Page 214
Section 5-17
Data Comparison
5-17-3 DOUBLE COMPARE – CMPL(60) Ladder Symbols
Operand Data Areas Cp1: First word of first compare word pair
CMPL(60) IR, SR, AR, DM, HR, TC, LR Cp1 Cp2: First word of second compare word pair Cp2
IR, SR, AR, DM, HR, TC, LR
000 (fixed)
Limitations
Cp1 and Cp1+1 must be in the same data area, as must Cp2 and Cp2+1.
Description
When the execution condition is OFF, CMPL(60) is not executed. When the execution condition is ON, CMPL(60) joins the 4-digit hexadecimal content of Cp1+1 with that of Cp1, and that of Cp2+1 with that of Cp2 to create two 8-digit hexadecimal numbers, Cp+1,Cp1 and Cp2+1,Cp2. The two 8-digit numbers are then compared and the result is output to the GR, EQ, and LE flags in the SR area.
Precautions
Placing other instructions between CMPL(60) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed. CMPL(60) cannot be used to compare signed binary data. Use CPSL(––) instead. Refer to 5-17-9 DOUBLE SIGNED BINARY COMPARE – CPSL(––) for details.
Flags
ER:
Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
GR:
ON if Cp1+1,Cp1 is greater than Cp2+1,Cp2.
EQ:
ON if Cp1+1,Cp1 equals Cp2+1,Cp2.
LE:
ON if Cp1+1,Cp1 is less than Cp2+1,Cp2.
196
Page 215
Section 5-17
Data Comparison
The following example shows how to save the comparison result immediately. If the content of HR 10, HR 09 is greater than that of 011, 010, then 00200 is turned ON; if the two contents are equal, 00201 is turned ON; if content of HR 10, HR 09 is less than that of 011, 010, then 00202 is turned ON. In some applications, only one of the three OUTs would be necessary, making the use of TR 0 unnecessary. With this type of programming, 00200, 00201, and 00202 are changed only when CMPL(60) is executed.
Example: Saving CMPL(60) Results
00000
TR 0 CMPL(60) HR 09 010 --25505 00200
Greater Than
00201
Equal
00202
Less Than
25506
25507
Address
Instruction
00000 00001 00002
LD OUT CMPL(60)
Operands
TR HR
00003
AND
Address
Instruction
00004 00005 00006 00007 00008 00009 00010
OUT LD AND OUT LD AND OUT
00000 0 09 010 25505
Operands
TR
TR
00200 0 25506 00201 0 25507 00202
5-17-4 BLOCK COMPARE – BCMP(68) Operand Data Areas CD: Compare data
Ladder Symbols
IR, SR, AR, DM, HR, TC, LR, # BCMP(68)
@BCMP(68)
CD
CD
CB
CB
R
R
CB: First comparison block word
Limitations
IR, DM, HR, TC, LR R: Result word IR, SR, AR, DM, HR, TC, LR
Each lower limit word in the comparison block must be less than or equal to the upper limit.
197
Page 216
Section 5-17
Data Comparison Description
When the execution condition is OFF, BCMP(68) is not executed. When the execution condition is ON, BCMP(68) compares CD to the ranges defined by a block consisting of of CB, CB+1, CB+2, ..., CB+31. Each range is defined by two words, the first one providing the lower limit and the second word providing the upper limit. If CD is found to be within any of these ranges (inclusive of the upper and lower limits), the corresponding bit in R is set. The comparisons that are made and the corresponding bit in R that is set for each true comparison are shown below. The rest of the bits in R will be turned OFF. CB ≤ CD ≤ CB+1 Bit 00 CB+2 ≤ CD ≤ CB+3 Bit 01 CB+4 ≤ CD ≤ CB+5 Bit 02 CB+6 ≤ CD ≤ CB+7 Bit 03 CB+8 ≤ CD ≤ CB+9 Bit 04 CB+10 ≤ CD ≤ CB+11 Bit 05 CB+12 ≤ CD ≤ CB+13 Bit 06 CB+14 ≤ CD ≤ CB+15 Bit 07 CB+16 ≤ CD ≤ CB+17 Bit 08 CB+18 ≤ CD ≤ CB+19 Bit 09 CB+20 ≤ CD ≤ CB+21 Bit 10 CB+22 ≤ CD ≤ CB+23 Bit 11 CB+24 ≤ CD ≤ CB+25 Bit 12 CB+26 ≤ CD ≤ CB+27 Bit 13 CB+28 ≤ CD ≤ CB+29 Bit 14 CB+30 ≤ CD ≤ CB+31 Bit 15 Normally the first word in the range is less than the second, but if the first word in the range is greater than the second, the corresponding bit in R will be turned OFF when CD is outside of the range defined by the two words, as shown in the following diagram. CB
CB + 1
0000
9999 CB+1
0000
Flags
ER:
CB
9999
The comparison block (i.e., CB through CB+31) exceeds the data area. Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
198
Page 217
Section 5-17
Data Comparison Example
The following example shows the comparisons made and the results provided for BCMP(68). Here, the comparison is made during each cycle when 00000 is ON.
