Page 101

984-685/785 Local Drop Configuration

System Number _____ (page )

W80___-0__ Power Cable 8 I/O slot

8 I/O slot

W80___-0__ Signal Cable

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

Housing H8 -100 or P8___0-000 Aux. Power Supply Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits

+5Vdc +4.3Vdc -5Vdc Total Power Housing #1 W80___-0__ Power Cable 8

I/O slot

8 I/O slot

W80___-0__ Signal Cable

8 I/O slot

8 I/O slot

8 I/O slot

System slots may contain: Any B8xx-xxx I/O Module or a J878-000 Modbus modem

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

Housing H8___-100 or P8___0-000 Aux Power Supply Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits

+5Vdc +4.3Vdc -5Vdc Total Power Housing #2

(To additional housings)

3-102

Page 102

984-685/785 Local Drop Configuration

System Number _____ (page )

W80___-0__ Power Cable 8

I/O slot

8 I/O slot

W80___-0__ Signal Cable

8 I/O slot

8 I/O slot

8 I/O slot

System slots slots may contain: Any B8xx-xxx I/O Module or a J878-000 Modbus modem

8 I/O slot

8 I/O slot

Housing H81 -100

Housing H8 -100 or P8___0-000 Aux. Power Supply

Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits

+5Vdc +4.3Vdc -5Vdc Total Power Housing #2

3-103

Page 103 read from a scan by OCR; it may hold reading errors

PU r Select CPU hype bee on Con UnoaKon, Menor, ered Yeo Acedia: bo dus Rance [ko Ciserete [ko Teta) [ko Bites reaqurencearts. Forts Plus Ports [eo BitsOrop** peer aeehern Iikoaurt The (0) bubs cer dronassunre he preeioe [2 | oo [| saps | siesie2 [me | sadn use ofa PES or JBI, Taibe ore aot fo eed Oe crete FD or HOUSINGS L otal + perteen JC? Ear Reeves. Prirresry Scorch The fst housing in soos WG rystenn nrust be Winch = | A542 10-20 a Pirrerythe renceining housing, 52 corny. (4eots) | SSH 10-209 | SS-HS10- 100 19 inch (Patots) | SSHS 19-209 | SS-HO19- 100 2? inch (1d shots] | SEH S27 209 | SSH oe 100 CABLES LF oeeedory hoa ee oe uel, fol od power cabies 1S. 5.08. Bot. Saft. 20 t. een emuired. are Poserer Mobe: Different power cables ape uened for systems with ened without eum. WK Aue, poaver supplies. P.5. ARE WPA Cae] OS WSCC Ce hia, ERMA OS OS Woe 1 Checese: thee berth required . Waa, P.5. ARE APEC Cae] OS. WSS Ca hia, hie, Bro HWEC 01 Sonal AS Went-ore| MWA OE Weod-oos] PYM AS WSO O12 POWER SUPPLIES r Power pequirenvents for I +540: HY GWILAC: SWE: Total housmeg #4 (princry) nuat not Voboge ir Oh ire Oh ire Feawer cote” any ov bbe lana ot ono ebro Autiber ASPSH000 evn » tao WAC ania #00 Media Fo bekal system power require: arte BPR) tao WAC: S000 eC S00 econ eeceed CAU's intemal power supoly capebiiby, on aundiery power supply ritest bee added in stot 1 of thee reeot secon deny housing .

To ues this oon puretion dhs ob OD Select the con pomentsshown on op pecing page, within the quidedines shove. O The cate g numbers in the sheded bowes com prise your bill of maternal. OConigure enyremobe [ko drops required. Foul.es for Eason Chon gene one

OMean un dloveble [E> configuration is 32 modules, & housings.

O Recomm ended hobal hength of cabling between first end beet hous OEspereson botifth Frouesing sddreses up ho fend (AO tok when 17 is ote. ings ere Wesed with print comiguretion.

3-104

Page 104

984X Local Drop Configuration

System Number _____ (page )

984- 8

8 I/O slot

Auxillary Power Supply

8 I/O slot

8 I/O slot

8 I/O slot

8 /O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

Housing H8 -100

Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits

+5Vdc +4.3Vdc -5Vdc Total Power Housing #1 W80___-0__ Power Cable 8 I/O slot

8 I/O slot

8 I/O slot

W80___-0__ System slots may contain: Any B8xx-xxx I/O Module or a J878-000 Modbus modem

Signal Cable 8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

Housing H8___-100 or P8___0-000 Aux. Power Supply Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits

+5Vdc +4.3Vdc -5Vdc Total Power Housing #2

(To additional housings)

3-105

Page 105

984X Local Drop Configuration

System Number _____ (page )

W80___-0__ Power Cable 8 I/O slot

8 I/O slot

W80___-0__ Signal Cable

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

Housing H8 -100 or P8___0-000 Aux Power Supply Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits

