Page 61

Appendix A

Inspection and Maintenance 3.

Remove the screws that mount the Output Unit to the Backplane. Pulling the Unit toward you, remove the Output Unit from the Backplane.

4.

There are eight screws on each side of the Output Unit. Remove these screws to detach the case from the cover.

5.

Pull out the printed circuit board.

6.

Insert a new fuse.

7.

Reassemble in reverse order.

Output Unit Relays To replace a Relay in an Output Unit, follow the steps below. 1.

Turn OFF the power to the PC.

2.

Detach the terminal block from the Output Unit, by removing the screws located at the top and bottom of the terminal block. Mounting screws Located at the top and bottom.

Terminal block mounting screws Located at the top and bottom of the terminal block. Cover mounting screws (8)

3.

Remove the screws that mount the Output Unit to the Backplane. Pulling the Unit toward you remove the Output Unit from the Backplane.

4.

There are eight screws on each side of the Output Unit. Remove these screws to detach the case from the cover.

5.

Pull out the printed circuit board. Place the Relays on the circuit board.

6.

Use the Relay Puller to pull out the Relay. Insert a new Relay.

7.

Reassemble in reverse order.

Batteries When the battery is nearly discharged, the ALARM indicator blinks and the message “BATT LOW” appears on the Programming Console. When this occurs, replace the battery within one week to avoid loss of data. The battery comes with its own connector as a set. To replace the Battery Set follow the steps below. The entire replacement must be completed within five minutes to ensure that the data will not be lost.

55

Page 62

Appendix A

Inspection and Maintenance 1.

Turn OFF the power to the PC. (If the power was not already ON, turn the power ON for at least one minute before turning the power OFF.)

2.

Remove the cover from the battery compartment.

3.

Remove the old Battery Set.

4.

Install the new Battery Set as shown below.

Battery connector

Battery Set

5.

Replace the cover of the battery compartment.

6.

When a Programming Console is mounted to the CPU after the battery has been replaced, “BATT LOW” will be displayed. This message can be cleared by pressing CLR, FUN, MONTR, or just turning the power to the PC OFF and the ON again to clear the error message on the Programming Console.

Note

56

The service life of the battery is four years at 25°C.

Page 63

B

Specifications Power Supply Model

3G2A5-PS221-E/222-E/223-E

3G2A5-PS212-E/213-E

Supply Voltage

100 to 120/200 to 240 VAC (selectable) 50/60 Hz

24 VDC

Operating Voltage Range

85 to 132/170 to 264 VAC

20.4 to 26.4 VDC

Power Consumption

150 VA max.

55 W max.

Output Capacity

PS221: 7 A 5 VDC PS223: 120 A 5 VDC PS222: 7 A 5 VDC

PS213: 9 A 5 VDC PS212: 7 A 5 VDC

24 VDC Output*

0.8 A 24 VDC ±10%

Not provided

Insulation Resistance

5 MΩ min. (at 500 VDC) between AC terminals

Dielectric Strength**

1,500 VAC 50/60 Hz for 1 minute (between AC and GR terminals) leakage current 10 m A max.

Noise Immunity

1,000 Vp-p, pulse width: 1 µs, rise time: 1 ns

Vibration Resistance

Mechanical durability: 10 to 25 Hz, 2 mm double amplitude, in X, Y, and Z directions, for 2 hours each Electrical durability: 16.7 Hz, 1 mm double amplitude, in X, Y, and Z directions, for 10 minutes each 98 m/s2 in downward direction, 3 times

Shock

Humidity

Operating: 0° to 55°C Storage: –20° to 65°C 35% to 85% RH (without condensation)

Atmosphere

Must be free from corrosive gasses

Grounding

Less than 100 Ω

Structure

Panel-mounted

Weight

8 kilograms max.

Ambient Temperature

500 VAC 50/60 Hz for 1 minute (between DC and GR terminals) leakage current 1 mA max.

*This output is not provided on Model PS223-E. **When performing the dielectric strength test or the insulation resistance test be sure to disconnect the LG terminals from the GR (ground) terminals to protect the program and internal parts from damage.

