems. Refer to the following configuration pages associated with the remote I/O interface you have chosen. 1. P890 or P892 remote drop in H810-208 four-slot housing. 2. P890 or P892 remote drops in H810, H819 or H827-209 housings. 3. J890 or J892 remote I/O drops.
3-113
Page 113
INTERFACE
Bable | ASCII aspegond | Snge | Mia aspegson4 | Sno 2
POWER SUPPLIES hy +06 +4 AS os) Toba Vee ing tin Ap tn ones
Seconda | APES) 120 WAC
45Fese001) 240 ¥ac at VDC S000 000 =o Fro a
Eech rtefece lisedinchides « 2000m4 Power Supp ky fee bebe). Blane roqulroment> for housing ¥41
(pri rary } nvuet rot ooco ed ony of deo Enboties ohrowin
Touwgos thio oon guna ion dies ot
DO Sehect the conmponentsshown on appear ig page, wehin the guidelines shove. DO The cstetog numbers in the shed oo Gon prize your billot risteried .
O Configure eryrencbe IS drops required (924-4o0o).
Poulos for Drop Chon guna ones
OA sein un of one howeding can be configured per drop if uedieg te H 1c. h,
3-114
Page 114
H810-208 Configuration (Remote I/O) (P890/P892)
System Number _____ (page )
Configuration 2 I/O Drop P89_-001 PS/RIO
8 I/O slot
8 I/O slot
8 I/O slot
Housing H810-208
Interface
Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits
+5Vdc +4.3Vdc -5Vdc Total Power Housing #1
I/O slots may contain: Any B8xx-xxx I/O Module or a J878-000 Modbus modem
3-115
Page 115
INTERFACE
Cable AS Il
Topo Prot:
S5P2o-004 | Snge he, ASP | Sage 2
HOUSINGS
Pri Sec a“ once! The inst housing in a booal I systern rust be Winch = | ASH 10-200 hae, Poirrery, the renesining housing, 2@comckny. (4aots) | SSHS 10209 | SSH 0-100
19 inh (Padots] | SSH 19-208 | AS-Ho19- 100
2? inch (dd stots) | SEH SOP 209 | OS Hoe. 100
CABLES LF oeeoodiory hee eee oar Uae, od ened power cables 1S t. 5.08. Bot, eat. 2.0 t. een epuierd. are Povrer Mobe: Different power cables are wpe for syshenis with ened without supe. We Supe, poaver Supplies. PS. PE WSIS Crem) OE WAS OAC he, Pree SH OWS 14 Chrocese the bergth required . WG, PS. Ee WIC Crem) OE Wa OAC hye, hye, A WEOR 01 Signal AS Wen-one| MI AS WEnd-ooe] nL as Weot ot POWER SUPPLIES a Bower pour oments for sappy +00 +4 VOC ab Total housing #4 (primary) nvuot not Wokege ter hy ies Ah tr Prenear od any oF dees Enaibot ions eo vit Susiliery APE ie] 10 WA F tebalsysten power requinem arts 20 VAC Ee S000 ices Torso eecned CFU 's inbemesl power supoly cepesbiiby, on auediery power supply slated Bt mmust be edded in alot 1 of the rest at Wo S000 O00 S00 [aon . secon deny howuire
Tous Gio cont guration dee ob OSalect the comporentsshown on opposing page, within de guidelines ebove. O The catalog numbers in the sheded bower com prise your billof metered.
Foul. es for Drop thon guna ones
Obfesdinum dloaveble [A> configuration is Se modules, 5 howaings.
O Recomm ended bobal length of cabling between first end beet housing is 20 feet.
OExpercion bofifth howding addresses up bo Stred [eS sok when 157 ings ere Used with price comiguretion.
