The text of a manual · part 26 of 60
C200HX/C200HG/C200HE Programmable Controllers Operation Manual, pages 244 to 253
Pages 244 to 253 of 586
The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200HE-CPU42-E
Page 244
Section 5-18
Data Conversion
5-18-15 2’S COMPLEMENT – NEG(––)
Ladder Symbols
Operand Data Areas
NEG(––)
S: Source word
S
IR, SR, AR, DM, HR, TC, LR, #
R
R: Result word IR, SR, AR, DM, HR, LR
Description
Converts the four-digit hexadecimal content of the source word (S) to its 2’s complement and outputs the result to the result word (R). This operation is effectively the same as subtracting S from 0000 and outputting the result to R. If the content of S is 0000, the content of R will also be 0000 after execution, and EQ (SR 25506) will be turned on. If the content of S is 8000, the content of R will also be 8000 after execution, and UF (SR 25405) will be turned on. Note Refer to page 27 for details on 16-bit signed binary data.
Flags
Example
ER:
Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
EQ:
ON when the content of S is 0000; otherwise OFF.
UF:
ON when the content of S is 8000; otherwise OFF.
N:
ON when bit 15 of R is set to 1; otherwise OFF.
The following example shows how to use NEG(––) to find the 2’s complement of the hexadecimal value 001F and output the result to DM 0020. 00000 NEG(––) #001F DM 0020
Address
Instruction
00000 00001
LD NEG(––)
#0000 #001F
#FFE1
226
00000 # DM
---
–
Operands
Output to DM 0020.
001F 0020
Page 245
Section 5-18
Data Conversion
5-18-16 DOUBLE 2’S COMPLEMENT – NEGL(––) Ladder Symbols
Operand Data Areas
NEGL(––)
S: First source word
S
IR, SR, AR, DM, HR, TC, LR
R
R: First result word
---
IR, SR, AR, DM, HR, LR
Limitations
S and S+1 must be in the same data area, as must R and R+1.
Description
Converts the eight-digit hexadecimal content of the source words (S and S+1) to its 2’s complement and outputs the result to the result words (R and R+1). This operation is effectively the same as subtracting the eight-digit content S and S+1 from $0000 0000 and outputting the result to R and R+1. If the content of S is 0000 0000, the content of R will also be 0000 0000 after execution and EQ (SR 25506) will be turned on. If the content of S is 8000 0000, the content of R will also be 8000 0000 after execution and UF (SR 25405) will be turned on. Note Refer to page 27 for details on 32-bit signed binary data.
Flags
Example
ER:
Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
EQ:
ON when the content of S+1, S is 0000 0000; otherwise OFF.
UF:
ON when the content of S+1, S is 8000 0000; otherwise OFF.
N:
ON when bit 15 of R+1 is set to 1; otherwise OFF.
The following example shows how to use NEGL(––) to find the 2’s complement of the hexadecimal value in LR 21, LR 20 (001F FFFF) and output the result to DM 0021, DM 0020. 00000 NEG(––) LR20 DM 0020
Address
Instruction
00000 00001
LD NEGL(––)
00000 LR DM
---
0000 S+1: LR 21
–
Operands
001F R+1: DM 0021 FFE0
20 0020
0000 S: LR 20 FFFF R: DM 0020 0001
227
Page 246
Section 5-19
BCD Calculations
5-19 BCD Calculations The BCD calculation instructions – INC(38), DEC(39), ADD(30), ADDL(54), SUB(31), SUBL(55), MUL(32), MULL(56), DIV(33), DIVL(57), FDIV(79), and ROOT(72) – all perform arithmetic operations on BCD data. For INC(38) and DEC(39) the source and result words are the same. That is, the content of the source word is overwritten with the instruction result. All other instructions change only the content of the words in which results are placed, i.e., the contents of source words are the same before and after execution of any of the other BCD calculation instructions. STC(40) and CLC(41), which set and clear the carry flag, are included in this group because most of the BCD operations make use of the Carry Flag (CY) in their results. Binary calculations and shift operations also use CY. The addition and subtraction instructions include CY in the calculation as well as in the result. Be sure to clear CY if its previous status is not required in the calculation, and to use the result placed in CY, if required, before it is changed by execution of any other instruction.
5-19-1 INCREMENT – INC(38) Ladder Symbols
Operand Data Areas
INC(38)
@INC(38)
Wd
Wd
Wd: Increment word (BCD) IR, SR, AR, DM, HR, LR
Description
When the execution condition is OFF, INC(38) is not executed. When the execution condition is ON, INC(38) increments Wd, without affecting Carry (CY).