00000 BCMP(68)
Address
Instruction
00000 00001
LD BCMP(68)
001 HR 10
Operands 00000
HR 05
HR HR
CD 001 001
Lower limits 0210
HR 10 HR 12 HR 14 HR 16 HR 18 HR 20 HR 22 HR 24 HR 26 HR 28 HR 30 HR 32 HR 34 HR 36 HR 38 HR 40
Compare data in IR 001 (which contains 0210) with the given ranges.
Upper limits
0000 0101 0201 0301 0401 0501 0601 0701 0801 0901 1001 1101 1201 1301 1401 1501
HR 11 HR 13 HR 15 HR 17 HR 19 HR 21 HR 23 HR 25 HR 27 HR 29 HR 31 HR 33 HR 35 HR 37 HR 39 HR 41
001 10 05
R: HR 05 0100 0200 0300 0400 0500 0600 0700 0800 0900 1000 1100 1200 1300 1400 1500 1600
HR 0500 HR 0501 HR 0502 HR 0503 HR 0504 HR 0505 HR 0506 HR 0507 HR 0508 HR 0509 HR 0510 HR 0511 HR 0512 HR 0513 HR 0514 HR 0515
0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0
5-17-5 TABLE COMPARE – TCMP(85) Operand Data Areas CD: Compare data
Ladder Symbols
IR, SR, AR, DM, HR, TC, LR, # TCMP(85)
@TCMP(85)
CD
CD
TB
TB
R
R
TB: First comparison table word IR, AR, DM, HR, TC, LR R: Result word IR, SR, AR, DM, HR, TC, LR
Limitations
TB and TB+15 must be in the same data area.
Description
When the execution condition is OFF, TCMP(85) is not executed. When the execution condition is ON, TCMP(85) compares CD to the content of TB, TB+1, TB+2, ..., and TB+15. If CD is equal to the content of any of these words, the corresponding bit in R is set, e.g., if the CD equals the content of TB, bit 00 is turned ON, if it equals that of TB+1, bit 01 is turned ON, etc. The rest of the bits in R will be turned OFF.
Flags
ER:
EQ:
The comparison table (i.e., TB through TB+15) exceeds the data area. Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.) ON if none of the words in the comparison table match CD, i.e., all of the bits in R are OFF.
199
Page 218
Section 5-17
Data Comparison Example
The following example shows the comparisons made and the results provided for TCMP(85). Here, the comparison is made during each cycle when 00000 is ON.
00000 TCMP(85) 001
Address
Instruction
00000 00001
LD TCMP(85)
Operands 00000
HR 10 HR 05
CD: 001 001
Upper limits 0210
Compare the data in IR 001 with the given ranges.
HR 10 HR 11 HR 12 HR 13 HR 14 HR 15 HR 16 HR 17 HR 18 HR 19 HR 20 HR 21 HR 22 HR 23 HR 24 HR 25
HR HR
001 10 05
R: HR 05 0100 0200 0210 0400 0500 0600 0210 0800 0900 1000 0210 1200 1300 1400 0210 1600
HR 0500 HR 0501 HR 0502 HR 0503 HR 0504 HR 0505 HR 0506 HR 0507 HR 0508 HR 0509 HR 0510 HR 0511 HR 0512 HR 0513 HR 0514 HR 0515
0 0 1 0 0 0 1 0 0 0 1 0 0 0 1 0
5-17-6 AREA RANGE COMPARE – ZCP(88) Operand Data Areas CD: Compare data
Ladder Symbols
IR, SR, AR, DM, HR, TC, LR, # ZCP(88) LL: Lower limit of range CD
IR, SR, AR, DM, HR, TC, LR, #
LL
UL: Upper limit of range
UL
IR, SR, AR, DM, HR, TC, LR, #
Limitations
LL must be less than or equal to UL.
