Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 6 of 60

C200HX/C200HG/C200HE Programmable Controllers Operation Manual, pages 44 to 53

Pages 44 to 53 of 586

The original document is the PDF (3.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200HE-CPU42-E

Page 44

Section 3-2

Data Area Structure

An actual data location within any data area but the TC area is designated by its address. The address designates the bit or word within the area where the desired data is located. The TC area consists of TC numbers, each of which is used for a specific timer or counter defined in the program. Refer to 3-8 TC Area for more details on TC numbers and to 5-14 Timer and Counter Instructions for information on their application. The rest of the data areas (i.e., the IR, SR, HR, DM, AR, and LR areas) consist of words, each of which consists of 16 bits numbered 00 through 15 from right to left. IR words 000 and 001 are shown below with bit numbers. Here, the content of each word is shown as all zeros. Bit 00 is called the rightmost bit; bit 15, the leftmost bit. The term least significant bit is often used for rightmost bit; the term most significant bit, for leftmost bit. These terms are not used in this manual because a single data word is often split into two or more parts, with each part used for different parameters or operands. When this is done, the rightmost bits of a word may actually become the most significant bits, i.e., the leftmost bits in another word,when combined with other bits to form a new word. Bit number

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

IR word 000

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

IR word 001

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

The DM area is accessible by word only; you cannot designate an individual bit within a DM word. Data in the IR, SR, HR, AR, and LR areas is accessible either by word or by bit, depending on the instruction in which the data is being used. To designate one of these areas by word, all that is necessary is the acronym (if required) and the two-, three-, or four-digit word address. To designate an area by bit, the word address is combined with the bit number as a single four- or fivedigit address. The following table show examples of this. The two rightmost digits of a bit designation must indicate a bit between 00 and 15, i.e., the rightmost digit must be 5 or less the next digit to the left, either 0 or 1. The same TC number can be used to designate either the present value (PV) of the timer or counter, or a bit that functions as the Completion Flag for the timer or counter. This is explained in more detail in 3-8 TC Area. Area

Data Structure

Word designation

Bit designation

IR

000

00015 (leftmost bit in word 000)

SR

252

25200 (rightmost bit in word 252)

DM

DM 1250

Not possible

TC

TC 215 (designates PV)

TC 215 (designates completion flag)

LR

LR 12

LR 1200

Word data input as decimal values is stored in binary-coded decimal (BCD); word data entered as hexadecimal is stored in binary form. Each four bits of a word represents one digit, either a hexadecimal or decimal digit, numerically equivalent to the value of the binary bits. One word of data thus contains four digits, which are numbered from right to left. These digit numbers and the corresponding bit numbers for one word are shown below.

Digit number

3

2

1

0

Bit number

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Contents

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

When referring to the entire word, the digit numbered 0 is called the rightmost digit; the one numbered 3, the leftmost digit.

26

Page 45

Section 3-2

Data Area Structure

When inputting data into data areas, it must be input in the proper form for the intended purpose. This is no problem when designating individual bits, which are merely turned ON (equivalent to a binary value of 1) or OFF (a binary value of 0). When inputting word data, however, it is important to input it either as decimal or as hexadecimal, depending on what is called for by the instruction it is to be used for. Section 5 Instruction Set specifies when a particular form of data is required for an instruction. Converting Different Forms of Data

Binary and hexadecimal can be easily converted back and forth because each four bits of a binary number is numerically equivalent to one digit of a hexadecimal number. The binary number 0101111101011111 is converted to hexadecimal by considering each set of four bits in order from the right. Binary 1111 is hexadecimal F; binary 0101 is hexadecimal 5. The hexadecimal equivalent would thus be 5F5F, or 24,415 in decimal (163 x 5 + 162 x 15 + 16 x 5 + 15). Decimal and BCD are easily converted back and forth. In this case, each BCD digit (i.e., each group of four BCD bits) is numerically equivalent of the corresponding decimal digit. The BCD bits 0101011101010111 are converted to decimal by considering each four bits from the right. Binary 0101 is decimal 5; binary 0111 is decimal 7. The decimal equivalent would thus be 5,757. Note that this is not the same numeric value as the hexadecimal equivalent of 0101011101010111, which would be 5,757 hexadecimal, or 22,359 in decimal (163 x 5 + 162 x 7 + 16 x 5 + 7). Because the numeric equivalent of each four BCD binary bits must be numerically equivalent to a decimal value, any four bit combination numerically greater than 9 cannot be used, e.g., 1011 is not allowed because it is numerically equivalent to 11, which cannot be expressed as a single digit in decimal notation. The binary bits 1011 are of course allowed in hexadecimal are a equivalent to the hexadecimal digit C. There are instructions provided to convert data either direction between BCD and hexadecimal. Refer to 5-18 Data Conversion for details. Tables of binary equivalents to hexadecimal and BCD digits are provided in the appendices for reference.

