Page 31
UM325-1 MODBUS COMMUNICATIONS
4.3.7 Loopback Test
This command causes URICA to re-transmit the received data from the MODBUS master. NOTE The implementation of the Loopback Test requires that the first word of data, after the Diagnostic Code portion, indicate the number of words (registers) being transmitted. For example, when the Master sends a Loopback Test command with Diag. Code = 00 00, followed by 6 registers of data, the value in the first data register should be 00 06.
4.3.8 Preset Multiple Registers
This command changes the value of multiple 4xxxx holding registers. When changing the value of a floating point or double integer address that uses two consecutive registers, this command must be used (Function Code 06 will not work).
4.3.9 Report Slave ID
This command will cause URICA to respond with nine bytes of data, similar to a Modicon 984 PLC.
Byte Contents
] 09 Slave ID
2 FF Run Indicator 3 00 not used
4 00 not used
5 00 not used
6 00 not used
7 AO power on, run
(may not reflect actual URICA conditions)
8 00 not used
9 00 not used
4.4 MODBUS ERROR CODES
Table 4-1 shows the exception response codes supported by the Model 325 URICA. legal data in a message or difficulty in communicating with URICA will result in exception code responses. When URICA detects one of these errors, it sends a response message to the master consisting of slave address, function code, error code and error check fields. To indicate that the response is a notification of an error, the high order bit of the function code is set to |.
October 1995 4.3
Page 32
MODBUS COMMUNICATIONS UM325-1
TABLE 4-1 MODBUS Exception Response Codes
CODE NAME MEANING
01 ILLEGAL FUNCTION The message function received is not an allowable action for the slave. If a poll command was issued, this code indicates that no program function preceded it.
02 ILLEGAL DATA The address referenced in the data field is not valid for ADDRESS the addressed slave location. 03 ILLEGAL DATA VALUE _ The value referenced in the data field is not allowable in the addressed slave location.
4-4 October 1995
Page 33
UM325-1 MAINTENANCE
5. MAINTENANCE
Model 325 URICA maintenance requirements are minimal. Activities such as cleaning and visual inspection should be performed at regular intervals. The severity of URICA's operating environment will determine the frequency of maintenance. Additional topics in this section include troubleshooting, board replacement, and recommended spare and replacement parts. If technical assistance is needed, refer to Section 1.3 Product Support.
5.1 PREVENTIVE MAINTENANCE
The objective for establishing a preventive maintenance program is to provide maximum operating efficiency by reducing down time.
5.1.1 Cleaning
URICA should be cleaned as often as operating conditions require. Excessive accumulation of dust or dirt on the case prevents efficient heat dissipation and can cause overheating and component breakdown. A damp cloth can be used to clean the case.
Circuit boards should not be cleaned unless accumulated foreign material is causing a problem. The enclosed design should prevent matter from building up. If cleaning becomes necessary, remove debris with either a soft brush or low velocity deionized air.
5.1.2 Visual Inspection
As part of a preventive maintenance program, URICA should be visually inspected. Terminal block connections should be checked periodically. Remove the cover and look for damaged or heat stressed parts on the circuit boards. Check for excessive dirt or dust build-up which may impede air flow and inhibit proper heat dissipation.
5.2 CIRCUIT BOARD HANDLING
Special handling procedures are required whenever a circuit board is removed, adjusted or installed in the case. These procedures are required to prevent component damage from the electrostatic discharge hazard to which most semiconductors are vulnerable. Electrostatic discharge (ESD) can damage semiconductor devices. Handling procedures that prevent the build up of electrostatic potentials are required whenever circuit boards are handled. When handling a circuit board, follow the procedures outlined in the Board Replacement section of this instruction.
5.3 FUSE LOCATION
A power input fuse is located on the circuit board as shown in Figure 5-1. A replacement fuse may be obtained from any local electronics supplier or may be order from the factory. Refer to the Parts List at the back of this instruction for fuse part number and description.
October 1995 5-]
Page 34
MAINTENANCE UM325-1
To replace the fuse, refer to section 5.5 for removal and installation of the cover. Visually inspect the circuit board for damaged or overheated components. Insert a new fuse and install the cover. Reconnect the terminal strip and apply power. Operate URICA off-line for several minutes to be sure that a condition does not exist which will cause the replacement fuse to fail.
5.4 TROUBLESHOOTING
Troubleshooting URICA is done by interpreting the status of 4 LEDs on the faceplate. Upon power up, a lamp test is performed to verify that all 4 LEDs light.
TABLE 5-1 LED Maintenance Indicators
LED MEANING OPERATION
RDY Ready Normally ON continuously following start-up. Any other indication indicates a problem at the station or it's interconnections.
CMD Command Turned ON whenever this station is addressed by the MODBUS
RCV Received initiator. Remains on until the response is sent, or if no response is sent, until the operation is terminated.
HRT Hart Command | This light is lit every time a HART command is sent to a field
SNT Sent device.
ACT Active Flashes steady indicating normal operation
5.4.1 MODBUS Communications
Problem: URICA is not communicating to the MODBUS master.
The CMD RCV LED should light each time a MODBUS command is received. If it does not light, proper communication is not occurring. Check the following:
1. The communication DIP switch settings in Section 3 must match the communication settings of the MODBUS master (or modem if used).
2. Check the cable connections. Verify the pinout of the cable.
3. If communicating to a modem (or other DCE device), check to see that SW2-8 is set to ON. Refer to Section 3.1.2.5 for more information.
Problem: All HART data is 999999.9.