Flags
ER:
Wd is not BCD Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
EQ:
ON when the incremented result is 0.
5-19-2 DECREMENT – DEC(39) Ladder Symbols
Operand Data Areas
DEC(39)
@DEC(39)
Wd
Wd
Wd: Decrement word (BCD) IR, SR, AR, DM, HR, LR
Description
When the execution condition is OFF, DEC(39) is not executed. When the execution condition is ON, DEC(39) decrements Wd, without affecting CY. DEC(39) works the same way as INC(38) except that it decrements the value instead of incrementing it.
Flags
ER:
Wd is not BCD Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
EQ:
228
ON when the decremented result is 0.
Page 247
Section 5-19
BCD Calculations
5-19-3 SET CARRY – STC(40) Ladder Symbols STC(40)
@STC(40)
When the execution condition is OFF, STC(40) is not executed. When the execution condition is ON, STC(40) turns ON CY (SR 25504). Note Refer to Appendix C Error and Arithmetic Flag Operation for a table listing the instructions that affect CY.
5-19-4 CLEAR CARRY – CLC(41) Ladder Symbols CLC(41)
@CLC(41)
When the execution condition is OFF, CLC(41) is not executed. When the execution condition is ON, CLC(41) turns OFF CY (SR 25504). CLEAR CARRY is used to reset (turn OFF) CY (SR 25504) to “0.” CY is automatically reset to “0” when END(01) is executed at the end of each cycle. Note Refer to Appendix C Error and Arithmetic Flag Operation for a table listing the instructions that affect CY.
5-19-5 BCD ADD – ADD(30) Operand Data Areas Au: Augend word (BCD)
Ladder Symbols
IR, SR, AR, DM, HR, TC, LR, # ADD(30)
@ADD(30)
Au
Au
Ad
Ad
R
R
Ad: Addend word (BCD)
Description
R: Result word IR, SR, AR, DM, HR, LR
When the execution condition is OFF, ADD(30) is not executed. When the execution condition is ON, ADD(30) adds the contents of Au, Ad, and CY, and places the result in R. CY will be set if the result is greater than 9999.
Au + Ad + CY Flags
IR, SR, AR, DM, HR, TC, LR, #
ER:
CY
R
Au and/or Ad is not BCD. Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
CY:
ON when there is a carry in the result.
EQ:
ON when the result is 0.
229
Page 248
Section 5-19
BCD Calculations Example
If 00002 is ON, the program represented by the following diagram clears CY with CLC(41), adds the content of LR 25 to a constant (6103), places the result in DM 0100, and then moves either all zeros or 0001 into DM 0101 depending on the status of CY (25504). This ensures that any carry from the last digit is preserved in R+1 so that the entire result can be later handled as eight-digit data.
TR 0 00002 CLC(41)
ADD(30)
Address
Instruction
00000 00001 00002 00003
LR OUT CLC(41) ADD(30)
LR 25 #6103 DM 0100 25504 MOV(21)
00004 00005
25504 MOV(21)
00006 00007 00008
TR
LD AND NOT MOV(21)
#0000 DM 0101
00002 0
LR # DM
25 6103 0100 25504
# DM TR
0001 0101 0 25504
# DM
0000 0101
AND MOV(21)
#0001 DM 0101
Operands
Although two ADD(30) can be used together to perform eight-digit BCD addition, ADDL(54) is designed specifically for this purpose.
5-19-6 DOUBLE BCD ADD – ADDL(54) Operand Data Areas Au: First augend word (BCD)
Ladder Symbols
IR, SR, AR, DM, HR, TC, LR ADDL(54)
@ADDL(54)
Au
Au
Ad
Ad
R
R
Ad: First addend word (BCD) IR, SR, AR, DM, HR, TC, LR R: First result word IR, SR, AR, DM, HR, LR
Limitations
Each of the following pairs must be in the same data area: Au and Au+1, Ad and Ad+1, and R and R+1.
Description
When the execution condition is OFF, ADDL(54) is not executed. When the execution condition is ON, ADDL(54) adds the contents of CY to the 8-digit value in Au and Au+1 to the 8-digit value in Ad and Ad+1, and places the result in R and R+1. CY will be set if the result is greater than 99999999. Au + 1
Au
Ad + 1
Ad
+ CY
230
CY R+1
R
Page 249
Section 5-19
BCD Calculations Flags
ER:
Au and/or Ad is not BCD. Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
Example
CY:
ON when there is a carry in the result.