Decimal Points

Decimal points are used in timers only. The least significant digit represents tenths of a second. All arithmetic instructions operate on integers only.

Signed and Unsigned Binary Data This section explains signed and unsigned binary data formats. Many instructions can use either signed or unsigned data and a few (CPS(––), CPSL(––), DBS(––), DBSL(––), MBS(––), and MBSL(––)) use signed data exclusively. Unsigned binary

Unsigned binary is the standard format used in OMRON PCs. Data in this manual are unsigned unless otherwise stated. Unsigned binary values are always positive and range from 0 ($0000) to 65,535 ($FFFF). Eight-digit values range from 0 ($0000 0000) to 4,294,967,295 ($FFFF FFFF).

163

Digit value

162

161

160

Bit number

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Contents

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

27

Page 46

Section 3-2

Data Area Structure Signed Binary

Signed binary data can have either a positive and negative value. The sign is indicated by the status of bit 15. If bit 15 is OFF, the number is positive and if bit 15 is ON, the number is negative. Positive signed binary values range from 0 ($0000) to 32,767 ($7FFF), and negative signed binary values range from –32,768 ($8000) to –1 ($FFFF).

Sign indicator 163

Digit value

162

161

160

Bit number

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Contents

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Eight-digit positive values range from 0 ($0000 0000) to 2,147,483,647 ($7FFF FFFF), and eight-digit negative values range from –2,147,483,648 ($8000 0000) to –1 ($FFFF FFFF). The following table shows the corresponding decimal, 16-bit hexadecimal, and 32-bit hexadecimal values. Decimal 2147483647 2147483646 . . . 32768 32767 32766 . . . 2 1 0 –1 –2 . . . –32767 –32768 –32769 . . . –2147483647 –2147483648

Converting Decimal to Signed Binary

28

16-bit Hex ----. . . --7FFF 7FFE . . . 0002 0001 0000 FFFF FFFE . . . 8001 8000 --. . . -----

32-bit Hex 7FFFFFFF 7FFFFFFE . . . 00008000 00007FFF 00007FFE . . . 00000002 00000001 00000000 FFFFFFFF FFFFFFFE . . . FFFF8001 FFFF8000 FFFF7FFF . . . 80000001 80000000

Positive signed binary data is identical to unsigned binary data (up to 32,767) and can be converted using BIN(100). The following procedure converts negative decimal values between –32,768 and –1 to signed binary. In this example –12345 is converted to CFC7.

Page 47

Section 3-3

IR (Internal Relay) Area

1. First take the absolute value (12345) and convert to unsigned binary: Bit number

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Contents

0

0

1

1

0

0

0

0

0

0

1

1

1

0

0

1

2. Next take the complement: Bit number

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Contents

1

1

0

0

1

1

1

1

1

1

0

0

0

1

1

0

3. Finally add one: Bit number

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Contents

1

1

0

0

1

1

1

1

1

1

0

0

0

1

1

1

Reverse the procedure to convert negative signed binary data to decimal.

3-3

IR (Internal Relay) Area The IR area is used both as data to control I/O points, and as work bits to manipulate and store data internally. It is accessible both by bit and by word. In the C200HX/HG/HE PC, the IR area is comprised of words IR 000 to IR 235 (IR area 1) and IR 300 to IR 511 (IR area 2). Basic instructions have somewhat longer execution times when they access IR area 2 rather than IR area 1. Words in the IR area that are used to control I/O points are called I/O words. Bits in I/O words are called I/O bits. Bits in the IR area which are not assigned as I/O bits can be used as work bits. IR area work bits are reset when power is interrupted or PC operation is stopped. Area IR Area 1 I/O Area 1 Group-2 High-density I/O Unit Area 1 and B7A Interface Unit Area SYSMAC BUS and DeviceNet Output Area Special I/O Unit Area 1 Optical I/O Unit and I/O Terminal Area Work Area IR Area 2 I/O Area 2 Work Area Group-2 High-density I/O Unit Area 2 Work Area DeviceNet Input Area Special I/O Unit Area 2 Work Area

