Page 15

SECTION 2 C200H-AD001 Analog Input Unit This section provides the information required to install and operate a C200H-AD001 Analog Input Unit. 2-1

2-2 2-3

2-4

Before Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-1 Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-2 Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bit and DM Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Functions and Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-1 Input Signal Range Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-2 Square Root . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-3 Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-4 Mean Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-5 Peak Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-6 Input Disconnection Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-7 Data Setting Example and Programming Concepts . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8 8 10 11 15 18 19 19 20 21 22 23 23 26

7

Page 16

Section 2-1

Before Operation

2-1

Before Operation

2-1-1 Nomenclature and Functions

Model label Unit number setting switch

Display panel

Function setting DIP switch

Voltage/current input terminals Backplane connector

Indicators Indicator

Color

Function

RUN

Green

Lit when the Analog Input Unit is operating correctly. If operation is not normal, this indicator turns OFF and Unit operation is stopped.

BROKEN WIRE

Red

Lit when an input signal wire is disconnected. This indicator operates only when the input range is set to 1 to 5 V/4 to 20 mA.

Functions Function

The following table briefly outlines the basic functions of the C200H-AD001. These functions are covered in more detail in 2-3 Functions and Programming. Explanation

Input range setting

The input range can be set according to the input signal level that is to be used. The same input range is used for all of the inputs for a particular Unit. The voltage range of 1 to 5 V and the current range of 4 to 20 mA, however, can be used at the user’s option for any input.

Square root

Converts quadratic data, such as thermocouple input, to linear data.

Scaling

Converts an analog input signal to a preset range of BCD data for output.

Mean value

Sums the sampling data and calculates the mean value for output.

Peak value

Holds the maximum values for A/D conversion data, scaling data, mean data, and square root data, and outputs them as output data. The Disconnection Detection Flag is turned ON and the BROKEN WIRE indicator is lit if the input signal wire becomes disconnected when 1 to 5 V/4 to 20 mA are set.

Disconnection detection

8

Page 17

Section 2-1

Before Operation Block Diagram

The following diagram shows the basic internal configuration of the Unit.

Input point 1

SW

+Voltage Input +Current Input

Input point 3

Input point 2

–Input

CPU ROM/ RAM

+Voltage Input +Current Input

A/D converter Multiplexer

–Input

C200H or C200HS PC I/O bus

+Voltage Input +Current Input Range selector

–Input

Input point 4

Bus interface

Photocoupler

+Voltage Input +Current Input

Photocoupler Watchdog timer

–Input Common DC/DC Analog power supply Analog 0 V converter

+5 V 0V

9

Page 18

Section 2-1

Before Operation

2-1-2 Switch Settings There are four settings necessary for this Unit: unit number, number of inputs, input range, and data reading mode. Unit Number Unit number setting switch The switch notch points to the unit number. The switch in the figure to the left is set to 0. Odd numbers, in parentheses here, are not shown on the Unit. Use a standard screwdriver and set a different unit number for each Analog I/O Unit. IR area memory is allocated according to unit number, as shown in the table below.

Note

Number of Inputs

Switch setting

Unit number

IR words

DM words

0

Unit #0

IR 100 to 109

DM 1000 to 1099

1

Unit #1

IR 110 to 119

DM 1100 to 1199

2

Unit #2

IR 120 to 129

DM 1200 to 1299

3

Unit #3

IR 130 to 139

DM 1300 to 1399

4

Unit #4

IR 140 to 149

DM 1400 to 1499

5

Unit #5

IR 150 to 159

DM 1500 to 1599

6

Unit #6

IR 160 to 169

DM 1600 to 1699

7

Unit #7

IR 170 to 179

DM 1700 to 1799

8

Unit #8

IR 180 to 189

DM 1800 to 1899

9

Unit #9

IR 190 to 199

DM 1900 to 1999

1. The unit number setting switch is factory set to 0. 2. If two or more Special I/O Units are assigned the same unit number, an I/O UNIT OVER error will be generated and the PC will not operate. 3. Make the unit number settings with the power turned off to the PC. If the settings are made with the power on, they will not go into effect until either the power is turned off and then on again or the Special I/O Unit Restart Flag (AR0100 to AR0109) is turned ON. There can be 1, 2, or 4 inputs depending on the settings of pins 1 and 2, as shown in the table below.

