For the Omron C500-BI081/ 3G2A5-BI081 and Omron C500-OD219

Page 91

Appendix B

Specifications AC Input Units 3G2A5-IA121

3G2A5-IA222

Input Voltage

100 to 120 VAC )10%/*15% 50/60 Hz

200 to 240 VAC )10%/*15% 50/60 Hz

Input Impedance

9.7 kΩ (50 Hz), 8 kΩ (60 Hz)

22 kΩ (50 Hz), 18 kΩ (60 Hz)

Input Current

10 mA typical (at 100 VAC)

10 mA typical (at 200 VAC)

ON Voltage

60 VAC min.

120 VAC min.

OFF Voltage

20 VAC max.

40 VAC max.

ON Response Time

35 ms max.

35 ms max.

OFF Response Time

55 ms max.

55 ms max.

No. of Points

16 (8 points/common, 2 circuits)

16 (8 points/common, 2 circuits)

Internal Current Consumption

10 mA 5 VDC max.

12 mA 5 VDC max.

Weight

450 grams max.

450 grams max.

Circuit Configuration IN 00 to

560 Ω

0.33 µF

330 kΩ

Ω

IN 00

IN 08 to

560 Ω

0.33 µF

330 kΩ

Ω

220

Internal Circuit

IN 07 COM

680 Ω

IN 08

0.15 µF

1 MΩ 220

Ω to

IN 15 COM

IN 15 COM

Terminal Connections

0

0

0 1 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 NC 18 NC 19

~

100 to 120 VAC ~

A-shape

0 1 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 NC 18 NC 19 1 2

1 2

100 to 120VAC

Dimensions

Ω to

Internal Circuit

0.15 µF

1 MΩ 220

220

IN 07 COM

680 Ω

200 to 240VAC

~

200 to 240 VAC ~

A-shape

85

Page 92

Appendix B

Specifications AC Input Units Continued 3G2A5-IA122

3G2A5-IA223

Input Voltage

100 to 120 VAC )10%/*15% 50/60 Hz

200 to 240 VAC )10%/*15% 50/60 Hz

Input Impedance

9.7 kΩ (50 Hz), 8 kΩ (60 Hz)

22 kΩ (50 Hz), 18 kΩ (60 Hz)

Input Current

10 mA typical (at 100 VAC)

10 mA typical (at 200 VAC)

ON Voltage

60 VAC min.

120 VAC min.

OFF Voltage

20 VAC max.

40 VAC max.

ON Response Time

35 ms max.

35 ms max.

OFF Response Time

55 ms max.

55 ms max.

No. of Points

32 (8 points/common, 4 circuits)

32 (8 points/common, 4 circuits)

Internal Current Consumption

60 mA 5 VDC max.

60 mA 5 VDC max.

Weight

600 grams max.

600 grams max.

Circuit Configuration

IN 00 to IN 07

I

COM IN 08 to IN 15 COM IN 00 to IN 07

II

COM

330 Ω 0.33 µF 330 kΩ

IN 00 to

IN 07

220

Ω

I

100 to ~ 120 VAC

Dimensions

86

C-shape

Ω

IN 08 to

330 Ω 0.33 µF 330 kΩ

COM

IN 00 to

IN 07

220

Ω

Internal Circuit

II

560 Ω 0.15 µF 1 MΩ 270

Ω

COM IN 08 to

IN 15 COM

I

100 to ~ 120 VAC

1 MΩ 270

COM

IN 15

Internal Circuit

IN 08 to IN 15 COM

Terminal Connections

560 Ω 0.15 µF

A

B 0

II

0 0 0 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 7 7 7 7 COM 8 COM 8 8 9 8 9 9 10 9 10 10 11 10 11 11 12 11 12 12 13 12 13 13 14 13 14 14 15 14 15 15 16 15 16 COM 17 COM 17 18 NC NC 18

I

~ 100 to

120 VAC 200 to ~ 240 VAC

~ 100 to

120 VAC 200 to 240 VAC

C-shape

~

A

B 0

II

0 0 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 5 4 5 5 6 5 6 6 7 6 7 7 7 COM 8 COM 8 8 9 8 9 9 10 9 10 10 11 10 11 11 12 11 12 12 13 12 13 13 14 13 14 14 15 14 15 15 16 15 COM 16 17 COM 17 18 NC NC 18 0