Description
When the execution condition is OFF, ZCP(88) is not executed. When the execution condition is ON, ZCP(88) compares CD to the range defined by lower limit LL and upper limit UL and outputs the result to the GR, EQ, and LE flags in the SR area. The resulting flag status is shown in the following table. Flag status
Comparison result
200
CD < LL
GR (SR 25505) EQ (SR 25506) 0 0
LE (SR 25507) 1
LL ≤ CD ≤ UL
0
1
0
UL < CD
1
0
0
Page 219
Section 5-17
Data Comparison Precautions
Placing other instructions between ZCP(88) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
Flags
ER:
Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.) LL is greater than UL. ON if LL ≤ CD ≤ UL
LE:
ON if CD < LL.
GR:
ON if CD > UL.
The following example shows how to save the comparison result immediately. If IR 100 > AB1F, IR 00200 is turned ON; if #0010 ≤ IR 100 ≤ AB1F, IR 00201 is turned ON; if IR 100 < 0010, IR 00202 is turned ON.
Example: Saving ZCP(88) Results
00000
EQ:
TR 0 ZCP(88) IR 100 #0010 #AB1F
25505 00200
Greater Than (above range)
00201
Equal (within range)
00202
Less Than (below range)
25506
25507
Address
Instruction
00000 00001 00002
LD OUT ZCP(88)
Operands
TR IR # #
00003
AND
00000 0 100 0010 AB1F 25505
Address
Instruction
00004 00005 00006 00007 00008 00009 00010
OUT LD AND OUT LD AND OUT
Operands
TR
TR
00200 0 25506 00201 0 25507 00202
5-17-7 DOUBLE AREA RANGE COMPARE – ZCPL(––) Operand Data Areas Ladder Symbols
CD: Compare data IR, SR, AR, DM, HR, LR
ZCPL(––) LL: Lower limit of range CD LL UL
Limitations
IR, SR, AR, DM, HR, LR UL: Upper limit of range IR, SR, AR, DM, HR, LR
The 8-digit value in LL+1,LL must be less than or equal to UL+1,UL. CD and CD+1 must be in the same data area, as must LL and LL+1, and UL and UL+1.
201
Page 220
Section 5-17
Data Comparison Description
When the execution condition is OFF, ZCPL(––) is not executed. When the execution condition is ON, ZCPL(––) compares the 8-digit value in CD, CD+1 to the range defined by lower limit LL+1,LL and upper limit UL+1,UL and outputs the result to the GR, EQ, and LE flags in the SR area. The resulting flag status is shown in the following table. Flag status
Comparison result GR (SR 25505)
EQ (SR 25506)
LE (SR 25507)
CD , CD+1< LL+1,LL
0
0
1
LL+1,LL ≤ CD, CD+1 ≤ UL+1,UL
0
1
0
UL+1,UL < CD, CD+1
1
0
0
Precautions
Placing other instructions between ZCPL(––) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
Flags
ER:
Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.) LL+1,LL is greater than UL+1,UL.
Example
EQ:
ON if LL+1,LL ≤ CD, CD+1 ≤ UL+1,UL
LE:
ON if CD, CD+1 < LL+1,LL.
GR:
ON if CD, CD+1 > UL+1,UL.
Refer to 5-17-6 AREA RANGE COMPARE – ZCP(88) for an example. The only difference between ZCP(88) and ZCPL(––) is the number of digits in the comparison data.
5-17-8 SIGNED BINARY COMPARE – CPS(––) Operand Data Areas Ladder Symbols
Cp1: First compare word IR, SR, AR, DM, HR, TC, LR, #
CPS(––) Cp2: Second compare word Cp1 Cp2 000
Description
IR, SR, AR, DM, HR, TC, LR, # Third operand: Set to 000. ---
When the execution condition is OFF, CPS(––) is not executed. When the execution condition is ON, CPS(––) compares the 16-bit (4-digit) signed binary contents in Cp1 and Cp2 and outputs the result to the GR, EQ, and LE flags in the SR area. Note
1. Refer to page 27 for details on 16-bit signed binary data. 2. Refer to 5-17-2 Compare – CMP(20) for details on saving comparison results.
Precautions
202
Placing other instructions between CPS(––) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
Page 221
Section 5-17
Data Comparison Flags
ER:
Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
EQ:
ON if Cp1 equals Cp2.
LE:
ON if Cp1 is less than Cp2.
GR:
ON if Cp1 is greater than Cp2. Flag status
Comparison result Cp1 < Cp2
GR (SR 25505) EQ (SR 25506) 0 0
LE (SR 25507) 1
Cp1 = Cp2
0
1
0
Cp1 > Cp2
1
0
0
5-17-9 DOUBLE SIGNED BINARY COMPARE – CPSL(––) Operand Data Areas Cp1: First compare word
Ladder Symbols
IR, SR, AR, DM, HR, TC, LR CPSL(––) Cp2: Second compare word Cp1
IR, SR, AR, DM, HR, TC, LR
Cp2
Third operand: Set to 000.
