The text of a manual · part 55 of 60
C200HX/C200HG/C200HE Programmable Controllers Operation Manual, pages 534 to 543
Pages 534 to 543 of 586
The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200HE-CPU42-E
Page 534
Appendix A
Standard Models Optical Power Tester Name
Specifications
Head Unit
Model number
S3200-CAT200 2 (provided with the Tester)
S3200-CAT2000
S3200-CAT270 2 (provided with the Tester)
S3200-CAT2700
SYSMAC BUS: C200H-RM001-PV1 C200H-RT001/RT002-P C500-RM001-(P)V1 C500-RT001/RT002-(P)V1
S3200-CAT282 2 (provided with the Tester)
S3200-CAT2820
SYSMAC NET: S3200-LSU03-01E C500-SNT31-V4
S3200-CAT320 2 (provided with the Tester)
S3200-CAT3200
Optical Power Tester (see note) SYSMAC NET: (provided with a connector CV500-SNT31 adapter, light source unit, small C200HS-SNT32 single-head plug, hard case, SYSMAC LINK: and AC adapter) CV500-SLK11 C200HW-SLK13/14 CV1000H-SLK11
Standards ---
Note: There is no difference between the light source unit and connector adapter for the Head Unit and those for the Optical Power Tester. Head Unit Name Head Units (a set consisting of light source unit and connector adapter) (see note)
Specifications
Model number
SYSMAC NET: CV500-SNT31 C200HS-SNT32
S3200-CAT2002
SYSMAC LINK: CV500-SLK11 C200HW-SLK13/14 CV1000H-SLK11
S3200-CAT2702
SYSMAC BUS: C500-RM001-(P)V1 C500-RT001/RT002-(P)V1 C200H-RM001-PV1 C200H-RT001/RT002-PV1
S3200-CAT2822
SYSMAC NET: S3200-LSU03-01E C500-SNT31-V4
S3200-CAT3202
Standards ---
Note: Use a proper Head Unit model for the optical module to be used. If two types of optical modules (unit type and board type) are used, order an Optical Power Tester plus a proper Head Unit model. Master Fiber Set Name Master Fiber Sets (1 m)
Specifications
Model number
S3200-CAT3202 (SYSMAC NET, NSB, NSU, Bridge)
S3200-CAT3201
S3200-CAT2002/CAT2702 (SYSMAC NET, SYSMAC LINK)
S3200-CAT2001H
S3200-CAT2822 (SYSMAC BUS)
S3200-CAT2821
Standards ---
Note: 1. The Master Fiber Set is used in combination with the Optical Power Tester to check the optical levels of optical fiber cables connected to optical fiber cable connectors. 2. Optical fiber cables must be prepared and connected by specialists. 3. The Optical Power Tester, Head Unit, Master Fiber set, and Optical Fiber Assembling Tool are required to connect optical fiber cables.
516
Page 535
Appendix A
Standard Models
Programming Devices Name
Specifications
Model number
Standards
Hand-Held, w/backlight
C200H-PRO27-E
U, C
2-m Connecting Cable included
CQM1-PRO01-E
U, C
Programming Console Mounting Bracket
Used to attach Hand-held Programming Console to a panel.
C200H-ATT01
---
Programming Console Connecting Cables
For Hand-held Programming Console
2m
C200H-CN222
---
4m
C200H-CN422
---
Programming Consoles
Data Setting Console
Used for data input and process value display for the C200H-CP114, and
C200H-DSC01
Data Setting Console Connecting Cables
For C200H-DSC01
2m
C200H-CN225
4m
C200H-CN425
Connecting Cable
Used to connect an IBM PC/AT or compatible to the C200HX/HG/HE.
