Page 142
Inputting, Modifying, and Checking the Program
Example: Instruction
Searches
CLR
Section 7-5
135
Page 143
Inputting, Modifying, and Checking the Program
Section 7–5
Bit Search
7–5–6
Inserting and Deleting Instructions In PROGRAM mode, any instruction that is currently displayed can be deleted or another instruction can be inserted before it. These are not possible in RUN or MONITOR modes. To insert an instruction, display the instruction before which you want the new instruction to be placed, input the instruction word in the same way as when inputting a program initially, and then press INS and the down key. If other words are required for the instruction, input these in the same way as when inputting a program initially. To delete an instruction, display the instruction word of the instruction to be deleted and then press DEL and the up key. All the words for the designated instruction will be deleted. Note Be careful not to inadvertently delete instructions; there is no way to recover them without reinputting them completely.
Key Sequences
When an instruction is inserted or deleted, all addresses in Program Memory following the operation are adjusted automatically so that there are no blank addresses and no unaddressed instructions. Example
136
The following mnemonic code shows the changes that are achieved in a program through the key sequences and displays shown below.
Page 144
Section 7–5
Inputting, Modifying, and Checking the Program Before Insertion Address
Instruction
0000
LD
0100
0001
AND
0101
0002
LD
0201
0003
AND NOT
0102
0004
OR LD
0005
AND
0103
0006
AND NOT
0104
0007
OUT
0201
0008
END(01)
After Insertion Address
Instruction
0000
LD
0001
Data
–
–
After Deletion Data
Address
Instruction
Data
0100
0000
LD
0100
AND
0101
0001
AND NOT
0101
0002
LD
0201
0002
LD
0201
0003
AND NOT
0102
0003
AND NOT
0102
0004
OR LD
–
0004
OR LD
0005
AND
0103
0005
AND
0103
0006
AND
0105
0006
AND
0105
0007
AND NOT
0104
0007
AND NOT
0104
0008
OUT
0201
0008
OUT
0201
0009
END(01)
–
–
The following key inputs and displays show the procedure for achieving the program changes shown above.
137
Page 145
Section 7–5
Inputting, Modifying, and Checking the Program
Find the address prior to the insertion point
Insert the instruction
138
Page 146
Section 7–5
Inputting, Modifying, and Checking the Program
Find the instruction that requires deletion.
Confirm that this is the instruction to be deleted.
139
Page 147
Section 7–8
Program Backup and Restore Operations
7–6
Program Backup and Restore Operations Program Memory (UM) can be backed-up on a standard commercially available cassette tape recorder. Any kind of dependable magnetic tape of adequate length will suffice. To save a 16K-word program, the tape must be 30 minutes long. Always allow about 5 seconds of blank tape leader before the taped data begins. Store only one program on a single side of a tape; there is no way to identify separate programs stored on the same side of the tape. If a program is longer than will fit on one side, it can be split onto two sides. Be sure to label the contents of all cassette tapes clearly. Use patch cords to connect the cassette recorder earphone (or LINE-OUT) jack to the Programming Console EAR jack and the cassette recorder microphone (or LINE-IN) jack to the Programming Console MIC jack. Set the cassette recorder volume and tone controls to maximum levels. The PC must be in PROGRAM mode for all cassette tape operations. While the operation is in progress, the cursor will blink and the block count will be incremented on the display. Cassette tape operations may be halted at any time by pressing the CLR key.
Error Messages
7–6–1
The following error messages may appear during cassette tape operations.
Message
Meaning and appropriate response
0000 ERR ******* FILE NO.********
File number on cassette and designated file number are not the same. Repeat the operation using the correct file number.
**** MT VER ERR
Cassette tape contents differs from that in the PC. Check content of tape and/or the PC.
**** MT ERR
Cassette tape is faulty. Replace it with another.
Saving Program Memory Data This operation is used to copy the content of Program Memory to a cassette tape. The procedure is as follows:
1, 2, 3... 1. 2. 3. 4.