~ 200 to

240 VAC

~ 200 to

240 VAC

Page 93

Appendix B

Specifications Contact Output Units 3G2A5-OC221

3G2A5-OC223

Max. switching Capacity

2 A 250 VAC (cos of phase angle= 1), 0.5 A 250 VAC (cos of phase angle= 0.4), 2 A 24 VDC (8 A/common,16 A/Unit)

2 A 250 VAC (cos of phase angle= 1), 0.5 A 250 VAC (cos of phase angle= 0.4), 2 A 24 VDC (32 A/Unit)

Min. switching Capacity

10 mA 5 VDC

10 mA 5 VDC

Power for External Supply

Voltage: 24 VDC ±10 % Current: 10 mA/point, 160 mA/Unit

Voltage: 24 VDC ±10 % Current: 10 mA/point, 160 mA/Unit

Bit

G6B-114P-FD-US-M (24 VDC) w/socket

G6B-114P-FD-US-M (24 VDC) w/socket

Service Life of Relay

Electrical: 300,000 operations (resistive load) 100,000 operations (inductive load) Mechanical: 50,000,000 operations

Electrical: 300,000 operations (resistive load) 100,000 operations (inductive load) Mechanical: 50,000,000 operations

ON Response Time

15 ms max.

15 ms max.

OFF Response Time

15 ms max.

15 ms max.

No. of Points

16 (8 points/common, 2 circuits)

16 (independent common)

Internal Current Consumption

100 mA 5 VDC max.

100 mA 5 VDC max.

Weight

450 grams max.

450 grams max.

Circuit Configuration x x

OUT 00 to OUT 07 COM

Internal Circuit

Internal Circuit x

OUT 08 to

Relays are mounted on sockets and are replaceable. Terminal Connections

L

+

250 VAC 24 VDC max.

~ +

+

250 VAC 24 VDC max.

+

~

+

Internal Circuit

OUT 07 COM x

OUT 08 COM to

OUT 15 COM

OUT 15 COM

24 VDC 0V

24 VDC 0V

Relays are mounted on sockets and are replaceable.

0

0 1 2 L 2 3 L 3 4 L 4 5 L 5 6 L 6 L 7 7 COM 8 8 L 9 9 L 10 10 L 11 11 L 12 12 L 13 13 L 14 14 L 15 L 15 16 COM 17 18 19 L

Internal Circuit

OUT 00 COM to

1

B 0 1 2 3 4 5 6 7 ~ NC 8 9 ~ + 10 +~ 11 ~ + 12 ~ + 13 +~ 14 +~ 15 +~ 16 ~ NC + NC 17 17 18 + 18 24 VDC +

+~ +~ +~ +~ +~ +~ +~

250 VAC 24 VDC max.

A 0 0 1 1 2 2 L 3 3 L 4 4 L 5 5 L 6 6 L 7 7 NC 8 L 8 9 L 9 10 L 10 11 L 11 12 L 12 13 L 13 14 L 14 15 L 15 16 L L L

24 VDC Dimensions

A-shape

B-shape

87

Page 94

Appendix B

Specifications Contact Output Units Continued 3G2A5-OC224 Max. switching Capacity

2 A 250 VAC (cos of phase angle= 1), 0.5 A 250 VAC (cos of phase angle= 0.4), 2 A 24 VDC (8 A/common, 32 A/Unit)

Min. switching Capacity

10 mA 5 VDC

Power for External Supply

Voltage: 24 VDC ±10 % Current: 10 mA/point, 320 mA/Unit

Bit

G6B-114P-FD-US-M (24 VDC) w/socket

Service Life of Relay Electrical: 300,000 operations (resistive load) 100,000 operations (inductive load) Mechanical: 50,000,000 operations ON Response Time

15 ms max.

OFF Response Time 15 ms max. No. of Points

32 (8 points/common, 4 circuits)

Internal Current Consumption

200 mA 5 VDC max.

Weight

600 grams max.