3.3 m
CQM1-CIF02
---
Optional Products Name I/O Unit Cover
Specifications Cover for 10-pin terminal block
Model number C200H-COV11
Standards ---
Terminal Block Cov- Short protection for 10-pin terminal block (package of 10 covers ers); 8 pts
C200H-COV02
Short protection for 19-pin terminal block (package of 10 covers); 12 pts
C200H-COV03
Connector Cover
Protective cover for unused I/O Connecting Cable connectors
C500-COV02
Space Unit
Used for vacant slots
C200H-SP001
N, L
Battery Set
For C200H or C200HS RAM Memory Unit only
C200H-BAT09
---
517
Page 536
Appendix A
Standard Models Name
Specifications
Model number
Standards
Relay
24 VDC
G6B-1174P-FD-US ---
Backplane Insulation Plates
For C200HW-BC031 (3-slot CPU Backplane)
C200H-ATT31
For C200HW-BC051 (5-slot CPU Backplane)
C200H-ATT51
For C200HW-BC081 (8-slot CPU Backplane)
C200H-ATT81
For C200HW-BC101 (10-slot CPU Backplane)
C200H-ATTA1
For C200HW-BI031 (3-slot I/O Backplane)
C200HW-ATT32
For C200HW-BI051 (5-slot I/O Backplane)
C200HW-ATT52
For C200HW-BI081 (8-slot I/O Backplane)
C200HW-ATT82
For C200HW-BI101 (10-slot I/O Backplane)
C200HW-ATTA2
For 3-slot Backplane
C200H-ATT33
For 5-slot Backplane
C200H-ATT53
For 8-slot Backplane
C200H-ATT83
For 10-slot Backplane
C200H-ATTA3
---
External Connectors Solder terminal; 40p and a Connector Cover
C500-CE401
---
Solderless terminal; 40p and a Connector Cover (Crimp-type)
C500-CE402
---
Pressure welded terminal; 40p
C500-CE403
---
Solder terminal; 40p and a Connector Cover (Horizontal-type)
C500-CE404
---
Crimp-style terminal; 40p and a Connector Cover (Horizontaltype)
C500-CE405
---
I/O Brackets
---
N
Mounting Rails and Accessories Name
Specifications
Model number
DIN Track Mounting Bracket
1 set (2 included)
C200H-DIN01
DIN Tracks
Length: 50 cm; height: 7.3 cm
PFP-50N
Length: 1 m; height: 7.3 cm
PFP-100N
Length: 1 m; height: 16 mm
PFP-100N2
End Plate
---
PFP-M
Spacer
---
PFP-S
Standards ---
Note: Order DIN Tracks, End Plates, and Spacers in units of 10 each. SYSMAC Support Software (SSS) Name SYSMAC Support Software (for C20, C120, C200H, C200HS, C200HE, C200HG, C200HX, C500, C1000H, C2000H, CQM1, and CVM1)
518
Specifications 3.5”, 2HD for IBM PC/AT compatible Note: Version 1.0 doesn’t support the additional functions of the C200HX/HG/HE.
Model number C500-ZL3AT1-E
Standards ---
Page 537
Appendix A
Standard Models Protocol Support Software Name Protocol Support Software
Specifications 3.5”, 2HD for IBM PC/AT compatible
Model number C200HW-ZW3AT1-E
Standards ---
Training Materials Name
Specifications
Model number
Standards
SYSMAC Training System
Includes text book, cassette tape, and input switch board.
C200H-ETL01-E
---
Fuzzy Training System
Includes a Fuzzy Training System Manual, a Main C200H-ETL13-E Unit, a C200H-MR831 Memory Unit, a C200HPRO27-E Programming Console, a C200HCN222 Cable for the Programming Console, C500-SU981-E Fuzzy Training Software, an RS-232C Cable, and a carrying belt.
---
519
Page 538
Page 539
Appendix B Programming Instructions A PC instruction is input either by pressing the corresponding Programming Console key(s) (e.g., LD, AND, OR, NOT) or by using function codes. To input an instruction with its function code, press FUN, the function code, and then WRITE. Refer to the pages listed programming and instruction details. Code
Mnemonic
Name, AND
AND, AND LD
AND LOAD, AND NOT
AND NOT, CNT
COUNTER, LD, Function
Page
Logically ANDs status of designated bit with execution condition. Logically ANDs results of preceding blocks.
149
Logically ANDs inverse of designated bit with execution condition. A decrementing counter.
149
LOAD
Used to start instruction line with the status of the designated bit or to define a logic block for use with AND LD and OR LD.
149
LD NOT
LOAD NOT
Used to start instruction line with inverse of designated bit.