Range IR 000 to IR 029 IR 030 to IR 049 IR 050 to IR 099 IR 100 to IR 199 IR 200 to IR 231 IR 232 to IR 235 IR 300 to IR 309 IR 310 to IR 329 IR 330 to IR 341 IR 342 to IR 349 IR 350 to IR 399 IR 400 to IR 459 IR 460 to IR 511

I/O Words

If a Unit brings inputs into the PC, the bit assigned to it is an input bit; if the Unit sends an output from the PC, the bit is an output bit. To turn ON an output, the output bit assigned to it must be turned ON. When an input turns ON, the input bit assigned to it also turns ON. These facts can be used in the program to access input status and control output status through I/O bits.

Input Bit Usage

Input bits can be used to directly input external signals to the PC and can be used in any order in programming. Each input bit can also be used in as many instructions as required to achieve effective and proper control. They cannot be used in

29

Page 48

Section 3-3

IR (Internal Relay) Area instructions that control bit status, e.g., the OUTPUT, DIFFERENTIATION UP, and KEEP instructions. Output Bit Usage

Output bits are used to output program execution results and can be used in any order in programming. Because outputs are refreshed only once during each cycle (i.e., once each time the program is executed), any output bit can be used in only one instruction that controls its status, including OUT, KEEP(11), DIFU(13), DIFD(14) and SFT(10). If an output bit is used in more than one such instruction, only the status determined by the last instruction will actually be output from the PC. See 5-15-1 Shift Register – SFT(10) for an example that uses an output bit in two ‘bit-control’ instructions.

Word Allocation for Racks

I/O words are allocated to the CPU Rack and Expansion I/O Racks by slot position. One I/O word is allocated to each slot, as shown in the following table. Since each slot is allocated only one I/O word, a 3-slot rack uses only the first 3 words, a 5-slot rack uses only the first 5 words, and an 8-slot rack uses only the first 8 words. Words that are allocated to unused or nonexistent slots are available as work words. Right side of a 10-slot rack →

← Left side of rack Rack

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Slot 6

Slot 7

Slot 8

Slot 9

Slot 10

CPU

IR 000

IR 001

IR 002

IR 003

IR 004

IR 005

IR 006

IR 007

IR 008

IR 009

1st Expansion

IR 010

IR 011

IR 012

IR 013

IR 014

IR 015

IR 016

IR 017

IR 018

IR 019

2nd Expansion

IR 020

IR 021

IR 022

IR 023

IR 024

IR 025

IR 026

IR 027

IR 028

IR 029

3rd Expansion

IR 300

IR 301

IR 302

IR 303

IR 304

IR 305

IR 306

IR 307

IR 308

IR 309

Unused Words

Any words allocated to a Unit that does not use them can be used in programming as work words and bits. Units that do not used the words assigned to the slot they are mounted to include Link Units (e.g., Host Link Units, PC Link Units, SYSMAC NET Link Units, etc.), Remote I/O Master Units, Special I/O Units, Group-2 High-density I/O Units, B7A Interface Units, and Auxiliary Power Supply Units.

Allocation for Special I/O Units and Slave Racks

In most C200HX/HG/HE PCs, up to sixteen Special I/O Units may be mounted in any slot of the CPU Rack or Expansion I/O Racks. (A limited number of Special I/O Units can be installed in Remote I/O Slave Racks, too.) Each Special I/O Unit is allocated ten words based on its unit number (0 to F). Up to ten Special I/O Units may be mounted in the and PCs. Each Unit is allocated ten words based on its unit number (0 to 9). Unit number 0 1 2 3 4 5 6 7 8 9

30

I/O words IR 100 to IR 109 IR 110 to IR 119 IR 120 to IR 129 IR 130 to IR 139 IR 140 to IR 149 IR 150 to IR 159 IR 160 to IR 169 IR 170 to IR 179 IR 180 to IR 189 IR 190 to IR 199

PC Restrictions None

Page 49

Section 3-3

IR (Internal Relay) Area Unit number A B C D E F

I/O words IR 400 to IR 409 IR 410 to IR 419 IR 420 to IR 429 IR 430 to IR 439 IR 440 to IR 449 IR 450 to IR 459

PC Restrictions Not available in and PCs.

