The text of a manual · part 40 of 60

C200HX/C200HG/C200HE Programmable Controllers Operation Manual, pages 384 to 393

Pages 384 to 393 of 586

The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200HE-CPU42-E

Page 384

Section 6-1

Cycle Time

The first three operations immediately after power application are performed only once each time the PC is turned on. The rest of the operations are performed in cyclic fashion. The cycle time is the time that is required for the CPU Unit to complete one of these cycles. This cycle includes basically 9 types of operation: Overseeing, Program execution, Cycle time calculation, I/O refreshing, Host Link Unit servicing, RS-232C port servicing, Peripheral Device servicing, Communications Board servicing, and SYSMAC NET/SYSMAC LINK servicing. The cycle time is the total time required for the PC to perform all 9 of these operations. The time required for operation 3, cycle time calculation, is negligible and can be ignored in actual calculations. Operation 1. Overseeing 2. Program execution

3. Cycle time calculation

4. I/O refreshing

Time required

Function

0.7 ms (2.1 ms in the C200HE-CPU11-E)

Watchdog timer reset. I/O Bus, Program Memory checked. Clock refreshed. Total execution time for all instructions varies Program executed. with program size, the instructions used, and execution conditions. Refer to 6-3 Instruction Execution Times for details. Negligible, but a wait can be generated to Cycle time calculated. When the CYCLE bring the cycle time up to the minimum setTIME instruction (SCAN(18)) is executed, ting if one has been made. waits until the set time has elapsed and then resets the watchdog timer. Total of following times: Input bits set according to status of input signals. Output signals sent according to 20 μs per input byte (8 points). 20 μs per output byte (8 points). (12-point Output Units status of output bits in memory. PC Link Unit I/O refresh time.

Inputs and Outputs in Remote I/O Systems refreshed.

Special I/O Unit refresh time.

Special I/O Units serviced.

1.1 ms per Remote I/O Master Unit + 0.17 ms per I/O word used on Slave Racks.

Group-2 High-density I/O Units serviced.

calculated as 16 points.)

Group-2 (High-density) I/O Unit refresh time. Refer to the tables below for details on PC Link, Special I/O Unit, and Group-2 Highdensity I/O Unit refresh times. 5. Host Link Unit servicing

6 ms per Unit max.

Commands from computers connected through Rack-mounting Host Link Units processed.

6. RS-232C port servicing

0 ms when no device is connected.

Communications with devices connected to RS-232C port processed.

7. Peripheral device servicing 8. Communications Board servicing

9. SYSMAC NET Link/ SYSMAC LINK servicing PC card servicing

366

0.26 ms minimum or T × 0.05, where T is the cycle time calculated in operation 3 0 ms when no device is connected. 0.26 ms minimum or T × 0.05, where T is the cycle time calculated in operation 3 0.5 ms + processing time per port. The processing time per port is as follows: 0.26 ms minimum or T × 0.05, where T is the cycle time calculated in operation 3 0 ms when no Communications Unit is mounted. For or 0.8 ms + 15 ms max. per Unit. For 3.5 ms max. per Unit. For C200HW-PCU01/PCS01: 6 ms max.

Commands from Programming Devices (computers, Programming Consoles, etc.) processed. Commands from the Communications Board (RS-232C, RS-422, or RS-485) are processed. Commands from computers and other devices connected to SYSMAC NET Link/ SYSMAC LINK/PC Card Units processed.

Page 385

Section 6-1

Cycle Time PC Link Unit I/O Refresh

I/O pts to refresh

Time required (ms)

Special I/O Unit Refresh

512

7.4

256

4.1

128

2.7

64

1.7

Unit C200H-ID501/215 C200H-OD501/215 C200H-MD501/215 C200H-CT001-V1/CT002 C200H-CT021 C200H-NC111/NC112 C200HW-NC113 C200H-NC211 C200HW-NC213 C200HW-NC413 C200H-MC221 C200H-AD001 C200H-DA001 C200H-TS001/TS101 C200H-ASC02 C200H-IDS01-V1/IDS21 C200H-OV001 C200H-FZ001

