Summary
What is in it
The installation guide for the Omron C500 programmable controller system. It describes every component (CPU Rack, CPU and I/O Power Supplies, Expansion I/O Backplanes, I/O Control and I/O Interface Units, I/O Units and Memory Packs), then explains assembly and system configurations, current consumption and I/O connections, the installation environment and noise prevention, power and safety considerations, with inspection, specifications and a standard models list (including Units such as the 3G2A5-DA003 and C500-RM201) in the appendices.
Its parts
- Precautions
- Introduction
- Description of All Components
- Assembly
- System Connections
- Installation Environment
- Power Considerations
- Safety Considerations
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Omron's C500 Programmable Controller Installation Guide (revised May 2000) for the whole C500 system: CPU racks, CPU and expansion power supplies, expansion I/O racks, I/O units, special I/O units and link units. It prints most part numbers with the 3G2A5- prefix, for example 3G2A5-PS222-E, 3G2A5-OD412 and 3G2A5-DA003, and some with C500-, such as C500-OD219. It helps the reader assemble racks, budget power supply current, install, maintain and look up specifications and model numbers.
- CPU racks
- Seven CPU rack backplanes with 3, 5 (2 models), 6, 8 (2 models) or 9 I/O slots p. 19
- Expansion I/O racks
- Like a CPU rack without the CPU; each needs its own power supply and an I/O Interface Unit in the leftmost I/O position p. 23, 25
- Expansion power supplies
- 3G2A5-PS222-E (100 to 120/200 to 240 VAC, selectable) and 3G2A5-PS212-E (24 VDC): 7 A 5 VDC, 6.5 A for I/O Units p. 23
- CPU power supply
- Mounts in the rightmost slot of the CPU rack; 100 to 120 VAC, 200 to 240 VAC or 24 VDC models p. 21
- Current budget
- A 7 A CPU power supply leaves only 5 A for I/O Units p. 21
- 24 VDC service output
- 0.8 A 24 VDC on 3G2A5-PS221-E and 3G2A5-PS222-E for DC Input Units; the PC stops above 0.8 A p. 21, 24
- Operating voltage range
- AC supplies 85 to 132/170 to 264 VAC; 24 VDC supplies 20.4 to 26.4 VDC p. 63
- Environment
- Operating 0 to 55 °C; storage -20 to 65 °C; 35% to 85% RH without condensation p. 63
- CPU
- Ladder diagram programming; 71 instructions; 24K words memory; 512 I/O bits p. 64
- Battery
- Service life four years at 25 °C; ALARM blinks and BATT LOW shows when it is nearly flat p. 61, 62
- C500-OD219 outputs
- C500-OD219: 16 transistor outputs (8 points/common, 2 circuits), 12 to 24 VDC +10%, -15%, 2.1 A (8 A/common, 16 A/Unit) p. 86
- C500-OD219 timing
- C500-OD219: ON response 0.2 ms max, OFF response 0.4 ms max; residual voltage 0.7 V max; leakage 0.1 mA max p. 86
- C500-OD219 power, fuse
- C500-OD219: 160 mA 5 VDC internal; 10 A 250 V fuses (two); external supply 100 mA 12 to 24 VDC min; 550 grams max p. 40, 86, 95
- AC supply fuse
- 3G2A5-PS221-E, 3G2A5-PS222-E, 3G2A5-PS223-E: 3 A 250 V (6.35 dia. x 32) p. 95
What this manual walks you through
- Parts of the CPU rack and the CPU p. 19, 20
- Wiring a power supply and setting its voltage selector p. 21, 22, 24
- Adding expansion I/O racks with I/O Control and I/O Interface Units p. 23, 25
- Budgeting power supply current for I/O Units p. 39, 40, 41
- Replacing output unit fuses and relays p. 61
- Replacing the battery p. 61, 62
- Power supply, CPU and output unit specifications p. 63, 64, 86
- Unit fuses, rack dimensions and weights p. 95, 96, 99
- Looking up standard model numbers p. 102, 103, 104, 105
Good to know
- Keep the total current of the Units on a rack within what its power supply makes available for I/O Units. p. 21
- Without an I/O Interface Unit on each expansion I/O rack, data communication cannot take place. p. 25
- A battery change must be finished within five minutes so data is not lost. p. 61
- Disconnect the LG terminals from the GR terminals before a dielectric strength or insulation resistance test. p. 63
Questions this manual answers
What power supply does a C500 expansion I/O rack use?
A 3G2A5-PS222-E for 100 to 120/200 to 240 VAC or a 3G2A5-PS212-E for 24 VDC, each giving 7 A at 5 VDC with 6.5 A for I/O Units. p. 23
What are the ratings of the C500-OD219 output unit?
16 transistor outputs at 12 to 24 VDC, 2.1 A each, with 8 A per common and 16 A per unit. p. 86
How long does the C500 battery last?
Four years at 25 °C. When the ALARM indicator blinks and BATT LOW appears, replace it within one week. p. 61, 62
Where does the I/O Interface Unit go on a C500 expansion rack?
In the leftmost I/O position of the Expansion I/O Backplane; one is needed on each expansion rack. p. 25