Note I/O words that aren’t allocated to Special I/O Units can be used as work words. Up to five Slave Racks may be used, whether one or two Masters are used. IR area words are allocated to Slave Racks by the unit number on the Unit, as shown in the following tables. Unit number

I/O words

0

IR 050 to IR 059

1

IR 060 to IR 069

2

IR 070 to IR 079

3

IR 080 to IR 089

4

IR 090 to IR 099

The C500-RT001/002-(P)V1 Remote I/O Slave Rack may be used, but it requires 20 I/O words, not 10, and therefore occupies the I/O words allocated to 2 C200H Slave Racks, both the words allocated to the unit number set on the rack and the words allocated to the following unit number. When using a C200HX/ HG/HE CPU Unit, do not set the unit number on a C500 Slave Rack to 4, because there is no unit number 5. With the C500 Slave Rack, I/O words are allocated only to installed Units, from left to right, and not to slots as in the C200HX/ HG/HE Racks. Allocation for Optical I/O Units and I/O Terminals

I/O words between IR 200 and IR 231 are allocated to Optical I/O Units and I/O Terminals by unit number. The I/O word allocated to each Unit is IR 200+n, where n is the unit number set on the Unit.

Allocation for Remote I/O Master and Link Units

Remote Master I/O Units and Host Link Units do not use I/O words, and the PC Link Units use the LR area, so words allocated to the slots in which these Units are mounted are available as work words.

Bit Allocation for I/O Units

An I/O Unit may require anywhere from 8 to 16 bits, depending on the model. With most I/O Units, any bits not used for input or output are available as work bits. Transistor Output Units C200H-OD213 and C200H-OD411, as well as Triac Output Unit C200H-OA221, however, uses bit 08 for the Blown Fuse Flag. Transistor Output Unit C200H-OD214 uses bits 08 to 11 for the Alarm Flag. Bits 08 to 15 of any word allocated to these Units, therefore, cannot be used as work bits.

Bit Allocation for Interrupt Input Units

The Interrupt Input Unit uses the 8 bits of the first I/O word allocated to its slot in the CPU Rack. (An Interrupt Input Unit will operate as a normal Input Unit when installed in an Expansion I/O Rack.) The other 24 bits allocated to its slot in the CPU Rack can be used as work bits.

31

Page 50

IR (Internal Relay) Area

Section 3-3

Allocation for Group-2 High-density I/O Units and B7 Interface Units

Group-2 High-density I/O Units and B7A Interface Units are allocated words between IR 030 and IR 049 according to I/O number settings made on them and do not use the words allocated to the slots in which they are mounted. For 32-point Units, each Unit is allocated two words; for 64-point Units, each Unit is allocated four words. The words allocated for each I/O number are in the following tables. Any words or parts of words not used for I/O can be used as work words or bits in programming. 32-point Units I/O number

See note.

64-point Units

Words

I/O number

Words

0

IR 30 to IR 31

0

IR 30 to IR 33

1

IR 32 to IR 33

1

IR 32 to IR 35

2

IR 34 to IR 35

2

IR 34 to IR 37

3

IR 36 to IR 37

3

IR 36 to IR 39

4

IR 38 to IR 39

4

IR 38 to IR 41

5

IR 40 to IR 41

5

IR 40 to IR 43

6

IR 42 to IR 43

6

IR 42 to IR 45

7

IR 44 to IR 45

7

IR 44 to IR 47

8

IR 46 to IR 47

8

IR 46 to IR 49

9

IR 48 to IR 49

9

Cannot be used.

A

IR 330 to IR 331

A

IR 330 to IR 333

B

IR 332 to IR 333

B

IR 332 to IR 335

C

IR 334 to IR 335

C

IR 334 to IR 337

D

IR 336 to IR 337

D

IR 336 to IR 339

E

IR 338 to IR 339

E

IR 338 to IR 341

F

IR 340 to IR 341

F

Cannot be used.