C200H-CP114 C200H-AD002

C200H-DA002 C200HW-SRM21 C200HW-DRM21-V1 C200HW-DRT21

Time required per Unit 0.6 ms 0.6 ms when set for 32 I/O pts. 1.6 ms when set for dynamic I/O 2.0 ms 0.7 ms 2.1 ms 2.6 ms 5.0 ms 2.9 ms 4.5 ms 2 ms for normal operation 3 ms for refreshing expansion data area 1.1 ms 0.9 ms 1.2 ms 1.9 ms normally, 5.0 ms for @ format 2.0 ms normally, 5.5 ms for command transfer 3.3 ms 2.0 ms 2.7 ms 2.0 ms 1.4 ms 2.7 ms 1.0 ms 0.44 ms when the max. number of Slaves is 16. 0.88 ms when the max. number of Slaves is 32. 1.72 ms + 0.022 × the number of words

Group-2 High-density I/O Unit Refresh

Unit C200H-ID216 C200H-OD218 C200H-ID217 C200H-OD219

NT Links

If the PC is connected to a Programmable Terminal (PT) via a C200HX/HG/HE Interface Unit, the times shown in the following table will be required to refresh I/O for the PT.

Time required per Unit 0.18 ms 0.14 ms 0.31 ms 0.23 ms

Number of table entries for PT

I/O refresh time

Minimum setting: Character string table: 0 Numeral table: 0

2.5 ms

Maximum setting: Character string table: 32 Numeral table: 128

5.4 ms

367

Page 386

Section 6-2

Calculating Cycle Time Watchdog Timer and Long Cycle Times

Within the PC, the watchdog timer measures the cycle time and compares it to a set value. If the cycle time exceeds the set value of the watchdog timer, a FALS 9F error is generated and the CPU Unit stops. WDT(94) can be used to extend the set value for the watchdog timer. Even if the cycle time does not exceed the set value of the watchdog timer, a long cycle time can adversely affect the accuracy of system operations as shown in the following table. Cycle time (ms) 10 or greater 20 or greater 100 or greater 200 or greater 6,500 or greater

Online Editing

0.1-second clock pulse (SR 25500) not accurately readable and Cycle Time Error Flag (SR 25309) turns ON. 0.2-second clock pulse (SR 25501) not accurately readable. FALS code 9F generated regardless of watchdog timer setting and the system stops.

When online editing is executed from a Programming Device, operation will be interrupted for a maximum of 80 ms and interrupts will be masked to rewrite the user program. No warnings will be given for long cycle times during this interval. Check the effects on I/O response time before editing the program online. When bits 00 to 07 of AR 25 contain the password code of “5A,” online editing will be disabled and the CPU Unit will be in standby status while the Online Edit Disable Bit (AR 2509) is ON. The Online Edit Standby Flag (AR 2510) will be ON while the CPU Unit is in standby status. Processing will be executed when AR 2509 is turned OFF. (AR 2510 will be turned OFF, too.) ! Caution

6-2

Possible adverse affects TIMH(15) inaccurate when TC 016 through TC 511 are used. (Accuracy when using TC 000 through TC 0015 not affected.) 0.02-second clock pulse (SR 25401) not accurately readable.

Editing the program online can cause delays in I/O responses with no warnings being given from the system for the long cycle time produced by editing online. Before editing online, make sure that delays in I/O responses will not create a dangerous situation in the controlled system.

Calculating Cycle Time The PC configuration, the program, and program execution conditions must be taken into consideration when calculating the cycle time. This means taking into account such things as the number of I/O points, the programming instructions used, and whether or not peripheral devices are employed. This section shows some basic cycle time calculation examples. To simplify the examples, the instructions used in the programs have been assumed to be all either LD or OUT. The average execution time for the instructions is thus 0.156 μs. (Execution times are given in the table in 6-3 Instruction Execution Times.)

368

Page 387

Section 6-2

Calculating Cycle Time

6-2-1 PC with I/O Units Only Here, we’ll compute the cycle time for a simple PC. The CPU Unit controls only I/O Units, eight on the CPU Rack and five on a 5-slot Expansion I/O Rack. The PC configuration for this would be as shown below. It is assumed that the program contains 5,000 instructions requiring an average of 0.156 μs each to execute. 8-point Input Units

8-point Output Units

CPU Rack

Expansion I/O Rack

16-point Input Units

12-point Output Units

8-point Output Unit

Calculations

The equation for the cycle time from above is as follows: Cycle time =

Overseeing time + Program execution time + I/O refresh time + Peripheral device servicing time

Process

Calculation

With Peripheral Device 0.7 ms

Without Peripheral Device 0.7 ms

Overseeing

Fixed

Program execution

0.156 μs/instruction × 5,000 instructions See below.