000
---
Limitations
Cp1 and Cp1+1 must be in the same data area, as must Cp2 and Cp2+1.
Description
When the execution condition is OFF, CPSL(––) is not executed. When the execution condition is ON, CPSL(––) compares the 32-bit (8-digit) signed binary contents in Cp1+1, Cp1 and Cp2+1, Cp2 and outputs the result to the GR, EQ, and LE flags in the SR area. Note
1. Refer to page 27 for details on 32-bit signed binary data. 2. Refer to 5-17-2 Compare – CMP(20) for details on saving comparison results.
Precautions
Placing other instructions between CPSL(––) and the operation which accesses the EQ, LE, and GR flags may change the status of these flags. Be sure to access them before the desired status is changed.
Flags
ER:
Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
EQ:
ON if Cp1+1, Cp1 equals Cp2+1, Cp2.
LE:
ON if Cp1+1, Cp1 is less than Cp2+1, Cp2.
GR:
ON if Cp1+1, Cp1 is greater than Cp2+1, Cp2. Flag status
Comparison result Cp1+1, Cp1 < Cp2+1, Cp2
GR (SR 25505) EQ (SR 25506) 0 0
LE (SR 25507) 1
Cp1+1, Cp1 = Cp2+1, Cp2
0
1
0
Cp1+1, Cp1 > Cp2+1, Cp2
1
0
0
203
Page 222
Section 5-18
Data Conversion
5-18 Data Conversion The conversion instructions convert word data that is in one format into another format and output the converted data to specified result word(s). Conversions are available to convert between binary (hexadecimal) and BCD, to 7-segment display data, to ASCII, and between multiplexed and non-multiplexed data. All of these instructions change only the content of the words to which converted data is being moved, i.e., the content of source words is the same before and after execution of any of the conversion instructions.
5-18-1 BCD-TO-BINARY – BIN(23) Ladder Symbols
Operand Data Areas S: Source word (BCD)
BIN(23)
@BIN(23)
S
S
R
R
IR, SR, AR, DM, HR, TC, LR R: Result word
Description
IR, SR, AR, DM, HR, LR
When the execution condition is OFF, BIN(23) is not executed. When the execution condition is ON, BIN(23) converts the BCD content of S into the numerically equivalent binary bits, and outputs the binary value to R. Only the content of R is changed; the content of S is left unchanged. BCD
S
Binary
R
BIN(23) can be used to convert BCD to binary so that displays on the Programming Console or any other programming device will appear in hexadecimal rather than decimal. It can also be used to convert to binary to perform binary arithmetic operations rather than BCD arithmetic operations, e.g., when BCD and binary values must be added. Flags
ER:
The content of S is not BCD. Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
204
EQ:
ON when the result is zero.
N:
25402 is always OFF.
Page 223
Section 5-18
Data Conversion
5-18-2 DOUBLE BCD-TO-DOUBLE BINARY – BINL(58) Ladder Symbols
Operand Data Areas S: First source word (BCD)
BINL(58)
@BINL(58)
S
S
R
R
IR, SR, AR, DM, HR, TC, LR R: First result word
Description
Flags
IR, SR, AR, DM, HR, LR
When the execution condition is OFF, BINL(58) is not executed. When the execution condition is ON, BINL(58) converts an eight-digit number in S and S+1 into 32-bit binary data, and outputs the converted data to R and R+1.
ER:
BCD
S+1
S
Binary
R+1
R
The contents of S and/or S+1 words are not BCD. Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
EQ:
ON when the result is zero.
N:
25402 is always OFF.
5-18-3 BINARY-TO-BCD – BCD(24) Ladder Symbols
Operand Data Areas S: Source word (binary)
BCD(24)
@BCD(24)
S
S
R
R
IR, SR, AR, DM, HR, LR R: Result word
Description
IR, SR, AR, DM, HR, LR
BCD(24) converts the binary (hexadecimal) content of S into the numerically equivalent BCD bits, and outputs the BCD bits to R. Only the content of R is changed; the content of S is left unchanged. Binary
S
BCD
R
BCD(24) can be used to convert binary to BCD so that displays on the Programming Console or any other programming device will appear in decimal rather than hexadecimal. It can also be used to convert to BCD to perform BCD arithmetic operations rather than binary arithmetic operations, e.g., when BCD and binary values must be added.
205