Page 51
Section 6
Power Considerations
Introduction Use a commercially available 100 to 120 VAC, 200 to 240 VAC, or 24 VDC power source, according to the PC you are using (refer to Appendix B Specifications). Expansion I/O Racks, if used, must also be connected to the power source. If possible, use independent power sources for the PC, input devices, and output devices. All Racks of the PC may be connected to one power source.
Grounding The Line Ground (LG) terminal is a noise-filtered neutral terminal that does not normally require grounding. If electrical noise is a problem, however, this terminal should be connected to the Ground (GR) terminal. To avoid electrical shock, attach a grounded (earth ground) AWG 14 wire (cross-sectional area: 2 mm2 min.) to the GR terminal. The resistance to ground must be less than 100 Ω. Do not use a wire longer than 20 m. Care must be taken, because ground resistance is affected by environmental conditions such as soil composition, water content, time of year, and the length of time since the wire was laid underground. PC operation may be adversely affected if the ground wire is shared with other equipment, or if the ground wire is attached to the metal structure of a building. When using an Expansion I/O Rack, the Rack must also be grounded to the GR terminal. The same ground can be used for all connections.
Power Failure A sequential circuit is built into the PC to handle power interruptions. This circuit prevents malfunctions due to momentary power loss or voltage drops. A timing diagram for the operation of this circuit is shown below. OFF
ON
Power Supply Power failure detection signal
Momentary power failure detection time
CPU voltage (5 V)
Power reset Approx. 1 s
Run monitor outputs
The PC ignores all momentary power failures if the interruption lasts no longer than 10 ms. If the interruption lasts between 10 and 25 ms, the interruption may or may not be detected. If the supply voltage drops below 85% of the rated voltage for longer that 25 ms (less for the DC Power Supply), the PC will stop operating and the external outputs will be automatically turned OFF. Operation is resumed automatically when the voltage is restored to more than 85% of the rated value.
Wiring The following diagrams show the proper way to connect the power source to the PC. The terminals marked “NC” are not connected internally.
44
Page 52
Section 6
Power Considerations AC Connections 3G2A5-PS221-E/223-E Screw (4 mm head with selfraising pressure plate) Breaker
+ 1:1 isolation transformer
-
Voltage selector Short: 100 to 120 VAC Open: 200 to 240 VAC Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC leave them open.
Isolation transformer • Noise between the PC and ground can be significantly reduced by connecting a 1-to-1 isolation transformer. Do not ground the secondary coil of the transformer. AC power source
• Supply 100 to 120 or 200 to 240 VAC • Keep voltage fluctuations within the specified range (refer to Appendix B Specifications)
3G2A5-PS222-E
Screw (4 mm head with selfraising pressure plate)
Power line • Use AWG 14 twistedpair cable (cross-sectional area: 2 mm2 min.)
+
Voltage selector Short: 100 to 120 VAC Open: 200 to 240 VAC Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC, leave them open.
! Caution
Be sure to use a wire of at least 1.25 mm2 in thickness. Use M4 screws for tightening crimp terminals. Use ring crimp terminals for wiring. Do not connect bare stranded wires directly to terminal blocks. 8.6 mm max.
Tighten the screws on the terminal block of the AC Power Supply Unit to a torque of 1.2 N S m. Loose screws may result in burning or malfunction.
45
Page 53
Section 6
Power Considerations DC Connections 3G2A5-PS213-E
Screw (4 mm head with selfraising pressure plate)
Breaker
+
-
• Supply 24 VDC • Keep voltage fluctuations z within the specified range (refer to Appendix B Specifications)
3G2A5-PS212-E
Screw (4 mm head with selfraising pressure plate)
+
Power line • Use AWG 14 twisted-pair cable (cross-sectional area: 2 mm2 min.)
-
Be sure to use a wire of at least 1.25 mm2 in thickness. Use M4 screws for tightening crimp terminals. Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminal blocks. 8.6 mm max.
8.6 mm max.
Tighten the terminal block screws to a torque of 1.2 N S m.
46
Page 54
Section 6
Power Considerations Grounding Connections 3G2A5-PS223-E/221-E/213-E
Be sure to use a wire of at least 1.25 mm2 in thickness. Use M4 screws for tightening crimp terminals. Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminal blocks. 8.6 mm max.
8.6 mm max.
Tighten the terminal block screws to a torque of 1.2 N S m. Screw (4 mm head with selfraising pressure plate)
3G2A5-PS222-E/212-E
For grounding use 2mm2 cable. Be sure to keep the length of the cable less than 20 meters.
Screw (4 mm head with selfraising pressure plate)
! Caution
Ground the Power Supplies separately from peripheral devices.
47
Page 55
SECTION 7 Safety Considerations
49
Page 56
Section 7
Safety Considerations
Introduction There are certain safety requirements to be considered when installing the PC. Some of these, such as the emergency stop circuit (refer to Power Supply), are part of the initial wiring. The considerations described below should be kept in mind when operating the PC and when connecting I/O devices to the PC.