Note Unit numbers A to F cannot be set when using the following CPU Units: C200HE-CPU32(-Z), C200HE-CPU42(-Z), C200HG-CPU33(-Z), C200HGCPU43(-Z), C200HX-CPU34(-Z), and C200HX-CPU44(-Z). Set unit number 0 to 9 when using these CPU Units. When setting I/O numbers on the High-density I/O Units and B7A Interface Units, be sure that the settings will not cause the same words to be allocated to more than one Unit. For example, if I/O number 0 is allocated to a 64-point Unit, I/O number 1 cannot be used for any Unit in the system. Group-2 High-density I/O Units and B7A Interface Units are not considered Special I/O Units and do not affect the limit to the number of Special I/O Units allowed in the System, regardless of the number used. The words allocated to Group-2 High-density I/O Units correspond to the connectors on the Units as shown in the following table. Unit 32-point Units 64-point Units

Note

Word m m+1 m m+1 m+2 m+3

Connector/row Row A Row B CN1, row A CN1, row B CN2, row A CN2, row B

1. Group-2 High-density I/O Units and B7A Interface Units cannot be mounted to Slave Racks. 2. Refer to the Installation Guide for limitations on the number of Special I/O Units that can be mounted to Slave Racks.

32

Page 51

Section 3-4

SR (Special Relay) Area

3-4

SR (Special Relay) Area The SR area contains flags and control bits used for monitoring PC operation, accessing clock pulses, and signalling errors. SR area word addresses range from 236 through 299; bit addresses, from 23600 through 29915. The SR areas is divided into two sections. The first section ends at SR 255 and the second section begins at SR 256. When an SR area word is used as an operand in an instruction, the operand mustn’t cross over this boundary. Basic instructions that access bits in the SR Area 2 have longer execution times. Area

Range

SR Area 1

SR 23600 to SR 25507

SR Area 2

SR 25600 to SR 29915

The following table lists the functions of SR area flags and control bits. Most of these bits are described in more detail following the table. Descriptions are in order by bit number except that Link System bits are grouped together. Unless otherwise stated, flags are OFF until the specified condition arises, when they are turned ON. Restart bits are usually OFF, but when the user turns one ON then OFF, the specified Link Unit will be restarted. Other control bits are OFF until set by the user. Not all SR words and bits are writeable by the user. Be sure to check the function of a bit or word before attempting to use it in programming. Word(s)

Bit(s)

Function

236

00 to 07 08 to 15

Node loop status output area for operating level 0 of SYSMAC NET Link System Node loop status output area for operating level 1 of SYSMAC NET Link System

237

00 to 07

Completion code output area for operating level 0 following execution of SEND(90)/RECV(98) for SYSMAC LINK/SYSMAC NET Link System or CMCR(––) for a PC Card

08 to 15

Completion code output area for operating level 1 following execution of SEND(90)/RECV(98) for SYSMAC LINK/SYSMAC NET Link System or CMCR(––) for a PC Card

238 and 241

00 to 15

Data link status output area for operating level 0 of SYSMAC LINK or SYSMAC NET Link System

242 and 245

00 to 15

Data link status output area for operating level 1 of SYSMAC LINK or SYSMAC NET Link System

246

00 to 15

Not used

247 and 248

00 to 07 08 to 15

PC Link Unit Run Flags for Units 16 through 31 or data link status for operating level 1 PC Link Unit Error Flags for Units 16 through 31 or data link status for operating level 1

249 and 250

00 to 07 08 to 15

PC Link Unit Run Flags for Units 00 through 15 or data link status for operating level 0 PC Link Unit Error Flags for Units 00 through 15 or data link status for operating level 0

251

00 01 to 02 03 04 to 06

Remote I/O Error Read Bit Not used Remote I/O Error Flag Slave Rack number and unit number of Remote I/O Unit, Optical I/O Unit, or I/O Terminal with error Not used Master’s unit number and word allocated to Remote I/O Unit, Optical I/O Unit, or I/O Terminal with error (Hexadecimal)

Writeable

07 08 to 15

33

Page 52

SR (Special Relay) Area Word(s) 252

Bit(s) 00 01 02 03 04

253

254

34

05 06 07 08 09 10 11 12 13 14 15 00 to 07 08 09 10 11 12 13 14 15 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15