Circuit Configuration x

OUT 00 to OUT 07 COM OUT 08 OUT 15 COM OUT 00

Internal Circuit

Internal Circuit x

I to OUT 07 COM OUT 08 OUT 15 COM 24 VDC 0V

Terminal Connections

B II A 0 0 L 0 L 1 1 1 1 2 L L 2 2 2 3 L L 3 3 3 4 L L 4 4 4 5 L L 5 5 5 6 L L 6 6 6 7 L L 7 7 7 COML L COM 8 8 8 8 9 L L 9 9 9 10 L 10 L 10 10 11 L 11 L 11 11 12 L 12 L 12 12 13 L 13 L 13 13 14 L L 14 14 14 15 L L 15 15 15 16 L L 16 COM COM 17 17 18 18

I

250 VAC 24 VDC max.

+ ~

+

250 VAC 24 VDC max.

+

+ ~

+

24 VDC

Dimensions

88

C-shape

0

+

250 VAC 24 VDC max.

~ +

+ ~

250 VAC 24 VDC max.

+

II

Page 95

Appendix B

Specifications

Fuses Unit Model

Fuse Specifications

3G2A5-PS221-E 3G2A5-PS222-E 3G2A5-PS223-E

3 A 250 V (6.35 dia. x 32)

3G2A5-PS211-E 3G2A5-PS212-E 3G2A5-PS213-E

4 A 125 V (6.35 dia. x 32)

3G2A5-OD411 3G2A5-OD217 3G2A5-OA223

5 A 250 V (5.2 dia. x 20)

3G2A5-OA121 3G2A5-OA222 C500-OA226

5 A 250 V (6.35 dia. x 32)

C500-OD219

10 A 250 V

6.3 A 125 V (6.35 dia. x 32)

Dimensions All dimensions are in millimeters unless stated otherwise.

CPU Rack 3G2A5-BC081/BC082

250 150

465 480

3G2A5-BC051/BC052

150 250

360 375

C500-BC031

250 150

255 276

89

Page 96

Appendix B

Specifications C500-BC061

150

360 381

C500-BC091

250 150

465 486

Expansion I/O Rack 3G2A5-BI081

250 150

465 480

3G2A5-BI051

150 250

360 375

90

Page 97 read from a scan by OCR; it may hold reading errors

Specifications

Appendix B

A-shape I/O Unit

B-shape I/O Unit gaL_Il fo f < - ° J [et 93 34S] a * i a1 lope fone 250 tS) _ 93 34.54

91

Page 98 read from a scan by OCR; it may hold reading errors

Specifications Appendix B

C-shape I/O Unit

D-shape I/O Unit

139 345-1

92

Page 99

Appendix B

Specifications E-shape I/O Unit

Unit Weights Model 3G2C3-CPU11-V1 3G2A5-PS221/PS222/PS223 3G2A5-PS211/PS212 C500-II101 C500-II002 3G2A5-BC081 3G2A5-BC082 3G2A5-BI081 3G2A5-BC051 3G2A5-BC052 3G2A5-BI051 C500-BC091

Weight (max.) 1 kilogram each 1.1 kilograms 300 grams 350 grams each 2.6 kilograms each 2 kilograms

2.8 kilograms

C500-BC061

2.2 kilograms

C500-BC031

1.8 kilograms

93

Page 100

Appendix B

Specifications I/O Connecting Cables

Use an I/O Connecting Cable to connect the CPU Rack to an Expansion I/O Backplane or to connect an Expansion I/O Backplane to additional Expansion I/O Backplane. Fasten the connectors with the locks provided on the connectors to secure the connection between the cable connector and the connector on the Backplane. If the connectors are not properly connected or the I/O Connecting Cable is disconnected during CPU operation, errors such as I/O BUS error and I/O SETTING error will occur.

Lock spring

Lock spring

The length of the connecting cable depends on the distance between the two Racks to be connected. The length of the cable should be approximately 20 cm longer than the distance between the two Racks. Cable Length (L)

Distance between Rack (max.) (X)

30 cm

10 cm

50 cm

30 cm

80 cm

60 cm

1m

80 cm

2m

180 cm

Expansion Rack or I/O Rack

X

Expansion Rack

94