For the Omron C200H-CPU01-E
Page 24
Section
CPU Rack
2-1
2-1
CPU Rack The following figure shows the names of all the parts of a CPU Rack. There are four models of Backplanes available with 3, 5, 8 and 10 slots for I/O Units. You can use any of these Backplanes to build a CPU or Expansion I/O Rack. However, the C200H-OC225/OD212/OD21A 16-point Output Unit and C200H-B7AO1 B7A Interface Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.
This connector not used: Cover with a cap. Backplane
I/O Units I/O Connecting Cable connector Connects CPU Rack to Expansion I/O Rack When not used, cover with a cap.
10
CPU
Backplane mounting screws (four, with 4-mm dia. heads)
Page 25
Section
CPU
2-2
2-2
CPU The CPU is available in three models. The C200H-CPU01-E and C200HCPU11-E both run on 100 to 120 or 200 to 240 VAC, and the C200H-CPU03-E runs on 24 VDC. The C200H-CPU11-E is unique in that it connects the SYSMAC LINK Unit or SYSMAC NET Link Unit to the CPU. These two Units are mounted to either of the two slots located directly to the left of the the CPU and connected to the CPU via a bus connector. A separate Unit, the Bus Connector Unit, is required to connect the SYSMAC NET Link Unit or the SYSMAC LINK Unit to the CPU. Also note that model C200H-CPU11-E has an additional battery connected to the CPU. Note If you are using the SYSMAC LINK Unit or SYSMAC NET Link Unit in your C200H system, use model C200H-CPU11-E as the CPU. Otherwise, the link Units cannot be used.
C200H-CPU01-E/03
Indicators
Memory Pack connector
Power fuse
Detachable terminal block
Peripheral device mounting hole
Programming Console connector cover storage slot
Programming Console connector (Peripheral device connector) Remove cover to gain access to connector; store cover in cover storage slot.
Handheld Programming Console connector Remove cover to gain access to connector.
11
Page 26
Section
CPU
2-2
C200H-CPU11-E Indicators
Power fuse MF51NR (5.2 dia. x 20 mm) 2A 250 V
Memory Pack connector
Battery compartment
Bus connector Available only with the C200H-CPU11-E. Used to connect this Unit to a SYSMAC LINK Unit or SYSMAC NET Link Unit.
Handheld Programming Console connector
Programming Console connector cover storage slot
Programming Console connector (Peripheral device connector)
CPU Indicators
The following figure shows the indicators that are located on the front panel of the three CPU models. RUN indicator (green) Lights when the PC is operating normally.
ALARM (blinking red) Blinks if an error occurs that does not stop the CPU.
POWER (green) Lights when power is supplied to the CPU.
OUT INHIBIT (red) Lights when the Load OFF flag (SR bit 25215) turns ON, at which time all the outputs are turned OFF.
ERROR (solid red) Lights if an error occurs that stops the CPU, at which time the RUN indicator turns OFF and the outputs are turned OFF.
12
Page 27
Section
CPU Peripheral Device Connectors
2-2
All three CPU models are equipped with two connectors for peripheral devices. One is used for the Handheld Programming Console or the Data Access Console; the other is used for the CPU-Mounting Programming Console. The C200H-CPU11-E, however, has a third connector that is used for connecting the SYSMAC LINK Unit or the SYSMAC NET Link Unit to the CPU. To connect the Handheld Programming Console to the CPU, a Connecting Cable is required, as shown in the following diagram. Note If you are using the SYSMAC LINK Unit or SYSMAC NET Link Unit in your system, you must use model C200H-CPU11-E as the CPU. The other two models mentioned above are not equipped with the appropriate connectors.
Cable Connection
Connecting Cable
Handheld Programming Console
The CPU-mounting Programming Console can be mounted directly to the CPU and does not require a Connecting Cable. To mount the CPU-Mounting Programming Console (or any other peripheral device) directly to the CPU, follow the steps below. Direct Mounting
The CPU-mounting Programming Console, when mounted to the CPU, covers the two I/O Units located directly to the left of the CPU. For this reason it is important to know which shapes can be mounted to these slots. Notice, in the following diagram, that the two I/O Units mounted directly to the left of the CPU are A-shape Units. The CPU-mounting Programming Console can be mounted to the CPU provided A-shape I/O Units are mounted to these two slots. Make sure the protective covers of the two I/O Units are in place to avoid electrical interference with the CPU. Because the surface of B-shape and E-shape I/O Units protrudes a few centimeters from surface of the CPU, B-shape and E-shape I/O Units cannot be mounted to the two slots to the left of the CPU unless a Programming Console Base Unit is first mounted to the CPU to increase the mounting height of the Programming Console.