EQ:
ON when the result is 0.
When 00000 is ON, the following program adds two 12-digit numbers, the first contained in LR 20 through LR 22 and the second in DM 0012. The result is placed in LR 10 through HR 13. In the second addition (using ADD(30)), any carry from the first addition is included. The carry from the second addition is placed in HR 13 by using @ADB(50) (see 5-20-1 BINARY ADD – ADB(50)) with two all-zero constants to indirectly place the content of CY into HR 13.
00000
Address
Instruction
00000 00001 00002
LD CLC(41) @ADDL(54)
Operands
CLC(41) @ADDL(54) LR 20 DM 0010 HR 10 @ADD(30)
00003
DM 0012 HR 12
00004
LR DM HR
20 0010 10
LR DM HR
22 0012 12
# # HR
0000 0000 13
@ADD(30)
LR 22
@ADB(50)
00000
@ADB(50)
#0000 #0000 HR 13
5-19-7 BCD SUBTRACT – SUB(31) Operand Data Areas Mi: Minuend word (BCD)
Ladder Symbols
IR, SR, AR, DM, HR, TC, LR, # SUB(31)
@SUB(31)
Mi
Mi
Su
Su
R
R
Su: Subtrahend word (BCD)
Description
IR, SR, AR, DM, HR, TC, LR, # R: Result word IR, SR, AR, DM, HR, LR
When the execution condition is OFF, SUB(31) is not executed. When the execution condition is ON, SUB(31) subtracts the contents of Su and CY from Mi, and places the result in R. If the result is negative, CY is set and the 10’s complement of the actual result is placed in R. To convert the 10’s complement to the true result, subtract the content of R from zero (see example below).
Mi – Su – CY
CY
R
Note The 2’s COMPLEMENT – NEG(––) instruction can be used to convert binary data only, it cannot be used with BCD data.
231
Page 250
Section 5-19
BCD Calculations Flags
ER:
Mi and/or Su is not BCD. Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
! Caution
Example
CY:
ON when the result is negative, i.e., when Mi is less than Su plus CY.
EQ:
ON when the result is 0.
Be sure to clear the carry flag with CLC(41) before executing SUB(31) if its previous status is not required, and check the status of CY after doing a subtraction with SUB(31). If CY is ON as a result of executing SUB(31) (i.e., if the result is negative), the result is output as the 10’s complement of the true answer. To convert the output result to the true value, subtract the value in R from 0.
When 00002 is ON, the following ladder program clears CY, subtracts the contents of DM 0100 and CY from the content of 010 and places the result in HR 20. If CY is set by executing SUB(31), the result in HR 20 is subtracted from zero (note that CLC(41) is again required to obtain an accurate result), the result is placed back in HR 20, and HR 2100 is turned ON to indicate a negative result. If CY is not set by executing SUB(31), the result is positive, the second subtraction is not performed, and HR 2100 is not turned ON. HR 2100 is programmed as a self-maintaining bit so that a change in the status of CY will not turn it OFF when the program is recycled. In this example, differentiated forms of SUB(31) are used so that the subtraction operation is performed only once each time 00002 is turned ON. When another subtraction operation is to be performed, 00002 will need to be turned OFF for at least one cycle (resetting HR 2100) and then turned back ON.
TR 0 00002 CLC(41)
@SUB(31) 010
First subtraction
Address
Instruction
00000 00001 00002 00003
LD OUT CLC(41) @SUB(31)
Operands TR
DM 0100
DM HR
HR 20 25504 CLC(41)
@SUB(31) #0000
Second subtraction
00004 00005 00006
AND CLC(41) @SUB(31)
HR 20 HR 20 25504 HR 2100
HR 2100
Turned ON to indicate negative result.
00007 00008 00009 00010
LD AND OR OUT
# HR HR TR HR HR
00002 0
010 0100 20 25504
0000 20 20 0 25504 2100 2100
The first and second subtractions for this diagram are shown below using example data for 010 and DM 0100.