149, OR
OR
149, OR LD
OR LOAD
Logically ORs status of designated bit with execution condition. Logically ORs results of preceding blocks., OR NOT
OR NOT
149, OUT
OUTPUT, OUT NOT
OUTPUT NOT
Logically ORs inverse of designated bit with execution condition. Turns ON operand bit for ON execution condition; turns OFF operand bit for OFF execution condition. Turns operand bit OFF for ON execution condition; turns operand bit ON for OFF execution condition (i.e., inverts operation)., RSET
RESET
Turns the operand bit OFF when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF.
153, SET
SET
Turns the operand bit ON when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF.
153, TIM
TIMER
ON-delay (decrementing) timer operation.
159
00
NOP
NO OPERATION
158
01
END
END
02
IL
INTERLOCK
03
ILC
INTERLOCK CLEAR
04 05 (@)06
JMP JME FAL
07
FALS
08
STEP
JUMP JUMP END FAILURE ALARM AND RESET SEVERE FAILURE ALARM STEP DEFINE
Nothing is executed and program moves to next instruction. Required at the end of the program. If interlock condition is OFF, all outputs are turned OFF and all timer PVs reset between this IL(02) and the next ILC(03). Other instructions are treated as NOP; counter PVs are maintained. If jump condition is OFF, all instructions between JMP(04) and the corresponding JME(05) are ignored.
09
SNXT
STEP START
10
SFT
11
KEEP
12
CNTR
Generates a non-fatal error and outputs the designated FAL number to the Programming Console. Generates a fatal error and outputs the designated FALS number to the Programming Console. When used with a control bit, defines the start of a new step and resets the previous step. When used without N, defines the end of step execution.
150
166
150
150 150
158 155 155 157 157 304 304 295
295
SHIFT REGISTER
Used with a control bit to indicate the end of the step, reset the step, and start the next step. Creates a bit shift register.
KEEP
Defines a bit as a latch controlled by set and reset inputs.
154
REVERSIBLE COUNTER
Increases or decreases PV by one whenever the increment input or decrement input signals, respectively, go from OFF to ON.
169
171
521
Page 540
Appendix B
Programming Instructions Code
Mnemonic
Name
13
DIFU
DIFFERENTIATE UP
14
DIFD
15
TIMH
DIFFERENTIATE DOWN HIGH-SPEED TIMER
(@)16
WSFT
WORD SHIFT
17 to 19
For expansion instructions.
20
CMP
COMPARE
(@)21
MOV
MOVE
(@)22
MVN
MOVE NOT
(@)23
BIN
BCD TO BINARY
(@)24
BCD
BINARY TO BCD
(@)25
ASL
(@)26
ASR
(@)27
ROL
ARITHMETIC SHIFT LEFT ARITHMETIC SHIFT RIGHT ROTATE LEFT
(@)28
ROR
(@)29
Function
Page
Turns ON the designated bit for one cycle on the rising edge of the input signal. Turns ON the bit for one cycle on the trailing edge.
151
A high-speed, ON-delay (decrementing) timer.
164
Shifts data between starting and ending words in word units, writing zeros into starting word.
178
Compares the contents of two words and outputs result to GR, EQ, and LE Flags. Copies source data (word or constant) to destination word.
193
Inverts source data (word or constant) and then copies it to destination word. Converts four-digit, BCD data in source word into 16-bit binary data, and outputs converted data to result word. Converts binary data in source word into BCD, and outputs converted data to result word. Shifts each bit in single word of data one bit to left, with CY.
180
Shifts each bit in single word of data one bit to right, with CY. Rotates bits in single word of data one bit to left, with CY.
175
ROTATE RIGHT
Rotates bits in single word of data one bit to right, with CY.
176
COM
COMPLEMENT
Inverts bit status of one word of data.
277
(@)30
ADD
BCD ADD
229
(@)31
SUB
BCD SUBTRACT
(@)32
MUL
BCD MULTIPLY
(@)33
DIV
BCD DIVIDE
(@)34
ANDW
LOGICAL AND
Adds two four-digit BCD values and content of CY, and outputs result to specified result word. Subtracts a four-digit BCD value and CY from another four-digit BCD value and outputs result to the result word. Multiplies two four-digit BCD values and outputs result to specified result words. Divides four-digit BCD dividend by four-digit BCD divisor and outputs result to specified result words. Logically ANDs two 16-bit input words and sets corresponding bit in result word if corresponding bits in input words are both ON.