0: OFF 1: ON

The following table shows the effects of the various pin combinations. If there is no need to use all of the inputs, processing time can be shortened by setting the pins so that the smallest possible number of inputs is enabled. Pin number

10

Number of inputs

Inputs enabled

1 OFF

2 ON

1

Input 1 only is enabled.

ON

OFF

2

Inputs 1 and 2 only are enabled.

OFF

OFF

4

All inputs are enabled.

ON

ON

Not used.

–––

Page 19

Section 2-1

Before Operation Input Range

Use pin 3 to set the input range. Pin number 3 OFF ON

Input range Voltage input Current input Voltage input

1 to 5 V 4 to 20 mA 0 to 10 V

Note The same input range is used for all of the inputs for a particular Unit. The voltage range of 1 to 5 V and the current range of 4 to 20 mA, however, can be used at the user’s option at any input. Data Reading Mode

In normal mode, the input data is read only once before being converted from analog to digital. In filter mode, the input data is read three times and then the average values are converted from analog to digital. This helps to reduce the effects of electrical noise and so on. Using filter mode, however, results in longer processing time, as shown in the following table. Pin number 3

Data reading mode

A/D conversion time

OFF

Normal mode

2.5 ms/input max.

ON

Filter mode

4 ms/input

2-1-3 Wiring Terminal Allocation

The following illustration shows the function of each terminal.

Input 1 (–)

A0

Not used.

A1

Input 2 (–)

A2

Not used.

Voltage input 1 (+)

B1

Current input 1 (+)

B2

Voltage input 2 (+)

B3

Current input 2 (+)

B4

Voltage input 3 (+)

B5

Current input 3 (+)

B6

Voltage input 4 (+)

B7

Current input 4 (+)

B8

Not used.

B9

Common (Analog 0 V)

A3

Input 3 (–)

A4

Not used.

A5

Input 4 (–)

A6

Not used.

A7

Common (Analog 0 V)

B0

A8

The same input range is used for all of the inputs for a particular Unit. The voltage range of 1 to 5 V and the current range of 4 to +20 mA, however, can be used at the user’s option at any input. Use the DIP switch on the back panel of the Unit to set the input range and the number of inputs. (For details, refer to 2-1-2 Switch Settings.) When current input is used, short circuit the voltage input (+) and current input (+) terminals. The common terminal is connected to the 0 V of the Analog Input Unit’s analog circuit. Noise interference can be reduced by using shielded cables for input lines. The A8 and B9 terminals are short circuited internally.

11

Page 20

Section 2-1

Before Operation Voltage Inputs

The following diagram illustrates the external wiring of voltage inputs for the C200H-AD001. C200H-AD001 Input side Shield Input 1

Input 2

Input 3

0V

0V

0V

Input 4 0V

Note Terminals A8 and B9 are analog input ground terminals. They are not frame grounds and so do not connect them to a ground.

12

Page 21

Section 2-1

Before Operation Current Inputs

The following diagram illustrates the external wiring of current inputs for the C200H-AD001. When current inputs are used, use the short pins provided with the Unit to short circuit the V+ and I+ terminals as shown in the diagram. C200H-AD001 Input side Shield Input 1

0V

(Short pin)

+V

Input 2

0V +V

Input 3

Input 4

(Short pin)

0V +V

0V +V

(Short pin)

(Short pin)

Note Terminals A8 and B9 are analog input ground terminals. They are not frame grounds and so do not connect them to a ground.

13