0.78 ms

0.78 ms

0.34 ms

0.34 ms

Minimum time

0.26 ms

0.0 ms

Total of above

2.08 ms

1.82 ms

I/O refresh Peripheral device servicing Cycle time

The I/O refresh time would be as follows for two16-point Input Units, four 8-point Input Units, two 12-point Output Units (12-point Units are treated as 16-point Units), and five 8-point Output Units controlled by the PC: (16 pts × 2) + (8 pts × 4) 8 pts

× 20 μs +

(16 pts × 2) + (8 pts × 5) 8 pts

× 20 μs = 0.34 ms

6-2-2 PC with Host Link and Remote I/O Master Units Here, the cycle time is computed for a PC with a Host Link Unit and Remote I/O Master Unit installed. The PC configuration for this could be as shown below. The CPU Unit controls three 8-point Input Units, three 8-point Output Units, a Host Link Unit, and a Remote I/O Master Unit connected to a Remote I/O Slave Rack containing four 16-point Input Units and four 12-point Output Units.

369

Page 388

Section 6-2

Calculating Cycle Time

It is assumed that the program contains 5,000 instructions requiring an average of 0.156 μs each to execute, and that nothing is connected to the RS-232C port and no SYSMAC NET/SYSMAC LINK Unit is mounted.

Host Link Unit Remote I/O Master Unit

8-point Output Units

8-point Input Units

CPU Rack

Computer

Slave Rack

16-point Input Units

Calculations

12-point Output Units

The equation for the cycle time is as follows: Cycle time =

Overseeing time + Program execution time + I/O refreshing time + Host Link Unit servicing time + Peripheral device servicing time

Process

Calculation

With Peripheral Device 0.7 ms

Without Peripheral Device 0.7 ms

Overseeing

Fixed

Program execution

0.78 ms

0.78 ms

I/O refresh

0.156 μs/instruction × 5,000 instructions See below.

2.58 ms

2.58 ms

Host Link servicing

Fixed

6.0 ms

6.0 ms

Peripheral device servicing

0.7 + 0.78 + 2.58 + 6 = 10.06

0.50 ms

0.0 ms

Cycle time

10.06 × 0.05 = 0.50 Total of above

10.56 ms

10.06 ms

The I/O refreshing time would be as follows for three 8-point Input Units and three 8-point Output Units mounted in the CPU Rack, and eight Units mounted in a Slave Rack.

(8 pts × 3) + (8 pts × 3) × 20 μs + 1.1 ms + 8 Units × 0.17 ms = 2.58 ms 8 pts

370

Page 389

Section 6-3

Instruction Execution Times

6-3

Instruction Execution Times The following table lists the execution times for all instructions that are available for the C200HX/HG/HE. The maximum and minimum execution times and the conditions which cause them are given where relevant. When “word” is referred to in the Conditions column, it implies the content of any word except for indirectly addressed DM words. Indirectly addressed DM words, which create longer execution times when used, are indicated by Execution times for most instructions depend on whether they are executed with an ON or an OFF execution condition. Exceptions are the ladder diagram instructions OUT and OUT NOT, which require the same time regardless of the execution condition. The OFF execution time for an instruction can also vary depending on the circumstances, i.e., whether it is in an interlocked program section and the execution condition for IL is OFF, whether it is between JMP(04) 00 and JME(05) 00 and the execution condition for JMP(04) 00 is OFF, or whether it is reset by an OFF execution condition. “R,” “IL,” and “JMP” are used to indicate these three times. All execution times are given in microseconds unless otherwise noted.

Instruction

Conditions

ON execution time (μs)

OFF execution time (μs)