Section 3-4

Function SEND(90)/RECV(98) Error Flag for operating level 0 of SYSMAC LINK or SYSMAC NET Link System or CMCR(––) Error Flag for PC Card SEND(90)/RECV(98) Enable Flag for operating level 0 of SYSMAC LINK or SYSMAC NET Link System or CMCR(––) Enable Flag for PC Card Operating Level 0 Data Link Operating Flag SEND(90)/RECV(98) Error Flag for operating level 1 of SYSMAC LINK or SYSMAC NET Link System or CMCR(––) Error Flag for PC Card SEND(90)/RECV(98) Enable Flag for operating level 1 of SYSMAC LINK or SYSMAC NET Link System or CMCR(––) Enable Flag for PC Card Operating Level 1 Data Link Operating Flag Rack-mounting Host Link Unit Level 1 Communications Error Flag Rack-mounting Host Link Unit Level 1 Restart Bit Peripheral Port Restart Bit RS-232C Port Restart Bit PC Setup Clear Bit Forced Status Hold Bit Data Retention Control Bit Rack-mounting Host Link Unit Level 0 Restart Bit Not used. Output OFF Bit FAL number output area (see error information provided elsewhere) Low Battery Flag Cycle Time Error Flag I/O Verification Error Flag Rack-mounting Host Link Unit Level 0 Communications Error Flag Remote I/O Error Flag Always ON Flag Always OFF Flag First Cycle Flag 1-minute clock pulse bit 0.02-second clock pulse bit Negative (N) Flag MTR Execution Flag Overflow Flag (for signed binary calculations) Underflow Flag (for signed binary calculations) Differential Monitor End Flag Step Flag HKY Execution Flag 7SEG Execution Flag DSW Execution Flag Interrupt Input Unit Error Flag Reserved by system (not accessible by user) Interrupt Program Error Flag Group-2 Error Flag Special Unit Error Flag (includes Special I/O, PC Link, Host Link, Remote I/O Master Units)

Page 53

Section 3-4

SR (Special Relay) Area Word(s) 255

256 to 261 262 263

Bit(s) 00 01 02 03 04 05 06 07 08 to 15 00 to 15 00 to 15 00 to 15

264

00 to 03

Function 0.1-second clock pulse bit 0.2-second clock pulse bit 1.0-second clock pulse bit Instruction Execution Error (ER) Flag These flags are turned OFF when the END(01) instruction is executed, so their status can’t be Carry (CY) Flag monitored from a Programming Console. Greater Than (GR) Flag Refer to Appendix C for a table showing which Equals (EQ) Flag instructions affect these flags. Less Than (LE) Flag Reserved by system (used for TR bits) Reserved by system Longest interrupt subroutine (action) execution time (0.1-ms units) Number of interrupt subroutine (action) with longest execution time. (8000 to 8255) (Bit 15 is the Interrupt Flag) RS-232C Port Error Code 0: No error 1: Parity error 2: Framing error

3: Overrun error

4: FCS error 04 05 06 07 08 to 11

RS-232C Port Communications Error RS-232C Port Send Ready Flag RS-232C Port Reception Completed Flag RS-232C Port Reception Overflow Flag Peripheral Port Error Code in General I/O Mode 0: No error 1: Parity error 2: Framing error

265

266 267

268 269

12 13 14 15 00 to 15

00 to 15 00 to 04 05 06 to 12 13 14 to 15 00 to 15 00 to 07 08 to 10 11 to 13 14 15

3: Overrun error

Peripheral Port Communications Error in General I/O Mode Peripheral Port Send Ready Flag in in General I/O Mode Peripheral Port Reception Completed Flag in General I/O Mode Peripheral Port Reception Overflow Flag in General I/O Mode NT Link (1:N) Mode Bits 00 to 07: Communicating with PT Flags for Units 0 to 7 Bits 08 to 15: Registering PT Priority Flags for Units 0 to 7 RS-232C Mode Bits 00 to 15: RS-232C Port Reception Counter Peripheral Reception Counter in RS-232C Mode Reserved by system (not accessible by user) Host Link Level 0 Send Ready Flag Reserved by system (not accessible by user) Host Link Level 1 Send Ready Flag Reserved by system (not accessible by user) Communications Board Error Information Memory Cassette Contents 00: Nothing; 01: UM; 02: IOM; 03: HIS Memory Cassette Capacity 0: 0 KW (no cassette); 2: 4 or 8 KW; 3: 16 KW; 4: 32 KW Reserved by system (not accessible by user) EEPROM Memory Cassette Protected or EPROM Memory Cassette Mounted Flag Memory Cassette Flag

35