Interlock Circuits When the PC controls an operation such as the clockwise and counterclockwise operation of a motor, provide an external interlock such as the one shown below to prevent both the forward and reverse outputs from turning ON at the same time. Interlock circuit
00501
MC2 MC1 Motor clockwise
PC 00502
MC1 MC2 Motor counterclockwise
This circuit prevents outputs MC1 and MC2 from both being ON at the same time. Even if the PC is programmed improperly or malfunctions, the motor is protected.
Power Supply Output The 24 VDC output of the CPU and Expansion I/O Power Supply may be used to power other devices. The output current of these supplies is limited to 0.3 A. A separate Power Supply must be provided if the devices being powered require a higher current.
Input Leakage Current When two-wire sensors, such as photoelectric sensors, proximity sensors or limit switches with LEDs are connected to the PC as input devices, the input bit may be turned ON erroneously by leakage current. In order to prevent this, connect a bleeder resistor across the input as shown below. Input power supply
Bleeder resistor
R
PC
Sensor
If the leakage current is less than 1.3 mA, there should be no problem. If the leakage current is greater than 1.3 mA, determine the value and rating for the bleeder resistor using the following formulas. I = leakage current in mA 7.2 kΩ max. R= 2.4 x I – 3 2.3 W= W min. R
50
Page 57
Section 7
Safety Considerations Output Leakage Current
If there is a possibility of leakage current causing a transistor or triac to malfunction, connect a bleeder resistor across the output as shown below. OUT
L
R Load Power Supply
PC Bleeder resistor COM
Determine the value and rating for the bleeder resistor using the following formula. R
EON I
Where Eon = ON voltage of the load I = leakage current in mA R = bleeder resistance
Output Surge Current When connecting a transistor or triac Output Unit to an output device having a high surge current (such as an incandescent lamp), care must be taken to avoid damage to the Output Unit. The transistor and triac Output Units are capable of withstanding a surge current of ten times the rated current. If the surge current for a particular device exceeds this amount, use the circuit shown below to protect the Output Unit.
L
OUT
+ R COM
Another way of protecting the Output Unit lets the load draw a small current (about one third the rated current) while the output is OFF, significantly reducing the surge current. This circuit (shown below) not only reduces the surge current, but also reduces the voltage across the load at the same time. R OUT
L
+ COM
Transistor Output Residual Voltage When connecting TTL circuits to transistor Output Units, connect a pull-up resistor and a CMOS IC between the two. This is because of the residual voltage left on the transistor output after the output turns OFF.
51
Page 58
Section 7
Safety Considerations Inductive Load Surge Suppressor
When an inductive load is connected to an I/O Unit, connect a surge suppressor or diode in parallel with the load as shown in the following diagram. This is so that the back electromagnetic field generated by the load will be absorbed. Resistor: 50 W Capacitor: 0.47 µF Voltage: 200 V Diode: Must withstand voltages of more than three times the load voltage and an average current of 1 A IN
L
DC Input
Diode COM
OUT
L
Relay Output Unit Triac Output Unit Surge suppressor COM OUT
L
+
Relay Output Unit Transistor Output Unit Diode COM
Electrical Noise Take appropriate measures when any electrical device likely to produce noise is connected to the PC as a load. Devices generating noise of more than 1,200 V (such as electromagnetic relays and valves) require noise suppression. For noise sources running on AC power, connect a diode in parallel with the coil of each device. When mounting a CPU Rack and an Expansion I/O Rack together on a mounting plate, provide a solid ground to the mounting plate. The mounting plate must be plated with a highly conductive surface in order to ensure noise immunity.
52
Page 59
Appendices
A Inspection and Maintenance ....... 20... 0. eect eet eee ene ne eee Cc B Specifications .. 0.0... eee nee eee eens oO C Standard Models ...... 2... cee eee cnet eens C]
53
Page 60
A
Inspection and Maintenance Certain consumable items in a PC (such as fuses, relays, or batteries) need occasional replacement. This Appendix explains how to replace each of these items. Refer to Appendix B Specifications for the specifications of individual consumable items. Always keep spare items on hand so that they can be used as immediate replacements.
CPU and Power Supply Fuses To replace a fuse in the CPU or Power Supply, follow the steps below. 1.
Turn OFF the power to the PC.
2.
Remove the fuse holder by turning it approximately 50° counterclockwise with a standard screwdriver.
3.
Remove the fuse from the holder.
Turn counterclockwise to remove, clockwise to attach Standard screwdriver
4.
Insert a new fuse.
5.
Reattach the fuse holder by turning it approximately 50° clockwise with a standard screwdriver.
Output Unit Fuses To replace a fuse in an Output Unit, follow the steps below. 1.
Turn OFF the power to the PC.
2.
Detach the terminal block from the Output Unit, by removing the screws located at the top and bottom of the terminal block. Mounting screws Located at the top and bottom.
Terminal block mounting screws Located at the top and bottom of the terminal block. Cover mounting screws (8)
54