Spec sheet · Moeller
Moeller 621-DC-TCX Spec Sheet
Spec sheet2 pagesPDF 60 KB
Both pages are below, each with its text.
Filed with · 1 model
Also filed with these models on the old site
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Two-page Pepperl+Fuchs data sheet, dated 2003-03-26, for the EASY 621-DC-TC control relay; it does not print the designation 621-DC-TCX. It gives the supply, input and output data, the front keys and display, accessories, and the EASY205-ASI module that makes the relay an AS-i slave.
- Device
- Electronic control relay with logic, time, counting and clock functions, programmed in ladder diagram on its display p. 2
- Supply voltage
- 20.4 ... 28.8 V DC, approx. 140 mA and approx. 3.5 W at 24 V DC p. 2
- Inputs
- 12 digital inputs; I7 and I8 can be used as analogue inputs p. 1, 2
- Outputs
- 8 transistor outputs, protected against short-circuit and reverse polarity p. 1, 2
- Display and keys
- 4-line LCD display with DEL, ALT, cursor, OK and ESC buttons p. 1
- Clock
- Real-time clock and time relay p. 1
- Input switching points
- State 0 below 5.0 V DC; state 1 above 15.0 V DC (I1-I6, I9-I12) or above 8.0 V DC (I7, I8) p. 2
- Input current
- At state 1: 3.3 mA on I1-I6 and I9-I12, 2.2 mA on I7, I8 (at 24 V DC) p. 2
- Input debounce
- Time delay can be set to 20 ms to debounce input signals p. 2
- AS-i expansion
- EASY205-ASI module makes it an intelligent AS-i slave, exchanging 4 inputs, 4 outputs and 4 bit parameters with the master p. 1, 2
- Accessories
- EASY-SOFT programming software, EASY-M-16K flash memory, EASY-PC-CAB cable p. 2
- Protection degree
- IP20 according to EN 60529 p. 2
- Mounting
- DIN rail p. 2
- Documentation
- Manuals in German and English, online or on CD-ROM p. 2
What this sheet walks you through
- Connecting the supply, inputs and outputs p. 1
- Using the front keys to edit circuits and menus p. 2
- Pairing the relay with an EASY205-ASI as an AS-i slave p. 2
Good to know
- Output short-circuit and overload are evaluated through diagnostic inputs I15 and I16. p. 2
- With the AS-i module fitted, the relay keeps operating on its own if the bus fails. p. 2
Questions this sheet answers
What supply voltage does the EASY 621-DC-TC need?
20.4 to 28.8 V DC, drawing about 140 mA at 24 V DC. p. 2
How many inputs and outputs does the EASY 621-DC-TC have?
12 digital inputs, two of which (I7, I8) can work as analogue inputs, and 8 transistor outputs. p. 1, 2
What software and cable program the EASY 621-DC-TC?
EASY-SOFT programming software with the EASY-PC-CAB cable. p. 2
Does the EASY control relay stop if the AS-i bus fails?
No. With the EASY205-ASI fitted, the relay stays autonomous and keeps operating on its own. p. 2
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
Control relayEASY 621-DC-TC4590Dimensions107.54.5 47.5 58Electrical connection
12 inputs I1 ... I6 Supply voltage
+24VD0VDI7A 0VI8AI9 ... I12
Model Number EASY 621-DC-TC
0V
Interface to AS-i connection EASY205-ASI
0VµP 8 outputsControl relayQ1 ... Q8FeaturesLoad0VQ
- 12 digital inputs of which 2 can be used in analogue mode
Auxiliary voltage for the outputs
- 8 transistor outputs
+24VQ
- 4-line LCD display
- Control panel/keys
- Real-time clock/time relay
- Interface for transfer to memory card or PC
Indicating / Operating means
- Expandable with I/O module EASY205 ASI for intelligent AS-i slave
Supply voltage Ue Inputs +24V
0V 0V I1103057_ENG.xmlPEPPERL+FUCHSI2I3I4I5I6I7I8I9I10 I11 I121 2DEL button ALT button3Cursor button4 5 6 7
OK button ESC button LC-display Socket for PC-interface (with cover)
LED DELALTPower / RunOK2003-03-26ESC+24V Q0VQQ1 Q2Q3 Q4Q5 Q6Q7 Q8Date of Issue
Outputs Auxiliary voltage for outputs
Subject to reasonable modifications due to technical advances.
Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
1
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
Control relayEASY 621-DC-TCTechnical dataFunction
Electrical specifications Rated operational voltage Rated operational current Power loss
Ue Ie
20,4 ... 28,8 V DC approx. 140 mA at 24 V DC approx. 3,5 W at 24 V DC
Input Number/Type Switching point
Input current
Signal delay
12 digital inputs 2 inputs (I7, I8) can be used as analogue inputs state 0: < 5.0 V DC (I1-I12) state 1: > 15.0 V DC (I1-I6, I9-I12) state 1: > 8.0 V DC (I7, I8) at state 1: I1-I6: 3.3 mA (at 24 V DC) I7, I8: 2.2 mA (at 24 V DC) I9-I12: 3.3 mA (at 24 V DC) Standard adjustment: 0.2 ñ 0.4 ms Time delay can be set to 20 ms to debounce input signals
Input 1 Number/Type Signal voltage Resolution Impedance
2 analogue inputs (I7 and I8 alternative) 0 ... 10 V DC 0,1 V 11,2 kOhm
Output Number/Type Short circuit protection/overload Current Voltage
8 electronic outputs, protected against short-circuit/reverse polarity Evaluation takes place with diagnostic input I15, I16 at state 0: 18 ... 32 mA at state 1: 22 ... 44 mA 20.4 V DC ... 28.8 V DC
Electrical isolation Input/Output Output/Power supply
safe electrical isolation per EN 50178 available
Ambient conditions Ambient temperature Storage temperature
-25 ... 55 °C (248 ... 328 K) -40 ... 70 °C (233 ... 343 K)
Mechanical specifications Core cross-section Protection degree Mass Mounting Connection possibilities
one wire 0.2 ... 4 mm2 IP20 according to EN 60529 300 g DIN rail 6-pin connector (lateral) for AS-i connecting circuit EASY205ASI
EASY 621-TC-DC is an electronic control relay with logic, time, counting and clock timing functions. It is designed for small, convenient control tasks, e. g. in machine and plant engineering. The circuit diagram is "wired" in the ladder diagram technique and directly given in the in the display. The combinations of an EASY 205-ASI ASInterface with the control relay provides an itelligent AS-i slave, which can perform extremely flexible, decentralised control tasks and information processing. So the relay remains autonomous: i. e. in the event of a bus failure, it can continue operating on its own. The combination can be addressed via the master or the ddressing socket on the interface module, the exchange of information to the AS-i master is provided by the 4 inputs and the 4 outputs as well as the 4 bit parameters of the interface module.
Documentation The documentation includes manuals in German and English. It is available on the Internet and in printed form as a CD-ROM on request.
Documentation Handbuch EASY Manual EASY Kurzanleitung EASY Training Guide EASY
Accessories EASY-SOFT Programming software EASY-M-16K flash memory EASY-PC-CAB cable
Matching system components EASY205-ASI AS-i connecting circuit
Date of Issue
2003-03-26
For operating the device you can use the front keys with following functions: 1 DEL button: Deletion of contacts / relays / connections / empty current path 2 ALT button: Indicate connections / changeover switch: Contact = N.O. or N.C. / insert current path 3 Cursor button: right, left, top, down select menu item Contacts, relays, select number P key on: Input P1 left-cursor Input P2 top-cursor Input P3 right-cursor Input P4 down-cursor 4 OK button: Sterp forward in menu, accept entry 5 ESC button: Take one step back in menu Menu, exit parameter function relay Exit without saving 6 LC-display: Inputs/outputs status indication Operating status Circuit diagram Display time 7 Socket for PC-interface (with cover)
103057_ENG.xml
Notes
Subject to reasonable modifications due to technical advances.
2
Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com