13
Page 28
Section
CPU
2-2
If you are using the C200H-CPU11-E, a SYSMAC LINK Unit or a SYSMAC LINK Unit can be mounted to either of the two slots to the left of the CPU. They are then connected to the CPU with the Bus Connector Unit.
Peripheral device
CPU Rack
A-shape I/O Units
1, 2, 3...
14
1. Remove the cover from the peripheral device connector with a standard screwdriver. 2. Connect the CPU-Mounting Programming Console to the peripheral device connector. 3. Attach the CPU-Mounting Programming Console to the CPU by tightening the mounting screws.
Page 29
Section
Expansion I/O Rack
2-3
2-3
Expansion I/O Rack The Backplane used to construct a CPU Rack is also used to construct an Expansion I/O Rack. An Expansion I/O Rack is identical to a CPU Rack, except the CPU has been replaced with a Power Supply. The parts of an Expansion I/O Rack are shown in the following diagram. I/O Connecting Cable Connector Connects Expansion I/O Rack to preceding Expansion I/O Rack or to CPU. Backplane
I/O Connecting Cable Connector. Connects Expansion I/O Rack to next Expansion I/O Rack. When not used, cover with a cap.
Power Supply
I/O Units Backplane mounting screws (four, with 4-mm dia. heads)
15
Page 30
Section
Power Supply
2-4
2-4
Power Supply The Power Supply used for Expansion I/O Racks is available in two models. One runs on 100 to 120 or 200 to 240 VAC, and the other runs on 24 VDC.
AC Power Supply POWER indicator (green) Lights when power is supplied to Power Supply
Power fuse 2 A 250 V (5.2-dia. x 20) MF51NR
AC Input Voltage selector terminals Short: 100 to 120 VAC Open: 200 to 240 VAC LG
Terminals for external connections
GR +
24 VDC 0.3 output NC NC
16
Page 31
Section
Power Supply
2-4
DC Power Supply POWER indicator (green) Lights when power is supplied to Power Supply
Power fuse 5 A 125 V (5.2-dia. x 20) MF51NR
+
24 VDC
NC Terminals for external connections
NC LG GR
+
(See note.)
NC NC NC NC
Note The LG and GR terminals are connected internally.
17
Page 32
I/O Units
2-5
Section
2-5
I/O Units I/O Units come in three shapes: A-shape, B-shape, and E-shape. Refer to Appendix B Specifications for the dimensions of each Unit.
A-shape I/O Units I/O Unit lock notch
Nameplate I/O indicators Indicate ON/OFF status of points
10-terminal terminal block
B-shape I/O Units I/O Unit lock notch
Nameplate I/O indicators Indicate ON/OFF status of points
19-terminal terminal block
18
Page 33
Section
Memory Units
2-6
E-shape I/O Units I/O Unit lock notch
Nameplate I/O indicators Indicate ON/OFF status of points
10-terminal terminal block
2-6
Memory Units There are three types of Memory Units, having three different types of memory. The three types of memory are EPROM, EEPROM, and RAM. Clock1
Memory
Model
Capacity
Maximum program size
Backup
EPROM
C200H-MP831
8K words
6,974 words
---
NO
EEPROM
C200H-ME431 C200H-ME831
4K words 8K words
2,878 words 6,974 words
RAM
C200H-MR431
4K words
2,878 words
Battery
NO
C200H-MR831
8K words
6,974 words
C200H-MR432
4K words
2,878 words
C200H-MR832
8K words
6,974 words
Capacitor
Contents for Memory Unit Registration
Fixed DM area (DM 1000 to DM 1999)
I/O table (see note)
UM (ladder program area)
Note I/O tables are also saved in the Memory Unit at the time of creation. Therefore, if the Memory Unit is set to write-protect, it will be impossible to create an I/O table.
19