For IR and SR 23600 to SR 25515

C200HX C200HG C200HE C200HX C200HG C200HE 0.104 0.156 0.312 0.104 0.156 0.313

For SR 25600 to SR 51115

0.208

0.313

0.626

0.104

0.156

0.313

For IR and SR 23600 to SR 25515

0.104

0.156

0.313

0.104

0.156

0.313

For SR 25600 to SR 51115

0.208

0.313

0.626

0.104

0.156

0.313

For IR and SR 23600 to SR 25515

0.104

0.156

0.312

0.104

0.156

0.313

For SR 25600 to SR 51115

0.208

0.313

0.626

0.104

0.156

0.313

For IR and SR 23600 to SR 25515

0.104

0.156

0.313

0.104

0.156

0.313

For SR 25600 to SR 51115

0.208

0.313

0.626

0.104

0.156

0.313

For IR and SR 23600 to SR 25515

0.104

0.156

0.313

0.104

0.156

0.313

For SR 25600 to SR 51115

0.208

0.313

0.626

0.104

0.156

0.313

For IR and SR 23600 to SR 25515

0.104

0.156

0.313

0.104

0.156

0.313

For SR 25600 to SR 51115

0.208

0.313

0.626

0.104

0.156

0.313

AND LD

---

0.104

0.156

0.313

0.104

0.156

0.313

OR LD

---

0.104

0.156

0.313

0.104

0.156

0.313

OUT

For IR and SR 23600 to SR 25515

0.208

0.313

0.626

0.208

0.313

0.626

For SR 25600 to SR 51115

0.313

0.468

0.936

0.208

0.313

0.626

For IR and SR 23600 to SR 25515

0.208

0.313

0.626

0.208

0.313

0.626

For SR 25600 to SR 51115

0.313

0.468

0.936

0.208

0.313

0.626

Constant for SV for SV For designated words 256 to 511 Constant for SV for SV For designated words 256 to 511 For IR and SR 23600 to SR 25515

0.417

0.625

1.25

0.417 0.417 0.417 0.208

0.625 0.625 0.625 0.313

1.25 1.25 1.25 0.626

0.417 22.45 0.417 0.417 22.55 0.417 0.208

0.625 22.45 0.625 0.625 22.55 0.625 0.313

1.25 37.15 1.25 1.25 37.25 1.25 0.626

For SR 25600 to SR 51115

0.313

0.468

0.936

0.208

0.313

0.626

For IR and SR 23600 to SR 25515

0.208

0.313

0.626

0.208

0.313

0.626

For SR 25600 to SR 51115

0.313

0.468

0.936

0.208

0.313

0.626

NOP(00)

---

0.104

0.156

0.312

0.313

0.469

0.938

END(01)

---

24.75

39.45

0.313

0.469

0.938

IL(02)

---

7.55

22.25

0.313

0.469

0.938

ILC(03)

---

9.25

23.95

0.313

0.469

0.938

LD LD NOT AND AND NOT OR OR NOT

OUT NOT TIM

CNT

SET RSET

371

Page 390

Section 6-3

Instruction Execution Times Instruction

Conditions

ON execution time (μs) OFF execution time (μs) C200HX C200HG C200HE C200HX C200HG C200HE

JMP(04)

---

7.65

22.35

0.313

0.469

0.938

JME(05)

---

7.95

22.65

0.313

0.469

0.938

FAL(06)

FAL numbers 01 to 99 FAL number 00

88.6 86.6

88.6 86.6

0.313 0.313

0.469 0.469

0.938 0.938

FALS(07)

---

---

(see note 2)

0.313

0.469

0.938

STEP(08)

---

33.1

47.8

0.313

0.469

0.938

15.3

30

SNXT(09)

---

9.25

23.95

0.313

0.469

0.938

SFT(10)

With 1-word shift register

21.05

35.75

R: 8.05

IL: 8.05

With 100-word shift register

117.8

132.5

R: 8.05

IL: 8.05

With 250-word shift register

262.5

277.2

R: 8.05

IL: 8.05

For IR and SR 23600 to SR 25515

0.208

0.313

0.625

0.208

0.319

JMP: 8.05 JMP: 8.05 JMP: 8.05 0.625

For SR 25600 to SR 51115

0.318

0.469

0.938

Constant for SV

19.15

33.85

R: 16.95 for SV

31.45

46.15

R: 16.95

DIFU(13)

---

13.75

28.45

Normal: 13.75

IL: 11.65 JMP: 11.65 IL: 11.65 JMP: 11.65 IL: 13.65 JMP: 11.95

DIFD(14)

---

13.65

28.35

Normal: 13.65

IL: 13.55 JMP: 11.85

TIMH(15)

Interrupt Constant for SV

18.35

33.05

R: 25.05

Normal cycle

16.55

31.25

R: 21.95

Interrupt for SV

18.35

33.05

R: 37.1

Normal cycle

16.55

31.25

R: 34.1

When shifting 1 word

16.45

31.15

0.313

IL: 24.05 JMP: 14.45 IL:21.05 JMP: 11.25 IL: 36.5 JMP: 14.45 IL: 33.3 JMP: 11.25 0.469 0.938

When shifting 6,144 words using

6.45 ms

(see note 2)

