SYSMAC C200H-AD001/DA001 Analog I/O Units Operation Guide: SECTION 1 - System Design
Pages 10 to 14 of 61, from SYSMAC C200H-AD001/DA001 Analog I/O Units Operation Guide
The original document is the PDF (608 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Omron C500-AD001
Page 10
SECTION 1 System Design This section describes the basic uses of Analog I/O Units in a Control System and illustrates the type of applications in which they might be found. 1-1 1-2 1-3 1-4 1-5
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Example Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 2 3 4 5
1
Page 11
Safety Precautions
1-1
Section 1-2
Introduction The C200H-AD001 Analog Input Unit is used to convert the output of analog field devices, usually sensors, to a digital form (12-bit binary) that the PC can read. The C200H-DA001 Analog Output Unit converts the digital output of the PC to analog signals which drive analog field devices.
C200H-AD001 Analog Input Unit
1-2
C200H-DA001 Analog Output Unit
Safety Precautions • Be sure that you have read this manual carefully and have understood the explanations before attempting any of the procedures described herein. OMRON accepts no responsibility for any damage or injury that may result from carrying out any operation that is not covered in this manual. • Be sure to turn off the power supply to the PC before carrying out any of the following operations: a) Mounting or removing a Unit. b) Setting switches. c) Mounting or removing a Terminal Block or connectors. d) Wiring the System or Units. • Use twisted-pair cables and keep high-voltage lines and power lines in separate ducts to reduce the risk of malfunctions due to electrical noise. • Before turning on the power supply, check to be sure that the switch settings and wiring are correct. • Check to be sure that the user program operates correctly.
2
Page 12
Basic Configuration
1-3
Section 1-3
Basic Configuration This diagram shows some of the possible field devices for the Analog I/O Units. Any I/O device can be used as long as voltage/current requirements fall within the specified ranges. The I/O device connected to the Analog I/O Unit will often serve as an interface for another device. For example, a preamplifier may amplify the output of a pressure gauge to the level required for the Analog Input Unit and a regulator may interface a heating system to control temperature.
C200H CPU Rack
Analog Input Unit
Temperature Pressure Speed Flow rate Voltage Current Power Power factor
Analog Output Unit
(Temperature control) Regulator (Speed control)
Preamp
Variable speed controller
M
(Position control) Transducer
Servocontroller
M
Chart recorder
3
Page 13
Example Configurations
1-4
Section 1-4
Example Configurations Below are two examples of how Analog I/O Units can be used in control systems. The first diagram shows a temperature regulating system and the second shows a servomotor positioning system.
Analog Input Unit C200H-AD001
Analog Output Unit C200H-DA001 Transducer
SYSMAC C200HS/C200H/C200HX/HG/HE
Temperature sensing element
Valve controller
M
Fuel
Sensor
Encoder
ÇÇÇÇ ÇÇÇÇ ÇÇÇÇ ÇÇÇÇ
M
Servo controller
Servo motor
Platform SYSMAC C200HS/C200H/C200HX/HG/HE
Locating pulse
High-speed Counter Unit C200H-CT001-V1
4
Analog Output Unit C200H-DA001 Analog Input Unit C200H-AD001
Page 14
System Considerations
1-5
Section 1-5
System Considerations
Number of Units
C200HS/C200H/C200HX/HG/HE Analog I/O Units are classified as Special I/O Units. A maximum total of ten Special I/O Units (including PC Link Units) can be mounted to the CPU Rack, Expansion I/O Racks, and Slave Racks of a single PC. A single C200H-NC211 Position Control Unit counts as two Units. The Units that belong to the various Special I/O Unit groups are shown in the following table. Their usage is limited according to the maximum current provided for the Rack and the amount of current consumed by each Unit. For details, refer to the C200HS/C200H Installation Guide.
Slave Racks
A
Certain limitations apply to the number of Special I/O Units that can be mounted on Slave Racks. The following table shows the maximum number of Group A, B, C, and D Special I/O Units that can be mounted on a single Slave Rack when only Units of that group are used. B
C
Multipoint I/O Units Temperature Control Units PID Control Units Cam Positioner Units
Temperature Sensor Units Voice Units
4 Units
–––
–––
–––
–––
8 Units
–––
–––
–––
–––
6 Units
–––
–––
–––
–––
2 Units
High-speed Counters Position Control Units (NC111/112) ASCII Units Analog I/O Units ID Sensor Units Fuzzy Logic Units
D Position Control Units (NC211)
If Units from any of the four groups are to be combined, then both of the following two equations must be satisfied. 3A + B + 2C + 6D x 12 A+B+C+Dx8 Units can be mounted on other Racks as well, until the maximum total of ten Units has been reached. Remember, though, that a single C200H-NC2111 Position Control Unit counts as two Units. PC Link Units must also be counted among the total of ten Units. System Configuration Considerations
C200HS/C200H Special I/O Units are allocated IR area words according to the unit number switch settings on their front panels. They do not use the words of the slots in which they are mounted. For details regarding data area allocations, refer to 2-2 and 3-2 IR and DM Bit Allocations. With the C200H, do not mount an Analog I/O Unit in the two slots adjacent to the CPU. Doing so would block peripheral devices such as the Programming Console from being connected. Special I/O Units cannot be used on a C200H Remote I/O Slave Rack if the Slave Rack is connected to different model PC (i.e., C500, C1000H, or C2000H).
Precautions
Be sure to turn off the power supply to the PC before installing or disconnecting Units or connecting lines. To reduce the risk of malfunctioning due to electrical noise, wire input and output lines in separate ducts from high-voltage and power lines. For further wiring precautions, refer to the respective sections on wiring for Analog Input Units and Analog Output Units.