232
Page 251
Section 5-19
BCD Calculations
Note The actual SUB(31) operation involves subtracting Su and CY from 10,000 plus Mi. For positive results the leftmost digit is truncated. For negative results the 10s complement is obtained. The procedure for establishing the correct answer is given below. First Subtraction IR 010 1029 DM 0100 – 3452 CY –0 HR 20 7577 (1029 + (10000 – 3452)) CY 1 (negative result) Second Subtraction 0000 HR 20 –7577 CY –0 HR 20 2423 (0000 + (10000 – 7577)) CY 1 (negative result) In the above case, the program would turn ON HR 2100 to indicate that the value held in HR 20 is negative.
5-19-8 DOUBLE BCD SUBTRACT – SUBL(55) Operand Data Areas Mi: First minuend word (BCD)
Ladder Symbols
IR, SR, AR, DM, HR, TC, LR SUBL(55)
@SUBL(55)
Mi
Mi
Su
Su
R
R
Su: First subtrahend word (BCD) IR, SR, AR, DM, HR, TC, LR R: First result word IR, SR, AR, DM, HR, LR
Limitations
Each of the following pairs must be in the same data area: Mi and Mi+1, Su and Su+1, and R and R+1.
Description
When the execution condition is OFF, SUBL(55) is not executed. When the execution condition is ON, SUBL(55) subtracts CY and the 8-digit contents of Su and Su+1 from the 8-digit value in Mi and Mi+1, and places the result in R and R+1. If the result is negative, CY is set and the 10’s complement of the actual result is placed in R. To convert the 10’s complement to the true result, subtract the content of R from zero. Since an 8-digit constant cannot be directly entered, use the BSET(71) instruction (see 5-16-3 BLOCK SET – BSET(71)) to create an 8-digit constant. Mi + 1
Mi
Su + 1
Su
– CY
CY
R+1
R
Note The DOUBLE 2’s COMPLEMENT – NEGL(––) instruction can be used to convert binary data only, it cannot be used with BCD data.
233
Page 252
Section 5-19
BCD Calculations Flags
ER:
Mi, M+1,Su, and Su+1 are not BCD. Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
CY:
ON when the result is negative, i.e., when Mi is less than Su.
EQ:
ON when the result is 0.
The following example works much like that for single-word subtraction. In this example, however, BSET(71) is required to clear the content of DM 0000 and DM 0001 so that a negative result can be subtracted from 0 (inputting an 8-digit constant is not possible). Example
TR 0 00003 CLC(41)
First subtraction
@SUBL(55) HR 20 120 DM 0100 25504 @BSET(71) #0000 DM 0000 DM 0001 CLC(41)
Second subtraction
@SUBL(55) DM 0000 DM 0100 DM 0100 25504 HR 2100
HR 2100
Address
Instruction
00000 00001 00002 00003
LD OUT CLC(41) @SUBL(55)
Turned ON to indicate negative result.
Operands
TR
HR DM 00004 00005
AND @BSET(71) # DM DM
234
00003 0
20 120 0100 25504 0000 0000 0001
Address 00006 00007
00008 00009 00010 00011
Instruction
Operands
CLC(41) @SUBL(55)
LD AND OR OUT
DM DM DM TR HR HR
0000 0100 0100 0 25504 2100 2100
Page 253
Section 5-19
BCD Calculations
5-19-9 BCD MULTIPLY – MUL(32) Operand Data Areas Md: Multiplicand (BCD)
Ladder Symbols
IR, SR, AR, DM, HR, TC, LR, # MUL(32)
@MUL(32)
Md
Md
Mr
Mr
R
R
Mr: Multiplier (BCD) IR, SR, AR, DM, HR, TC, LR, # R: First result word IR, SR, AR, DM, HR LR
Limitations
R and R+1 must be in the same data area.
Description
When the execution condition is OFF, MUL(32) is not executed. When the execution condition is ON, MUL(32) multiplies Md by the content of Mr, and places the result In R and R+1. Md
X R +1
Example
Mr
R
When IR 00000 is ON with the following program, the contents of IR 013 and DM 0005 are multiplied and the result is placed in HR 07 and HR 08. Example data and calculations are shown below the program.
00000 MUL(32) 013 DM 0005 HR 07
0
Flags
Instruction
00000 00001
LD MUL(32)
Operands 00000
DM HR
3
Md: IR 013 3 5 6
X
0
Mr: DM 0005 0 2 5
R+1: HR 08 0 0 8
3
R: HR 07 9 0
ER:
Address
013 00005 07
0
Md and/or Mr is not BCD. Indirectly addressed DM word is non-existent. (Content of word is not BCD, or the DM area boundary has been exceeded.)
EQ:
ON when the result is 0.
235