3-116
Page 116
P890/P892 Remote Drop Configuration
System Number _____ (page )
P89_-000 PS/RIO
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
Housing H8 -209
Interface
Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits
+5Vdc +4.3Vdc -5Vdc Total Power Housing #1 W80___-0__ Power Cable 8
I/O slot
8 I/O slot
W80___-0__ Signal Cable
8 I/O slot
8 I/O slot
8 I/O slot
I/O slots may contain: Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
Housing H8 -100 or P8___0-000 Aux Power Supply Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits
+5Vdc +4.3Vdc -5Vdc Total Power Housing #2
(To additional housings)
3-117
Page 117
P890/P892 Remote Drop Configuration W80___-0__ Power Cable P89_-000 PS/RIO Interface
8 I/O slot
8
I/O slot
System Number _____ (page )
W80___-0__ Signal Cable 8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8
I/O slot
8 -
I/O slot
Housing H8 -100
Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits
+5Vdc +4.3Vdc -5Vdc Total Power Housing #1 W80___-0__ Power Cable 8
I/O slot
8 I/O slot
W80___-0__ Signal Cable
8 I/O slot
8 I/O slot
8 I/O slot
System slots may contain: Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
Housing H8___-100 or P8___0-000 Aux Power Supply Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits
+5Vdc +4.3Vdc -5Vdc Total Power Housing #2
(To additional housings)
3-118
Page 118
P890/P892 Remote Drop Configuration
System Number _____ (page )
W80___-0__ Power Cable 8
I/O slot
8 I/O slot
W80___-0__ Signal Cable
8 I/O slot
8 I/O slot
8 I/O slot
System slots slots may contain: Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 I/O slot
8 I/O slot
Housing H81 -209 or P8___0-000 Aux. Power Supply
Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits
+5Vdc +4.3Vdc -5Vdc Total Power Housing #2
3-119
Page 119
INTERFACE
Cable SS Il Tope Proortes AS ESOO1 | Sinofe hy, 85-07 Oe Cua hy Ooo 404 Singe 2 O,5-oe 1 Dual 2 HOUSINGS Prircery Sac omchury ! The fret housing ina keesd |G systern rust be Woireh | SSH 10-20 rads Poimery the reneining Fossinoe, S@comcery, (4sons) | SSHS10-209 | SSH edo- 100 13 inch iF steers, “SH827-1035 | os Hoyo 400 iT T 2? inch (11 ots} AS-H819-1 03, SS-H ee? 100 | CABLES LF oeteoeerediory hoa eee ae uncer, eign gad powoe cabbies 1. S08. Bate. eat. 120 ¢. a equired. ane Power Mob): Different power cables ere weped for stern with end without eu. WK Ope, poer supplies, Po. Sa Wea Caes | OV why Oe PAG, SON SaCee: Cay Se OS ayaa hd Chrocese hee bength required . WANG, Ps. Se eh SoD Cae | Oy Wea Oe PAG, PAS, De 011 Sona OE RSI = Ce: hala, EE WRI = NE hae, ASME 01 oF r POWER SUPPLIES = rom te for Seely +a aD «GVO Tomy || Megat At (ocean) meet not Vokege iro iro iro Forres hone Prinener [45a qaooo] 120 Wc F tekatayrtern: power require enue Susilieny 240 WAC S000 5000 200 410200 sxoeed CAU's intemal power supply map ebiiby, an sundieny power supply APES Ooo] 1c WS Pitest bet added in dot dof thee ret 290 W400 rows. Aue Only aoe exe : secon deny heasing 78, Prine power sup ph is required bo L To use Hho oon gure ion dee ot
DO Select he con ponent sshown on op posing pege, within thee guidelines ebhove, DO The stele munibeers in thee sheded Bese con prise your Bill of nesterial.
Foul oo For
Eerop C.onl puro OMesin unm alloveble [E> configuration is Se modules, 5 housings. DO Bibsldrop rust mot eeceed CPL imitetions(se= CAI specication sheet. O Recomm ended bobal bength of oebling betvesen first ered beet Fousdig i= 2ofeet. D1 Exp redom bottfth: Froaiesireg addresses up bo Satie [KO sot avheen 15° Rrocesing =: ane uesed with prion configuration.
3-120
Page 120
J890/J892 Remote Drop Configuration
System Number _____ (page )
P840-000 P810-000 Primary
J89 -00 8 Remote I/O
- 8 I/O slot
- 8 I/O slot
- 8 I/O slot
- 8 /O slot
- 8 I/O slot
- 8 I/O slot
- 8 I/O slot
I/O slot
Housing H8 -103
Interface
P/S
Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits
+5Vdc +4.3Vdc -5Vdc Total Power Housing #1 W80___-0__ Power Cable 8 I/O slot
8 I/O slot
8 I/O slot
W80___-0__ I/O slots may contain: Any B8xx-xxx I/O Module or a J878-000 Modbus modem
Signal Cable 8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
8 I/O slot
Housing H8___-100 or P8___0-000 Aux. Power Supply Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits
+5Vdc +4.3Vdc -5Vdc Total Power Housing #2
(To additional housings)
3-121