Page 54

Appendix A Standard Models Analog Output Unit PC C200H/C200HS

Model C200H-DA001

Analog Input Unit PC C200H/C200HS

Model C200H-AD001

47

Page 55

Appendix B Specifications C200H-AD001 Analog Input Unit General Specifications All general specifications of the C200H-AD001 Analog Input Unit conform to those of the C Series.

Performance Specifications Item

Specifications

Number of analog inputs

4 max.

Input signal range (note 1)

Voltage input

1 to 5 V 0 to 10 V

Max. input signal (note 2) Input impedance

Current input

4 to 20 mA

Voltage input

-15 V

Current input

-30 mA

Voltage input

1 MΩ min.

Current input

250 Ω (rated value)

Resolution

1/4000 max. (full scale)

Converted data

12-bit binary (0000 to 0FA0)

Accuracy (note 3)

25°C

-0.5% (full scale, including linearity error)

0° to 55°C

-1.0% (full scale, including linearity error)

Conversion time (note 4)

2.5 ms max./point

Isolation

Between input terminals and PC: photocoupler Between input terminals: none

External connections

19-pin terminal block (removable)

Power consumption

550 mA max. at 5 VDC

Dimensions

34.5 x 130 x 128 (W x H x D) mm (see last page of this appendix)

Weight

450 g max.

Note 1. All points on the same Unit must use the same input range except for the 1 to 5-V and 4 to 20-mA ranges, which can be specified by point. 2. Operation in ranges beyond the maximum input signals will damage the Unit. Operate within the ranges listed above. 3. The accuracy is given for full scale (4,000). For example, an accuracy of -5% means a maximum error of 20 (BCD). 4. This is the time it takes for a full range input signal to be converted and to be stored in the memory of the Unit. It takes at least one scan before the converted data is read by the CPU.

49

Page 56

Appendix B

Specifications

Input Specifications Converted output data (Top: Binary Parentheses: BCD) 0 to 10 V 1 to 5 v/4 to 20 mA

0V

1V (4 mA)

5V (20 mA)

10 V Input signal

Note 1. All points on the same Unit must use the same input range except for the 1 to 5-V and 4 to 20-mA ranges, which can be specified by point. Refer to 2-1-2 Switch Settings for setting methods. 2. The maximum or minimum output value will be maintained if the input signals goes beyond the maximum (10 V, 5V, or 20 mA) or minimum (0 V, 1V, or 4 mA).

50

Page 57

Appendix B

Specifications

C200H-DA001 Analog Output Unit All general specifications of the C200H-DA001 Analog Output Unit conform to those of the C Series. Item

Specifications

Number of analog outputs

2

Output signal range (note 1)

Voltage outputs

1 to 5 V 0 to 10 V

Current outputs

4 to 20 mA

Max. output impedance

Voltage output: 0.5 Ω

Max. output current

Voltage output: 15 mA

Max. load resistance

Current output: 400 Ω

Resolution

1/4095 max. (full scale)

Set data

12-bit binary (0000 to 0FFF)

Accuracy (note 2)

25°C

±0.5% max. (full scale, including linearity error)

0° to 55°C

±1.0% max. (full scale, including linearity error)

Conversion time (note 3)

2.5 ms max./point

Isolation

Between output terminals and PC: photocoupler Between output terminals: none

External connections

19-pin terminal block (removable)

Power consumption

650 mA max. at 5 VDC

Dimensions

34.5 x 130 x 128 (W x H x D) mm (see last page of this appendix)

Weight

450 g max.

Note 1. All points on the same Unit must use the same output range except for the 1 to 5-V and 4 to 20-mA ranges, which can be specified by point. 2. The accuracy is given for full scale (4,095). For example, an accuracy of ±5% means a maximum error of 20 (BCD). 3. This is the time from after the data has been written to the Unit until an analog output appears. The output data will not be correct if output data is rewritten faster than it can be output.

51

Page 58

Appendix B

Specifications

Output Specifications Output signal 10 V 0 to 10 V 1 to 5 V/4 to 20 mA

5V (20 mA)

1V (4 mA) 0V

Digital input data (Top: Binary Parentheses: BCD)

Note All points on the same Unit must use the same output range except for the 1 to 5-V and 4 to 20-mA ranges, which can be specified by point. Refer to 3-1-2 Switch Settings for setting methods.

Dimensions (Unit: mm)

Backplane

The dimensions are the same for both the C200H-AD001 and C200H-DA001.

52

Page 59

Appendix C Data Memory Coding Sheets C200H-AD001 Analog Input Unit C200H-AD001 DM address (rightmost digits) 00

Data

Unit number:

DM1_00 to DM1_11 Usage

Scaling lower limit for input 1

01

Scaling upper limit for input 1

02

Scaling lower limit for input 2

03

Scaling upper limit for input 2

04

Scaling lower limit for input 3

05

Scaling upper limit for input 3

06

Scaling lower limit for input 3

07

Scaling upper limit for input 4

08

Number of terms for mean value for input 1

09

Number of terms for mean value for input 2

10

Number of terms for mean value for input 3

11

Number of terms for mean value for input 4

53

Page 60

Appendix C

Data Memory Coding Sheets

C200H-DA001 Analog Output Unit C200H-DA001 DM address (rightmost digits) 00

54

Unit number:

Data

DM1_00 to DM1_04 Usage

Lower output limit

01

Upper output limit

02

Lower alarm limit

03

Upper alarm limit

04

Alarm deadband

Page 61

Index A A/D conversion data, 16 analog input vs. digital output, 19

B block diagram C200H-AD001, 9 C200H-DA001, 31

C configurations, system, 4 considerations, 5

D data memory coding sheet, 53 data reading mode, setting, 11 digital output vs. analog input, 39 dimensions, 52 disconnection detection, 23 DM area allocation C200H-AD001, 15 , 17 C200H-DA001, 36 , 38 DM area contents, C200H-AD001, 18

F field devices, 3

I indicators C200H-AD001, 8 C200H-DA001, 30 input disconnection detection function, 23 input signal range, setting, 11 , 19 inputs number, setting, 10 signal range, setting, 11 , 19 IR area allocation C200H-AD001, 15 , 16 C200H-DA001, 36 , 37 IR area contents C200H-AD001, 16 C200H-DA001, 37

M mean function, 21 models, 47

N number of inputs, setting, 10

O output limit alarm function, 41 output limit function, 39 output signal range, setting, 32 , 39 outputs, signal range, setting, 32 , 39

P peak value function, 22 precautions, xi , 2 , 5 applications, xiii general, xii operating environment, xiii safety, xii programming examples C200H-AD001, 24 C200H-DA001, 43 pulse output function, 42 pulse output line, setting, 33 pulse outputs, setting, 33

S scaling function, 20 Slave Racks, 5 specifications, 49 square root function, 19 switches C200H-AD001, 10 C200H-DA001, 32

T troubleshooting C200H-AD001, 26 C200H-DA001, 45

U unit number, setting, Analog Input Unit, 10 unit numbers, setting C200H-AD001, 10 C200H-DA001, 32 Units, number, 5

W wiring C200H-AD001, 11 C200H-DA001, 33

55