Page 1 of SYSMAC C200H-AD001/DA001 Analog I/O Units Operation Guide

Manual · Omron

SYSMAC C200H-AD001/DA001 Analog I/O Units Operation Guide

Manual61 pagesPDF 608 KB

Operation guide for the OMRON SYSMAC C200H-AD001 Analog Input Unit and C200H-DA001 Analog Output Unit for C200H and C200HS PCs.

What this file really is

The old site listed this file as a manual for the Omron C500-AD001. Linked as the C500-AD001 manual, but it is the operation guide for the C200H-AD001 and C200H-DA001 Analog I/O Units for the C200H and C200HS PCs.

Download the PDF608 KB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

OMRON's operation guide for the C200H-AD001 Analog Input Unit and the C200H-DA001 Analog Output Unit, analog-digital and digital-analog converters for the C200H or C200HS PC. After precautions and a system design section, each unit gets its own section covering nomenclature, switch settings, wiring, bit and DM area allocations, functions such as scaling, mean value, peak value, square root, output limits and pulse output, programming examples and troubleshooting. Appendices list standard models, specifications and data memory coding sheets.

Its parts

  1. Precautions
  2. System Design
  3. C200H-AD001 Analog Input Unit
  4. C200H-DA001 Analog Output Units

From the manual

Key facts from this manual

Each line names its page in the PDF.

Operation guide for the Omron SYSMAC C200H-AD001 Analog Input Unit and C200H-DA001 Analog Output Unit, used with C200H and C200HS PCs. The site files it under the C500-AD001, but the guide covers only the two C200H units. It explains switch settings, wiring, the built-in functions, troubleshooting, and the specifications of both units.

Read for this summary: pages 1 to 4, 14 to 18, 22, 34 to 35, 37, 40 to 41 and 54 to 58 of 61.

Devices
C200H-AD001 Analog Input Unit (A/D) and C200H-DA001 Analog Output Unit (D/A) for C200H or C200HS PCs p. 4
Analog inputs
C200H-AD001: up to 4 inputs, converted to 12-bit binary p. 4, 55
Input ranges
C200H-AD001: 1 to 5 V, 4 to 20 mA, or 0 to 10 V (voltage inputs only) p. 4
Input resolution
C200H-AD001: 1/4000 max. (full scale); conversion time 2.5 ms max. per point p. 55
Analog outputs
C200H-DA001: 2 outputs from 12-bit binary data; 1 to 5 V, 4 to 20 mA, or 0 to 10 V p. 4, 57
Output accuracy
C200H-DA001: resolution 1/4095 max.; accuracy ±0.5% max. at 25°C, ±1.0% max. at 0° to 55°C (full scale) p. 57
Output drive
C200H-DA001: voltage output 15 mA max., 0.5 Ω max. output impedance; current output 400 Ω max. load p. 57
Power consumption
C200H-AD001: 550 mA max. at 5 VDC; C200H-DA001: 650 mA max. at 5 VDC p. 55, 57
Terminals
19-pin removable terminal block on both units p. 55, 57
Size and weight
34.5 x 130 x 128 (W x H x D) mm, 450 g max., same for both units p. 55, 57, 58
Input functions
C200H-AD001: scaling, mean value, peak value, square root, and input disconnection detection p. 4, 16
Output functions
C200H-DA001: output limit, output limit alarm, and a 0 V to 5 V pulse output separate from the analog output p. 4, 37
Alarm outputs
C200H-DA001: open-collector upper and lower limit alarm outputs, 100 mA max. per circuit, 5 to 24 VDC p. 40, 41
Unit number
0 to 9 on the front switch, a different number for each unit; factory set to 0 p. 18

What this manual walks you through

  • Planning how many Special I/O Units a PC and its Slave Racks can hold p. 14
  • Setting the unit number and the number of enabled inputs p. 18
  • Wiring analog inputs to keep out noise p. 22
  • Troubleshooting disconnection, setting and CPU errors on the input unit p. 34, 35
  • Restarting a Special I/O Unit with the AR restart bits p. 35
  • Wiring the analog, pulse and alarm outputs of the C200H-DA001 p. 40, 41

Good to know

  • Input signals beyond the maximum ratings damage the C200H-AD001. p. 55
  • On a C200H, an Analog I/O Unit must not go in the two slots next to the CPU, or the Programming Console cannot be connected. p. 14
  • Special I/O Units cannot be used on a C200H Remote I/O Slave Rack connected to a C500, C1000H, or C2000H PC. p. 14
  • A single C200H-DA001 output line cannot give voltage and current output at the same time. p. 41
  • Turn off the PC power before installing or disconnecting units or connecting lines. p. 14

Questions this manual answers

What input ranges does the C200H-AD001 accept?

1 to 5 V, 4 to 20 mA, or 0 to 10 V. The 0 to 10 V range is for voltage inputs only. p. 4

Why is the BROKEN WIRE light on my C200H-AD001 lit?

An input signal wire is disconnected. The indicator works only with the 1 to 5 V or 4 to 20 mA range; check the input wires, terminal block and input voltage. p. 16, 34

How many analog outputs does the C200H-DA001 have?

Two, each set to 1 to 5 V, 4 to 20 mA, or 0 to 10 V. p. 57

What causes an I/O UNIT OVER error?

Two or more Special I/O Units set to the same unit number. The PC then will not operate. p. 18

How much current do the C200H analog units draw from the rack?

The C200H-AD001 draws 550 mA max. and the C200H-DA001 650 mA max., both at 5 VDC. p. 55, 57

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. PRECAUTIONS6
  2. SECTION 1 - System Design10
  3. SECTION 2 - C200H-AD001 Analog Input Unit15
  4. SECTION 3 - C200H-DA001 Analog Output Units36
  5. APPENDIX54
    1. A - Standard Models54
    2. B - Specifications55
    3. C - Data Memory Coding Sheets59
  6. Index61

From the PDF’s own bookmarks.

The whole text · 9 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 41-4
  2. Pages 5 to 95-9
  3. SECTION 1 - System Design10-14
  4. SECTION 2 - C200H-AD001 Analog Input Unit, pages 15 to 2115-21
  5. SECTION 2 - C200H-AD001 Analog Input Unit, pages 22 to 2822-28
  6. SECTION 2 - C200H-AD001 Analog Input Unit, pages 29 to 3529-35
  7. SECTION 3 - C200H-DA001 Analog Output Units, pages 36 to 4436-44
  8. SECTION 3 - C200H-DA001 Analog Output Units, pages 45 to 5345-53
  9. Pages 54 to 6154-61

The file

Revision and size

RevisionCat. No. W127-E1-4, Revised February 2001
PublisherOMRON
Pages61
PDF608 KB
TextText from the PDF itself.