57

Page 64

Appendix B

Specifications CPU Specifications Programming Method

Ladder diagram

Instruction Length

1 address/instruction, (1 to 4 words/instruction)

Number of Instructions

71 (12 basic instructions + 59 special instructions)

Execution Time

3 to 8 µs (basic instructions)/22 to 504 µs (special instructions)

Memory Capacity

24K words

I/O bits

512 (0000 through 3115)

IR bits

416 (3200 through 5715)

SR bits

88 (5800 through 6307)

TR bits

8 (0 through 7)

HR bits

512 (0000 through 3115)

LR bits

512 (0000 through 3115) PC Link: max. configuration 8 PCs

Timers/Counters

128 (TIM/CNT 000 through 127) TIMs: 0 through 999.9 s TIMHs: 0 through 99.99 s CNT: 0 through 9999 counts 512 (0000 through 511) 16 bits/word

DM words Control Input Signal

START INPUT (in RUN mode, PC operates when contacts are closed and stops when contacts are opened) Input Voltage: 24 mA 24 VDC

Control Output Signal

RUN INPUT (Contacts are closed while PC is in RUN mode) Max. switching capacity: 2 A 250 VAC (resistive load) 0.5 A 250 VAC (inductive load, cos of phase angle= 0.4) 2 A 24 VDC Status of HR bits, preset value of counters (CNT), and contents of data memory (DM) are retained during power failure. Length of memory protection depends on the Memory Pack model being used (refer to Section 2-8 Memory Packs).

Memory Protection

Battery Life

4 years at 25°C, battery life is shortened at temperatures higher than 25°C. Replace battery with new one within 1 week when ALARM indicator blinks.

Self-diagnostic Functions

CPU failure (watchdog timer) Battery failure Cycle time error Memory failure I/O bus failure, etc.

Program Check

Program check (executed on start of RUN operation): END missing JMP-JME error Coil duplication Circuit error DIFU/DIFD over error IL/ILC error (Program can be checked by Programming Console or GPC.)

58

Page 65

Appendix B

Specifications DC Input Units 3G2A5-ID112

3G2A5-ID213

Input Voltage

5 to 12 VAC)10%/*15%

12 to 24 VAC)10%/*15%

Input Impedance

560 Ω

2.2 kΩ

Input Current

16 mA typical (at 12 VDC)

10 mA typical (at 24 VDC)

ON Voltage

4.0 VDC min.

10.2 VDC min.

OFF Voltage

1.5 VDC max.

3.0 VDC max.

ON Response Time

1.5 ms max.

1.5 ms max.

OFF Response Time

1.5 ms max.

1.5 ms max.

No. of Points

16 (8 points/common, 2 circuits)

16 (8 points/common, 2 circuits)

Internal Current Consumption

10 mA 5 VDC max.

20 mA 5 VDC max.

Weight

450 grams max.

450 grams max.

Circuit Configuration COM

COM 6.8 kΩ

IN 00 560 Ω to IN 06 IN 07

Internal Circuit

COM IN 08 to 560 Ω IN 14 IN 15

6.8 kΩ

IN 00 to 2.2 kΩ IN 06 IN 07

1.8 kΩ

Internal Circuit

COM IN 08 to 2.2 kΩ IN 14 IN 15

1.8 kΩ

Two-wire sensors cannot be connected. Terminal Connections

0

5 to 12 VDC +

5 to 12 VDC +

Dimensions

0 1 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 NC 18 NC 19

0

A-shape

0 1 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 NC 18 NC 19 1 2

1 2

12 to 24 VDC +

12 to 24 VDC +

A-shape

59

Page 66

Appendix B

Specifications DC Input Units Continued 3G2A5-ID212 (Input)

3G2A5-ID212 (Output)

Input Voltage

24 VDC)10%/*15%

Max. Switching Capacity

0.1 A 24 VDC)10%/*15%

Input Impedance

2.2 kΩ

Leakage Current

0.1 mA max.

Input Current

10 mA typical (at 24 VDC)

Residual Voltage

1.5 V max.

ON Voltage

10.2 VDC min.

ON Response Time

0.2 ms max.