When URICA is powered, the HART data is defaulted to 999999 9,
5.4.2 HART Communications
Following the lamp test, URICA will poll for any devices on the HART bus. This can take up to 30 seconds. After this initial poll cycle, URICA will begin communicating continuously with each HART device. The HRT SNT LED should light approximately twice a second. If the HRT SNT LED is lighting approximately once a second, URICA is not communicating with the HART devices. Recheck
§-2 October 1995
Page 35
UM325-1 MAINTENANCE the wiring. Make sure there is a proper current sense resistor across terminals 8 and 9. Refer to the transmitter’s installation procedures for more information.
5.5 BOARD REPLACEMENT
As is the case with most circuit boards populated with semiconductor components, precautions must be observed to prevent component damage from ESD (electrostatic discharge}. Accordingly, a maintenance kit (P/N 15545-110) containing a wrist strap and a conductive mat must be used whenever a board is removed from or installed in the case.
An uninstalled URICA board must be stored in a static shielding bag.
To replace the circuit board, refer to Figure 5-1 and perform the following procedures:
REMOVAL
1. Unplug the terminal strip from the terminal block.
IMPORTANT
When unplugging the terminal strip, be sure to grip the connector, not the wiring.
2. Ground the wrist strap. 3. Remove 4 screws from the top of the case and place the top aside. 4, Remove 3/4 screws which attach the board to the case. 5. Slide the circuit board to the rear of the case to free the terminal strip and lift the board from the case. INSTALLATION 1. Ground the wrist strap. 2. Remove circuit board from static shielding bag. 3. Disconnect screw terminals from the terminal block. IMPORTANT When unplugging the screw terminals from the terminal block, grip the two halves of the terminal strip. 4. Lower board into case, sliding the terminal strip through the front panel cutout. 5. Connect the board to the case by installing the supplied screws. 6. Plug the screw terminals into the terminal block. 7. Set the DIP switches. 8. Install the cover with the flat-head screws. 9. Make connections to terminal strip
October 1995 5-3
Page 36
MAINTENANCE
UM325-1, 4-40X 1/4 a \ 4 Places a @ \ J
\ a, - 6-32 X 1/2 \ 3 Places
Circuit Board
Note:
To separate terminal block sections, grasp the removable section and pull straight out from URICA's faceplate.
Removable _ Portion of Terminal Block,
See Note
FIGURE 5-1 URICA Exploded View
October 1995
Page 37
UM325-1 MAINTENANCE
5.6 RECOMMENDED SPARE AND REPLACEMENT PARTS
It is recommended that one spare of each of the following be stocked for every 1 to 10 units in service: Fuse and circuit board.
Replacement circuit boards and recommended spare parts are available from the factory. Part numbers are provided in the Parts List at the back of this manual.
IMPORTANT
When ordering a replacement or spare circuit board, provide the following data from the board to be replaced or spared.
® part number e software compatibility code ® serial number
An item being returned to the factory should be packaged in its original shipping container. Otherwise, package for safe shipment and contact the factory as described in Section 2.1.4 Send package to one of the addresses given in the warranty statement.
IMPORTANT
A circuit board must be placed in a static shielding bag before it is packaged for shipment.
5.7 SOFTWARE COMPATIBILITY IDENTIFICATION
When changing a circuit board, consideration must be given to software compatibility. A three letter software compatibility code is used to identify URICA software. This code is stored in MODBUS register $0811 as a string.
5.8 MAINTENANCE RECORD
An accurate record keeping system for maintenance operations should be established and kept up to date. Data extracted from the record can serve as a basis for ordering supplies such as spare parts. In addition, it is useful as a troubleshooting tool by providing historical maintenance data. Scheduled and unscheduled maintenance should be recorded.
October 1995 5-5
Page 38
MAINTENANCE UM325-1
5-6 October 1995
Page 39
UM325-1 MODEL DESIGNATION AND SPECIFICATION
6. MODEL DESIGNATION AND SPECIFICATIONS
This section contains the model designation table, accessory list and specifications for the Model 325 URICA.
6.1 MODEL DESIGNATION
Table 6-1 identifies the model designation entry on URICA’s nameplate. The nameplate also carries other important information in addition to the model designation.
e = Bill of material number (BOM)
e = =Serial number e Certifications - Review the certifications before installing or servicing URICA.
TABLE 6-1 Model 325, Model Designation
Basic Model Number 325H Basic Station with HART
Power Supply D 19-28 Vdc (galvanicly isolated)
Reserved for Factory Use N Not Used
Reserved for Factory Use N Not Used
Reserved for Factory Use N Not Used
Design Level A Current Design
Hazardous Area Classification F FM/CSA Approved, Class I, Division 2, Groups A, B, C & D
325H D N N N A F, Sample Model Number
October 1995 6-1
Page 40
MODEL DESIGNATION AND SPECIFICATIONS
UM325-!
6.2 ACCESSORIES
The accessories listed in Table 6-2 are available for use with the Model 325 URICA.
TABLE 6-2 Accessories
DESCRIPTION PART NUMBER General Purpose Power Supply, 24 Vdc, 2A 15124-1
DBOM to DBOF, 15 ft. straight-through shielded cable 16260-27
DB9OM to DB25F, Adapter 16801-9
120 Ohm RS422/485 Terminating Resistor 14700-121G
6.3 SPECIFICATIONS
The following are specifications for the Model 325 URICA.
6.3.1 Mechanical
DIMENSIONS 0.00.0... cece eeeceeeenseeecessneceecessceceecsaecessnaceceseesneeeesers See Figure 6-1 MOunting oo... eecceceeceecceneeeneeseeseaneeeesaesensaeeneeteeseaeeeeas See Figure 2-1 6.3.2 Electrical
Power Requirement:
Input Voltage... ce ccccescccseecessecesseceseecenneeenteersneaees 19-28 Vde Power Consumption .........cceccccccssecsesseseeesseseceresstaees 5 Watts maximum
6-2 October 1995