+5Vdc +4.3Vdc -5Vdc Total Power Housing #1 W80___-0__ Power Cable 8 I/O slot

8 I/O slot

W80___-0__ Signal Cable

8 I/O slot

8 I/O slot

8 I/O slot

System slots may contain: Any B8xx-xxx I/O Module or a J878-000 Modbus modem

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

8 I/O slot

Housing H8___-100 or P8___0-000 Aux Power Supply Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits

+5Vdc +4.3Vdc -5Vdc Total Power Housing #2

(To additional housings)

3-106

Page 106

984X Local Drop Configuration

System Number _____ (page )

W80___-0__ Power Cable 8

I/O slot

8 I/O slot

W80___-0__ Signal Cable

8 I/O slot

8 I/O slot

8 I/O slot

System slots slots may contain: Any B8xx-xxx I/O Module or a J878-000 Modbus modem

8 I/O slot

8 I/O slot

Housing H81 -100 or P8___0-000 Aux Power Supply

Discrete Inputs Discrete Outputs Total Discrete I/O Input Bits Output Bits

+5Vdc +4.3Vdc -5Vdc Total Power Housing #2

3-107

Page 107

Configuring a Remote I/O System

Remote I/O is the portion of the controller's I/O that is typically installed away from the PLC housing and that requires an interface module to communicate with the I/O processor at the CPU. Communication to the primary housing at each drop is accomplished through coaxial cable. A remote I/O system may consist of single or multiple housings at each drop. The 984-48x, 685, and 785 series of slot-mount PLCs, and all chassis-mount PLCs (984X, 984A, 984B) can support remote I/O systems. In a remote I/O configuration, a remote I/O processor in the PLC is connected, via coaxial cable, to a remote I/O interface device at each remote drop. All 984 PLCs that support remote I/O have been designed to control 800-Series I/O at the remote drops. Several option modules and/or field modification kits are available that allow you to control installed bases of 200 and 500-Series I/O at remote drops as well. (See description of S908 RIO processor for 984-685/785, in Controller Option Modules Section.) S908 Remote Input/Output Processor All 984 PLCs, except the 38x series, can communicate with remote I/O, a feature facilitated by the S908 communications protocol. This protocol is either built into the mainframe (as in the 984X, 984X, 984B, 984-480, and -485) or added as an optional module ( -685, and -785). If you use the S908 with any of the slot mount 685 or 785 series, you must also install an E908-131 or a E908-016 plug-in executive cartridge in the S908. The S908 Remote Input/Output Processor supports up to 32 drops of remote I/O, depending on the upper limit of the 984 PLC to which it is applied. Each drop can support up to two ASCII devices, depending on the remote input/output interface device at the drop. S908 processors are available with either one or two coaxial cable connectors. (984X, 984-480/485 support single cable only). The S908 is required for hot standby configurations.

3-108

Page 108

Remote I/O (Redundant Cable)

S908 remote input/output processing is designed to support communication with 800 I/O. However, the S908 can also support remote communications with 200 and 500 Series I/O, when you install these field modification kits and remote input/ output interfaces: Modification Kit

Interface

Function

J291 kit

P451 RIO interface

J290 kit

P453 RIO interface

984 w/ 200 Series; no ASCII devices 984 w/ 200 Series; 2 ASCII devices

The S908 can also communicate with the 500 Series I/O through the J290/J291 and a J540 adapter.

984/S911 Redundant Cable Hot Standby System

S908 Technical Specifications Communication Capabilities Controllers that use S908 AS-S908-0xx (chassis-mount) 984A, 984B AS-S908-1x0 (slot-mount)* 984-685/785 Integrated into PLC 984X, 984-48x Communication Mode Biphase-level modulation, HDLC message format Communication Speed 1.544 Mbit/second Coaxial Cable Connectors one or two ASCII Ports two per drop Environmental Operating Temperature Relative Humidity Shock Resistance Physical Space Requirements AS-S908-1x0 Weight AS-S908-1x0

0 ... 60°C 0 ... 95% (non-condensing) 10G (11ms)

One option slot in H8xx-209 housing 2.5 lbs (1.2 kg)

*AS-S908-110 Single Cable, AS-S908-120 Dual Cable; both require AS-E908-131 Executive Cartridge.

3-109

Page 109

Remote I/O Cable Recommendations

It is important to plan your system topology before you install the system. Our Application and Service personnel can help you design a system to meet your application requirements. You should consider the following recommendations when planning your cable layout. Your facility may have unique requirements that demand special considerations, so use these recommendations as guidelines only. Trunk Cables The trunk cable runs from the PLC to the remote I/O subsystems. Remote I/O communications operate at 1.544 MHz. Standard cable television cables cannot be used to support remote I/O communication. Three types of cable are recommended: RG-6/U coaxial, RG-11/U coaxial, or semirigid. Use one type of trunk cable throughout the entire remote I/O system. Do not mix cable types. The reflections that occur if signals move from one type of cable to another increase the voltage standing wave ratio (VSWR) in the system. Trunk cables must be terminated with a 75 Ωs cable terminator. There are limits to the length of the three trunk cable types, as follows: Cable