OFF Voltage

3.0 VDC max.

OFF Response Time

0.3 ms max.

ON Response Time

1.5 ms max.

Power for External Supply

24 VDC ±10 %

OFF Response Time

1.5 ms max.

Terminal Connections

Circuit Configuration COM (24 V)

A 560

Ω

DATA 0

2.2 kΩ to

560

Ω DATA 7 24 V

2.2 kΩ

STB 0 to STB 7

Internal Circuit

COM (0 V)

Internal Circuit

+ 24 VDC

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

DATA 0 DATA 1 DATA 2 DATA 3 DATA 4 DATA 5 DATA 6 DATA 7 COM (24 V) STB 0 STB 1 STB 2 STB 3 STB 4 STB 5 STB 6 STB 7 COM (0 V) 24 V NC

Refer to page 66 for connection. No. of Points

64

Internal Current Consumption

300 mA 5 VDC max.

Weight

450 grams max.

Dimensions

A-shape

60

Page 67

Appendix B

Specifications DC Input Units Continued 3G2A5-ID215

3G2A5-ID218

Input Voltage

12 to 24 VDC)10%/*15%

Input Impedance

2.2 kΩ

Input Current

10 mA typical (at 24 VDC)

ON Voltage

10.2 VDC min.

OFF Voltage

3.0 VDC max.

ON Response Time

15 ms max.

1.5 ms max.

OFF Response Time

15 ms max.

1.5 ms max.

No. of Points

32 (8 points/common, 4 circuits)

Internal Current Consumption

160 mA 5 VDC max.

Weight

450 grams max.

Circuit Configuration

2.2 kΩ

IN 00 to IN 07

I

ID215: 680 Ω ID218: 750 Ω

COM IN 08 to IN 15 COM

2.2 kΩ

IN 00 to IN 07

II

Internal Circuit

ID215: 680 Ω ID218: 750 Ω

COM IN 08 to IN 15 COM

Terminal Connections

I to 24 VDC

+

+ to 24 VDC +

Dimensions

+

A

B 0

II

0 0 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 7 7 7 7 COM COM 8 8 8 8 9 9 9 9 10 10 10 10 11 11 11 11 12 12 12 12 13 13 13 13 14 14 14 14 15 15 15 15 16 16 COM COM 17 17 18 NC NC 18 0

+

12 to 24 VDC +

+

12 to 24 VDC +

B-shape

61

Page 68

Appendix B

Specifications DC Input Units Continued

3G2A5-ID219 Input Voltage

24 VDC)10%/*15%

Input Impedance

3.3 kΩ

Input Current

7 mA typical (at 24 VDC)

ON Voltage

16.0 VDC min.

OFF Voltage

5.0 VDC max.

ON Response Time

1.5 ms max.

OFF Response Time

1.5 ms max.

No. of Points

64 (8 points/common, 8 circuits) (No. of contacts that can be turned ON changes depending on ambient temperature. See the characteristic data below.)

Internal Current Consumption Weight

600 grams max.

Circuit Configuration

I

II

IN 00 to IN 07 COM IN 08 to IN 15 COM IN 00 COM IN 08

III

COM IN 00 COM IN 08

IV

COM IN 00 COM IN 08

(Points) 60 3.3 kΩ

+

24 VDC

Dimensions

62

D-shape

Internal Circuit

No. of points 40 that can be 30 turned ON 20

Temperature is 38°C when 64 points can be turned ON.

10

3.3 kΩ

0 0 10 20 Temperature

II

24 VDC

Up to 35 points can be turned ON at 55°C.