(@)35
ORW
LOGICAL OR
Logically ORs two 16-bit input words and sets corresponding bit in result word if one or both of corresponding bits in input data are ON.
279
(@)36
XORW
EXCLUSIVE OR
Exclusively ORs two 16-bit input words and sets bit in result word when corresponding bits in input words differ in status.
280
(@)37
XNRW
EXCLUSIVE NOR
Exclusively NORs two 16-bit input words and sets bit in result word when corresponding bits in input words are same in status.
281
(@)38
INC
BCD INCREMENT
Increments four-digit BCD word by one.
228
(@)39
DEC
BCD DECREMENT
Decrements four-digit BCD word by one.
228
(@)40
STC
SET CARRY
Sets carry flag (i.e., turns CY ON).
229
(@)41
CLC
CLEAR CARRY
Clears carry flag (i.e., turns CY OFF).
229
45
TRSM
Initiates data tracing.
306
(@)46
MSG
TRACE MEMORY SAMPLE MESSAGE
Displays a 16-character message on the Programming Console display.
307
47 & 48
For expansion instructions.
(@)50
ADB
BINARY ADD
243
(@)51
SBB
BINARY SUBTRACT
Adds two four-digit hexadecimal values and content of CY, and outputs result to specified result word. Subtracts a four-digit hexadecimal value and CY from another four-digit hexadecimal value and outputs result to the result word.
522
151
180
204 205 175
176
231 235 236 278
245
Page 541
Appendix B
Programming Instructions Code
Mnemonic
Name
Function
Page
(@)52
MLB
BINARY MULTIPLY
Multiplies two four-digit hexadecimal values and outputs result to specified result words.
248
(@)53
DVB
BINARY DIVIDE
Divides four-digit hexadecimal dividend by four-digit hexa- 248 decimal divisor and outputs result to specified result words.
(@)54
ADDL
DOUBLE BCD ADD
Adds two eight-digit values (2 words each) and content of CY, and outputs result to specified result words.
230
(@)55
SUBL
DOUBLE BCD SUBTRACT
Subtracts an eight-digit BCD value and CY from another eight-digit BCD value and outputs result to the result words.
233
(@)56
MULL
DOUBLE BCD MULTIPLY
Multiplies two eight-digit BCD values and outputs result to specified result words.
236
(@)57
DIVL
DOUBLE BCD DIVIDE
Divides eight-digit BCD dividend by eight-digit BCD divisor and outputs result to specified result words.
237
(@)58
BINL
DOUBLE BCD TO DOUBLE BINARY
Converts BCD value in two consecutive source words into binary and outputs converted data to two consecutive result words.
205
(@)59
BCDL
DOUBLE BINARY TO DOUBLE BCD
Converts binary value in two consecutive source words into BCD and outputs converted data to two consecutive result words.
206
60 to 69
For expansion instructions.
(@)70
XFER
BLOCK TRANSFER
Moves content of several consecutive source words to consecutive destination words.
182
(@)71
BSET
BLOCK SET
Copies content of one word or constant to several consecutive words.
181
(@)72
ROOT
SQUARE ROOT
Computes square root of eight-digit BCD value and outputs truncated four-digit integer result to specified result word.
241
(@)73
XCHG
DATA EXCHANGE
Exchanges contents of two different words.
183
(@)74
SLD
ONE DIGIT SHIFT LEFT
Left shifts data between starting and ending words by one digit (four bits).
177
(@)75
SRD
ONE DIGIT SHIFT RIGHT
Right shifts data between starting and ending words by one digit (four bits).
177
(@)76
MLPX
4-TO-16/8-TO-256 DECODER
Converts up to four hexadecimal digits in source word into decimal values from 0 to 15 and turns ON, in result word(s), bit(s) whose position corresponds to converted value. Can also convert up to eight hexadecimal digits and turn ON corresponding bits in result words R to R+15.
209
(@)77
DMPX
16-TO-4/256-TO-8 ENCODER
Determines position of highest ON bit in source word(s) and writes the ON bit’s position (0 to F) to digit(s) in R. Can also determine the position of the highest ON bit in one or two groups of 16 words (S to S+15, S+16 to S+31) and writes the ON bit’s position (00 to FF) to byte(s) in R.