When comparing a constant to a word

0.417

0.625

1.25

0.313

0.469

0.938

When comparing two words

0.521

0.781

1.56

When comparing two

35.2

When transferring a constant to a word

0.417

0.625

1.25

0.313

0.469

0.938

When comparing two words

0.625

0.937

1.87

When transferring to

33.7

When transferring a constant to a word

0.417

0.625

1.25

0.313

0.469

0.938

When comparing two words

0.625

0.937

1.87

When transferring to

34.3

49

When converting a word to a word

19.65

34.35

0.313

0.469

0.938

When converting to

40.5

55.2

When converting a word to a word

18.25

32.95

0.313

0.469

0.938

When converting to

39.1

53.8

When shifting a word

12.25

26.95

0.313

0.469

0.938

When shifting

23.35

38.05

KEEP(11) CNTR(12)

WSFT(16)

CMP(20)

MOV(21)

MVN(22)

BIN(23) BCD(24) ASL(25)

372

(see note 1)

49.9

48.4

Page 391

Section 6-3

Instruction Execution Times Instruction ASR(26) ROL(27) ROR(28) COM(29) ADD(30)

SUB(31)

MUL(32)

DIV(33)

ANDW(34)

ORW(35)

XORW(36)

XNRW(37)

INC(38) DEC(39)

Conditions

ON execution time (μs) OFF execution time (μs) C200HX C200HG C200HE C200HX C200HG C200HE

When shifting a word

11.95

26.65

When shifting

22.95

37.65

When rotating a word

13.15

27.85

When rotating

24.25

38.95

When rotating a word

13.15

27.85

When rotating

24.25

38.95

When inverting a word

11.45

26.15

When inverting

22.65

37.35

Constant + word → word

16.65

31.35

Word + word→ word

18.45

33.15

+ →

50.1

64.8

Constant – word → word

16.65

31.35

Word – word→ word

18.45

33.15

– →

50.1

64.8

Constant × word → word

31.15

45.85

Word × word→ word

32.95

47.65

× →

64.7

79.4

Word ÷ constant → word

30.15

44.85

Word ÷ word→ word

32.35

47.05

÷ →

64.1

78.8

Constant AND word → word

14.35

29.05

Word AND word→ word

15.25

29.95

AND →

46.7

61.4

Constant OR word → word

14.35

29.05

Word OR word→ word

15.25

29.95

OR →

46.7

61.4

Constant XOR word → word

14.35

29.05

Word XOR word→ word

15.25

29.95

XOR →

46.7

61.4

Constant XNOR word → word

14.55

29.25

Word XNOR word→ word

15.45

30.15

XNOR →

46.9

61.6

When incrementing a word

11.55

26.25

When incrementing

22.45

37.15

When decrementing a word

11.45

26.15

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

When decrementing

22.35

37.05

STC(40)

---

7.22

21.92

0.313

0.469

0.938

CLC(41)

---

7.22

21.92

0.313

0.469

0.938

TRSM(45)

---

18.65

33.35

0.313

0.469

0.938

MSG(46)

Designated as DM

12.05

26.75

0.313

0.469

0.938

Designated as

21.95

36.65

Constant + word → word

19.15

33.85

0.313

0.469

0.938

Word + word → word

20.05

34.75

+ →

51.7

66.4

Constant – word → word

18.95

33.65

0.313

0.469

0.938

Word – word → word

19.85

34.55

– →

51.7

66.4

ADB(50)

SBB(51)

373

Page 392

Section 6-3

Instruction Execution Times Instruction

Conditions

ON execution time (μs) OFF execution time (μs) C200HX C200HG C200HE C200HX C200HG C200HE

Constant × word → word

16.95

31.65

Word × word → word

17.85

32.55

× →

49.3

64

Word ÷ constant → word

17.15

31.85

Word ÷ word → word

18.05

32.75

÷ →

49.7

64.4

Word + word → word

22.45

37.15

+ →

53.9

68.6

Word – word → word

22.45

37.15

– →

53.9

68.6

Word × word → word

110.6

125.3

× →

142.6

157.3

Word ÷ word → word

105.8

120.5

÷ →

135.8

150.5

BINL(58)

When converting words to words When converting to

35.15 55.9

BCDL(59)

When converting words to words When converting to

XFER(70)

MLB(52)

DVB(53)

ADDL(54) SUBL(55) MULL(56) DIVL(57)