50

560 Ω

Terminal Connections

+

No. of points that can be turned ON vs. temperature

560 Ω

COM

B A 20 20 NC 19 19 NC COM 18 18 15 15 17 17 14 14 16 16 13 13 15 15 12 12 14 14 11 11 13 13 10 10 12 12 9 11 11 9 8 10 10 8 COM COM 9 9 7 7 8 8 6 6 7 7 5 5 6 6 4 4 5 5 3 4 4 3 2 3 3 2 1 1 2 2 0 0 1 1

NC NC COM

30

A B IV 1 1 0 1 2 2 1 2 3 3 2 3 4 4 3 4 5 5 4 5 6 6 5 6 7 7 6 7 8 8 7 COM 9 9 COM 8 10 10 8 9 11 11 9 10 12 12 10 11 13 13 11 12 14 14 12 13 15 15 13 14 16 16 14 15 17 17 15 COM 18 18 COM NC 19 19 NC NC 20 20 NC

40 50 60 (°C)

III

0

I 24 VDC + +

24 VDC

24 VDC + +

24 VDC

24 VDC +

24 VDC +

Page 69

Appendix B

Specifications DC Input Units Continued

3G2A5-ID114 Input Voltage

12 VDC)10%/*15%

Input Impedance

1.6 kΩ

Input Current

7 mA typical (at 12 VDC)

ON Voltage

8.0 VDC min.

OFF Voltage

3.0 VDC max.

ON Response Time

1.5 ms max.

OFF Response Time

1.5 ms max.

No. of Points

64 (8 points/common, 8 circuits) (No. of contacts that can be turned ON changes depending on ambient temperature. See the characteristic data below.)

Internal Current Consumption

340 mA 5 VDC max.

Weight

600 grams max.

Circuit Configuration

I

II

IN 00 to IN 07 COM IN 08 to IN 15 COM IN 00 COM IN 08

III

COM IN 00 COM IN 08

IV

COM IN 00 COM IN 08

(Points) 60

1.5 kΩ

Up to 35 points can be turned ON at 55°C.

50

Internal Circuit

390 Ω

No. of points 40 that can be 30 turned ON 20

1.5 kΩ

Temperature is 38°C when 64 points can be turned ON.

10 0

0 10 20 Temperature

Terminal Connections II

+

12 VDC

+

12 VDC

Dimensions

No. of points that can be turned ON vs. temperature

390 Ω

COM

B A 20 20 NC 19 19 NC COM 18 18 15 15 17 17 14 14 16 16 13 13 15 15 12 12 14 14 11 11 13 13 10 12 12 10 9 11 11 9 8 8 10 10 COM COM 9 9 7 7 8 8 6 6 7 7 5 5 6 6 4 4 5 5 3 4 4 3 2 3 3 2 1 1 2 2 0 0 1 1

NC NC COM

30

A B IV 1 1 0 1 2 2 1 2 3 3 2 3 4 4 3 4 5 5 4 5 6 6 5 6 7 7 6 7 8 8 7 COM 9 9 COM 8 10 10 8 9 11 11 9 10 12 12 10 11 13 13 11 12 14 14 12 13 15 15 13 14 16 16 14 15 17 17 15 COM 18 18 COM NC 19 19 NC NC 20 20 NC

40 50 60 (°C)

III

0

I 12 VDC + +

12 VDC

12 VDC + +

12 VDC

12 VDC +

12 VDC +

D-shape

63

Page 70

Appendix B

Specifications DC Input Units Continued 3G2A5-ID218CN Input Voltage

12 to 24 VAC)10%/*15%

Input Impedance

2.2 kΩ

Input Current

10 mA typical (at 24 VDC)

ON Voltage

10.2 VDC min.

OFF Voltage

3.0 VDC max.

ON Response Time OFF Response Time No. of Points

1.5 ms max.

Internal Current Consumption Weight

200 mA 5 VDC max.

1.5 ms max. 32 (8 points/common, 4 circuits)

450 grams max.

Circuit Configuration

2.2 kΩ

IN 00 to

I

IN 08 to IN 15 COM

Ω

Internal Circuit

2.2 kΩ

IN 00 to

II

470

0.047 µF

IN 07 COM

470

0.047 µF

IN 07 COM

Ω

IN 08 to IN 15 COM

Terminal Connections

B 1 8 1 2 9 1 2 3 10 2 3 4 11 3 4 5 12 4 5 6 13 5 6 7 14 6 7 8 15 7 8 COM 9 COM 9 10 NC NC 10 11 NC NC 11 12 NC NC 12 A

0

+ +

Dimensions

64

E-shape, with no 4-terminal block

12 to 24 VDC

+ +