212
(@)78
SDEC
7-SEGMENT DECODER
Converts hexadecimal values from source word to data for seven-segment display.
215
(@)79
FDIV
FLOATING POINT DIVIDE
Divides one floating point value (Dd+1, Dd) by another (Dr+1, Dr) and outputs the result to R+1 and R.
238
(@)80
DIST
SINGLE WORD DISTRIBUTE
Moves one word of source data to destination word whose address is given by destination base word plus offset.
183
(@)81
COLL
DATA COLLECT
Extracts data from source word and writes it to destination word.
185
(@)82
MOVB
MOVE BIT
Transfers designated bit of source word or constant to des- 187 ignated bit of destination word.
(@)83
MOVD
MOVE DIGIT
Moves hexadecimal content of specified four-bit source digit(s) to specified destination digit(s) for up to four digits.
(@)84
SFTR
REVERSIBLE SHIFT REGISTER
Shifts data in specified word or series of words to either left 173 or right.
(@)85
TCMP
TABLE COMPARE
Compares four-digit hexadecimal value with values in table consisting of 16 words.
188
199
523
Page 542
Appendix B
Programming Instructions Code
Mnemonic
Name
(@)86
ASC
ASCII CONVERT
87 to 89
For expansion instructions.
(@)90
SEND
NETWORK SEND
(@)91
SBS
92
SBN
93
RET
SUBROUTINE ENTRY SUBROUTINE DEFINE RETURN
(@)94
WDT
(@)97
IORF
WATCHDOG TIMER REFRESH I/O REFRESH
(@)98
RECV
NETWORK RECEIVE
(@)99
MCRO
MACRO
Function
Page
Converts hexadecimal values from the source word to eight-bit ASCII code starting at leftmost or rightmost half of starting destination word.
218
Used for communications with other PCs linked through the SYSMAC NET Link System or SYSMAC LINK System. Calls and executes subroutine N.
322
Marks start of subroutine N.
286
Marks the end of a subroutine and returns control to main program. Increases the watchdog timer PV by 0 to 6300 ms.
286
Refreshes all I/O words between the start and end words.
310
Used for communications with other PCs linked through the SYSMAC NET Link System or SYSMAC LINK System. Calls and executes a subroutine replacing I/O words.
327
285
310
287
Expansion Instructions The following table shows the instructions that can be treated as expansion instructions. The default function codes are given for instructions that have codes assigned by default. Code
Mnemonic
Name
Function
17
(@)ASFT
ASYNCHRONOUS SHIFT REGISTER
Creates a shift register that exchanges the contents of adjacent words when one of the words is zero and the other is not.
178
18
(@)SCAN
CYCLE TIME
Sets the minimum cycle time (0 to 999.0 s).
305
19
(@)MCMP
MULTI-WORD COMPARE
192
47
(@)LMSG
48
(@)TERM
32-CHARACTER MESSAGE TERMINAL MODE
60
CMPL
DOUBLE COMPARE
Compares a block of 16 consecutive words to another block of 16 consecutive words. Outputs a 32-character message to the Programming Console. Switches the Programming Console to TERMINAL mode for the normal keyboard mapping operation. Compares two eight-digit hexadecimal values.
61
(@)MPRF (@)XFRB
63
(@)LINE
COLUMN TO LINE
64
(@)COLM
LINE TO COLUMN
65
(@)SEC
HOURS TO SECONDS
Refreshes I/O words allocated to Group-2 High-density I/O Units. Copies the status of up to 255 specified source bits to the specified destination bits. Copies a bit column from 16 consecutive words to the specified word. Copies the 16 bits from the specified word to a bit column of 16 consecutive words. Converts hour and minute data to second data.
311
62
GROUP-2 HIGH-DENSITY I/O REFRESH TRANSFER BITS
66
(@)HMS
SECONDS TO HOURS
Converts second data to hour and minute data.
208
67
(@)BCNT
BIT COUNTER
312
68
(@)BCMP
BLOCK COMPARE
69
(@)APR
ARITHMETIC PROCESS
Counts the total number of bits that are ON in the specified block of words. Judges whether the value of a word is within 16 ranges (defined by lower and upper limits). Performs sine, cosine, or linear approximation calculations.
87
TTIM
TOTALIZING TIMER
Creates a totalizing timer.