Maximum Length

RG-6/U RG-11/U 0.5 inch semirigid

5,000 ft (1.5 km) 8,000 ft (2.4 km) 15,000 ft (4.5 km)

Modicon RG-6/U Cable, Technical Specifications

The RG-6/U coaxial cable (part #97-5750-000) is a 5/16 inch flexible cable with moderate noise immunity and signal loss; it is used frequently as a drop cable and may be used as a trunk cable in some installations. Specification

RG-6/U Cable, #97-5750-000

Shield type Minimum bend radius Capacitance: Attenuation @ 1.544 MHz

Bonded foil quad shield 2.0 in (5 cm) 16.2 pfd/ft 0.41 dB/100 ft (1.44dB/100 m)

3-110

Modicon RG-11/U Cable, Technical Specifications The RG-11/U coaxial cable (part #97-5951-000) is a 3/8 inch flexible cable with good noise immunity and low signal loss. It is suitable for use as a trunk cable in most industrial environments and may be used as a drop cable in high noise environments. Specification

RG-11/U Cable, # 97-5951-000

Shield type Minimum bend radius Capacitance: Attenuation @ 1.544 MHz

Bonded foil quad shield 2.5 in (6.35 cm) 16.2 pfd/ft 0.2 dB/100 ft (.79 dB/100 m)

Semi-rigid Cable Semi-rigid cable construction is similar to flexible cable construction except that it uses a solid aluminum shield to provide 100% shield coverage. Semi-rigid cable is available in sizes from .5 to 1 inch, with .5 being the most widely used. It has high noise immunity and very low signal loss. Semi-rigid cable may be used as trunk cable when maximum distance and/or high noise immunity are required. Because it is not very flexible, it should not be used as a drop cable. We recommend a semirigid cable from Comm/Scope Co., Network Cable Division, General Instrument Corporation, P.O Box 1729, 1375 Lenour-Rhyne Blvd., Hickory, NC 28602-1729. Phone: (704) 324-2260. Isolating High Energy Cable As a general rule, adjacent high-energy cables should be separated by 12 to 14 inch/kV (30.48 ... 35.56 cm/kV). If they must cross, make sure they cross at right angles. Running Taps and Drop Cables to the I/O Subsystems Drops should be located no more than 100 feet (30 m) and no less than 8 ft (2 m) from a trunk cable. Taps should be placed as close as possible to the drop for ease of maintenance. The drop cable need not be the same cable type as the trunk cable. RG-6/U is normally used as the drop cable in systems that use RG-11/U or semirigid trunk cable.

Page 110

The following table shows the attenuation for the three different cable types: Cable

Attenuation

RG-6/U RG-11/U 0.5 inch semirigid

~7 dB/1000 ft (305 m) ~2 dB/1000 ft (305 m) ~0.8 dB/1000 ft (305 m)

If you use splitters, attenuation from center to either side is 6 dB. However, we recommend that you avoid using splitters (except in the case of Hot Standby systems where a splitter is required). Each RG-6/U drop cable is linked to the RG-11/U trunk cable via a tap. As the signal passes through a tap further down the trunk, the loss per tap is 1 dB. As the signal passes from a tap to the drop to which it is connected, the loss is 14 dB. As the signal passes through the drop cable connector, the loss is 0.7 dB. Cable Connectors For optimum system performance, we recommend that you use only one brand of connector throughout the system. Brand mixing can lead to unpredictable system performance. Modicon F-type Line Tap

Proper F- and BNC Connections Most failures in a remote I/O system are the result of bad connections. Some remote I/O products use F-connectors, and others use BNC connectors. Make sure that all connectors are properly crimped and tightened. Calculating Signal Attenuation Do not allow attenuation in excess of 35 dB at 1.544 MHz between the remote I/O processor in the PLC and any remote I/O interface at the drop. Working from a carefully detailed outline of your layout plan, you can calculate the expected loss based on length and type of the trunk cable, the number of drops in the system, and whether or not a splitter has been used. As a first step in planning a control system that uses multiple remote I/O drops, we urge you to generate an installation layout diagram. Start developing the diagram in the early planning stages, when you are making decisions about the PLC and drop locations, then annotate and update it regularly with: • • • • •

Part # MA-0185-100

Technical Specification

Insertion loss Return loss Tap loss Frequency range Impedance

-01 db (max.) -18 dB (min.) -14 dB (nom.) 0.1 ... 5 MHz 75 Ω

Modicon F-type Line Splitter, Part # MA-0186-100 Technical Specifications Insertion loss Return loss Frequency range Impedance

-6 db (max.) -18 dB (min.) 0.1 ... 5 MHz 75 Ω

Modicon Terminators The following chart identifies Modicon's terminators and their uses. Part #

Description

60-0513-000

75 Ω in-line terminator for use with the J890/J892 processor 75 Ω terminator for trunk cables 75 Ω terminator for drop cables

52-0422-000 52-0402-000

Estimated cable lengths Requirements for taps, terminators, and splitters Projected cable routings Mounting spaces available Alternate routing options

3-111