BSET(71)

ROOT(72)

XCHG(73) SLD(74)

SRD(75)

MLPX(76) DMPX(77)

374

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

49.85 70.6

0.313

0.469

0.938

25.75 46.5

40.45 61.2

0.313

0.469

0.938

When transferring 1 word

45.3

44.2

0.313

0.469

0.938

When transferring 1,024 words using

655

653.9

When transferring 6,143 words using

3.66 ms

(see note 3)

When setting a constant to 1 word

19.75

34.45

0.313

0.469

0.938

When setting ms to 1,024 words using

40.9

55.6

When setting ms to 6,144 words using

52.3

67

When taking root of word and placing in a word

41.7

56.4

0.313

0.469

0.938

When taking root of 99,999,999 in and placing in

85.5

100.2

Between words

14.45

29.15

0.313

0.469

0.938

Between

36.45

51.15

When shifting 1 word

15.65

30.35

0.313

0.469

0.938

When shifting 1,024 DM words using

2.72 ms

(see note 2)

When shifting 6,144 DM words using

16.2 ms

(see note 2)

When shifting 1 word

15.65

30.35

0.313

0.469

0.938

When shifting 1,024 DM words using

2.72 ms

(see note 2)

When shifting 6,144 DM words using

16.2 ms

(see note 2)

When decoding word to word

47.3

62

0.313

0.469

0.938

When decoding to

103.8

118.5

When encoding a word to a word

28.45

43.15

0.313

0.469

0.938

When encoding to

111.8

126.5

Page 393

Section 6-3

Instruction Execution Times Instruction SDEC(78)

FDIV(79)

DIST(80) COLL(81)

Conditions

ON execution time (μs) OFF execution time (μs) C200HX C200HG C200HE C200HX C200HG C200HE

When decoding a word to a word

26.95

41.65

When decoding 2 digits to

63.3

78

When decoding 4 digits to

71.7

86.4

Word ÷ word → word (equals 0)

62.3

77

Word ÷ word → word (doesn’t equal 0)

499

513.7

÷ →

843

857.7

Constant → (word + (word))

27.65

42.35

→ +

61.5

76.2

(Word + (word)) → word

28.75

43.45

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

0.313

0.469

0.938

+ →

64.3

79

MOVB(82)

When transferring a constant to a word When transferring word to a word When transferring to

17.35 19.45 52.9

32.05 34.15 67.6

0.313

0.469

0.938

MOVD(83)

When transferring a constant to a word When transferring word to a word When transferring to

16.95 18.25 54.3

31.65 32.95 69

0.313

0.469

0.938

SFTR(84)

When shifting 1 word When shifting 1,024 using

20.05 1.1 ms

0.313

0.469

0.938

When shifting 6,144 using

6.37 ms

Comparing to words in a designated table Comparing to words in a designated table Comparing → table Between words

37.25

34.75 (see note 2) (see note 2) 51.95

0.313

0.469

0.938

38.1 69.1

52.8 83.8

30.1

44.8

0.313

0.469

0.938

Between

78.3

93

1-word transmit

60.9

75.6

0.313

0.469

0.938

TCMP(85)

ASC(86) SEND(90)

1000-word transmit

99.2

113.9

SBS(91)

---

22.1

36.8

0.313

0.469

0.938

SBN(92)

---

---

---

0.313

0.469

0.938

RET(93)

---

20.9

35.6

0.313

0.469

0.938

WDT(94)

---

10.55

25.25

0.313

0.469

0.938

IORF(97)

1-word refresh

110 (IN), 170 (OUT)

110 (IN), 0.313 170 (OUT)

0.469

0.938

30-word refresh

2002

2000.9

1-word refresh

67.1

67.1

0.313

0.469

0.938

1000-word refresh

105.8

105.8

Designating a word parameter

38.5

53.2

0.313

0.469

0.938

Designating a parameter

RECV(98) MCRO(99)

58.2

72.9

When resetting 1 word Default: (17) When shifting 1 word using When shifting 10 word using

24.95 29.05 39.9

39.65 43.75 54.6

0.313

0.469

0.938

SCAN(––)

0.313

0.469

0.938

0.313

0.469

0.938

ASFT(––)

18.65

33.35

Default: (18) for SV

Constant for SV

30.45

45.15

MCMP(––)

60.3

75

93

107.7

Comparing 2 words, result word

Default: (19) Comparing 2 result

375