165
88
ZCP
AREA RANGE COMPARE
Compares a word to a range defined by lower and upper limits and outputs the result to the GR, EQ, and LE flags.
200
89
(@)INT
INTERRUPT CONTROL
Performs interrupt control, such as masking and unmasking the interrupt bits for I/O interrupts.
289
524
Page
308 309 196
189 224 225 207
197 263
Page 543
Appendix B
Programming Instructions Code
Mnemonic
Name
---
7SEG
---
(@)ADBL
7-SEGMENT DISPLAY OUTPUT DOUBLE BINARY ADD
---
AVG
AVERAGE VALUE
---
(@)BXF2
---
Function
Page
Converts 4- or 8-digit BCD data to 7-segment display format and then outputs the converted data. Adds two 8-digit binary values (normal or signed data) and outputs the result to R and R+1. Adds the specified number of hexadecimal words and computes the mean value. Rounds off to 4 digits past the decimal point.
340
EM BANK TRANSFER
Moves content of several consecutive source words to consecutive destination words. Words in the current EM bank can be specified for the source or destination.
191
CMCR
PCMCIA CARD MACRO
Performs macros to write files, read files, compare files to memory, search files, and other operations for PCMCIA Card Interface Units.
357
---
CPS CPSL
---
(@)DBS
---
(@)DBSL
---
DSW
DOUBLE SIGNED BINARY DIVIDE DIGITAL SWITCH INPUT
Compares two 16-bit (4-digit) signed binary values and outputs the result to the GR, EQ, and LE flags. Compares two 32-bit (8-digit) signed binary values and outputs the result to the GR, EQ, and LE flags. Divides one 16-bit signed binary value by another and outputs the 32-bit signed binary result to R+1 and R. Divides one 32-bit signed binary value by another and outputs the 64-bit signed binary result to R+3 to R. Inputs 4- or 8-digit BCD data from a digital switch.
202
---
SIGNED BINARY COMPARE DOUBLE SIGNED BINARY COMPARE SIGNED BINARY DIVIDE
---
(@)EMBC
SELECT EM BANK
321
---
(@)FCS
FCS CALCULATE
---
FPD
FAILURE POINT DETECT
Changes the current EM bank to the specified bank number. Checks for errors in data transmitted by a Host Link command. Finds errors within an instruction block.
---
(@)HEX
ASCII-TO-HEXADECIMAL
Converts ASCII data to hexadecimal data.
219
---
(@)IEMS
INDIRECT EM ADDRESSING
Changes the destination of indirect DM addressing to DM or the specified EM bank. This instruction can be used to change the current EM bank.
320
---
(@)IORD
SPECIAL I/O UNIT READ
354
---
(@)IOWR
SPECIAL I/O UNIT WRITE
---
(@)MAX
FIND MAXIMUM
---
(@)MBS
---
(@)MBSL
SIGNED BINARY MULTIPLY DOUBLE SIGNED BINARY MULTIPLY
Transfers data from the specified Special I/O Unit’s memory to words in the PC. Transfers data from words in the PC to the specified Special I/O Unit’s memory. Finds the maximum value in specified data area and outputs that value to another word. Multiplies the signed binary content of two words and outputs the 8-digit signed binary result to R+1 and R. Multiplies two 32-bit (8-digit) signed binary values and outputs the 16-digit signed binary result to R+3 through R.
---
(@)MIN
FIND MINIMUM
258
---
MTR
MATRIX INPUT
---
(@)NEG
2’S COMPLEMENT
Finds the minimum value in specified data area and outputs that value to another word. Inputs data from an 8 input point × 8 output point matrix and records that data in D to D+3. Converts the four-digit hexadecimal content of the source word to its 2’s complement and outputs the result to R.
---
(@)NEGL
DOUBLE 2’S COMPLEMENT
Converts the eight-digit hexadecimal content of the source words to its 2’s complement and outputs the result to R and R+1.
227
---
(@)PID
PID CONTROL
PID control is performed according to the operand and PID parameters that are preset. (The only CQM1 model that can use PID(––) is the
266
---
(@)PMCR
PROTOCOL MACRO
Calls and executes the specified communications sequence (protocol) that has been registered in the Communications Board.
339
249 259
203 255 256 343
312 314
355 257 253 254
352 226
525