Press EXT. Input a file number for the data that is to be saved. Start cassette tape recording. Within 5 seconds, press the SHIFT and REC/RESET keys.
Program saving continues until END(01) or the final address is reached. Cancel by pressing the CLR key.
Key Sequence
140
Page 148
Section 7–8
Program Backup and Restore Operations Example
Within 5 seconds... Blinking
(Recording in progress) Blinking
When it comes to END Blinking
Stop recording with CLR
Saved up to the final address)
7–6–2
Restoring or Comparing Program Memory Data This operation is used to restore Program Memory data from a cassette tape or to compare Program Memory data with the contents on a cassette tape. The procedure is as follows:
1, 2, 3... 1. 2. 3. 4.
Press EXT. Specify the number of the file to be restored or compared. Start playing the cassette tape. Within 5 seconds, press SHIFT and PLAY/SET to restore data or VER to compare data.
Program restoration or comparison continues until the final address or END(01) is reached or until the tape is finished. Cancel by pressing the CLR key. To restore or compare program data recorded on two sides of a tape or on two or more tapes, begin restoring or comparing from the lowest address.
141
Page 149
Program Backup and Restore Operations Section 7-8
Key Sequence
VER
No more than 5 seconds.
Example
Start the tape recorder playback. Continue within 5 seconds.
Blinking Blinking
SET
(Restoring in progress.) (Comparison in progress.)
(When it comes to END.)
(Restored up to END.) Stop comparison with CLR.
CLR
Stop restoring with CLR. (Compared to end of tape.)
CLR
142
Page 150
Debugging
7–7
Section 7–6
Debugging After inputting a program and correcting it for syntax errors, it must be executed and all execution errors must be eliminated. Execution errors include an excessively long scan time, errors in settings for various Units in the PC, and inappropriate control actions, i.e., the program not doing what it is designed to do. When necessary, the program can first be executed isolated from the actual control system and wired to artificial inputs and outputs to check for certain types of errors before actual trial operation with the controlled system.
Displaying and Clearing Error Messages
When an error occurs during program execution, it can be displayed for identification by pressing CLR, FUN, and then MONTR. If an error message is displayed, the MONTR key can be press to access any other error messages that are stored by the system in memory. If MONTR is pressed in PROGRAM mode, the error message will be cleared from memory; be sure to write down the error message when required before pressing MONTR. OK will be displayed when the last message has been cleared. If a beeper sounds and the error cannot be cleared by pressing MONTR, the cause of the error still exists and must be eliminated before the error message can be cleared. If this happens, take the appropriate corrective action to eliminate the error. Refer to Section 8 Troubleshooting for all details on all error messages. The sequence in which error messages are displayed depends on the priority levels of the errors. The messages for fatal errors (i.e., those that stop PC operation) are displayed before non-fatal ones. Although error messages can be displayed in any mode, they can be cleared only in PROGRAM mode. There is no way to restart the PC following a fatal error without first clearing the error message in PROGRAM mode.
Key Sequence
Example
The following displays show some of the messages that may appear. Refer to Section 8 Troubleshooting for an inclusive list of error messages, meanings, and appropriate responses.
143
Page 151
Section 7–7
Monitoring Operation and Modifying Data
Fatal errors
Non-fatal errors
All errors have been cleared
7–8
Monitoring Operation and Modifying Data The simplest form of operation monitoring is to display the address whose operand bit status is to be monitored using the Program Read or one of the search operations. As long as the operation is performed in RUN or MONITOR mode, the status of any bit displayed will be indicated. This section provides other procedures for monitoring data as well as procedures for modifying data that already exists in a data area. Data that can be modified includes the PV (present value) and SV (set value) for any timer or counter. All monitor operations in this section can be performed in RUN, MONITOR, or PROGRAM mode and can be cancelled by pressing the CLR key. All data modification operations except for timer/counter SV changes are performed after first performing one of the monitor operations. Data modification is possible in either MONITOR or PROGRAM mode, but cannot be performed in RUN mode.
144