The text of a manual · part 7 of 12
C500 Programmable Controller Installation Guide, pages 61 to 70
Pages 61 to 70 of 114
The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C500-BI081/ 3G2A5-BI081 and Omron C500-OD219
Page 61
Appendix A
Inspection and Maintenance 3.
Remove the screws that mount the Output Unit to the Backplane. Pulling the Unit toward you, remove the Output Unit from the Backplane.
4.
There are eight screws on each side of the Output Unit. Remove these screws to detach the case from the cover.
5.
Pull out the printed circuit board.
6.
Insert a new fuse.
7.
Reassemble in reverse order.
Output Unit Relays To replace a Relay in an Output Unit, follow the steps below. 1.
Turn OFF the power to the PC.
2.
Detach the terminal block from the Output Unit, by removing the screws located at the top and bottom of the terminal block. Mounting screws Located at the top and bottom.
Terminal block mounting screws Located at the top and bottom of the terminal block. Cover mounting screws (8)
3.
Remove the screws that mount the Output Unit to the Backplane. Pulling the Unit toward you remove the Output Unit from the Backplane.
4.
There are eight screws on each side of the Output Unit. Remove these screws to detach the case from the cover.
5.
Pull out the printed circuit board. Place the Relays on the circuit board.
6.
Use the Relay Puller to pull out the Relay. Insert a new Relay.
7.
Reassemble in reverse order.
Batteries When the battery is nearly discharged, the ALARM indicator blinks and the message “BATT LOW” appears on the Programming Console. When this occurs, replace the battery within one week to avoid loss of data. The battery comes with its own connector as a set. To replace the Battery Set follow the steps below. The entire replacement must be completed within five minutes to ensure that the data will not be lost.
55
Page 62
Appendix A
Inspection and Maintenance 1.
Turn OFF the power to the PC. (If the power was not already ON, turn the power ON for at least one minute before turning the power OFF.)
2.
Remove the cover from the battery compartment.
3.
Remove the old Battery Set.
4.
Install the new Battery Set as shown below.
Battery connector
Battery Set
5.
Replace the cover of the battery compartment.
6.
When a Programming Console is mounted to the CPU after the battery has been replaced, “BATT LOW” will be displayed. This message can be cleared by pressing CLR, FUN, MONTR, or just turning the power to the PC OFF and the ON again to clear the error message on the Programming Console.
Note
56
The service life of the battery is four years at 25°C.
Page 63
B
Specifications Power Supply Model
3G2A5-PS221-E/222-E/223-E
3G2A5-PS212-E/213-E
Supply Voltage
100 to 120/200 to 240 VAC (selectable) 50/60 Hz
24 VDC
Operating Voltage Range
85 to 132/170 to 264 VAC
20.4 to 26.4 VDC
Power Consumption
150 VA max.
55 W max.
Output Capacity
PS221: 7 A 5 VDC PS223: 120 A 5 VDC PS222: 7 A 5 VDC
PS213: 9 A 5 VDC PS212: 7 A 5 VDC
24 VDC Output*
0.8 A 24 VDC ±10%
Not provided
Insulation Resistance
5 MΩ min. (at 500 VDC) between AC terminals
Dielectric Strength**
1,500 VAC 50/60 Hz for 1 minute (between AC and GR terminals) leakage current 10 m A max.
Noise Immunity
1,000 Vp-p, pulse width: 1 µs, rise time: 1 ns
Vibration Resistance
Mechanical durability: 10 to 25 Hz, 2 mm double amplitude, in X, Y, and Z directions, for 2 hours each Electrical durability: 16.7 Hz, 1 mm double amplitude, in X, Y, and Z directions, for 10 minutes each 98 m/s2 in downward direction, 3 times
Shock
Humidity
Operating: 0° to 55°C Storage: –20° to 65°C 35% to 85% RH (without condensation)
Atmosphere
Must be free from corrosive gasses
Grounding
Less than 100 Ω
Structure
Panel-mounted
Weight
8 kilograms max.
Ambient Temperature
500 VAC 50/60 Hz for 1 minute (between DC and GR terminals) leakage current 1 mA max.
*This output is not provided on Model PS223-E. **When performing the dielectric strength test or the insulation resistance test be sure to disconnect the LG terminals from the GR (ground) terminals to protect the program and internal parts from damage.
57
Page 64
Appendix B
Specifications CPU Specifications Programming Method
Ladder diagram
Instruction Length
1 address/instruction, (1 to 4 words/instruction)
Number of Instructions
71 (12 basic instructions + 59 special instructions)
Execution Time
3 to 8 µs (basic instructions)/22 to 504 µs (special instructions)
Memory Capacity
24K words
I/O bits
512 (0000 through 3115)
IR bits
416 (3200 through 5715)
SR bits
88 (5800 through 6307)
TR bits
8 (0 through 7)
HR bits
512 (0000 through 3115)
LR bits
512 (0000 through 3115) PC Link: max. configuration 8 PCs
Timers/Counters
128 (TIM/CNT 000 through 127) TIMs: 0 through 999.9 s TIMHs: 0 through 99.99 s CNT: 0 through 9999 counts 512 (0000 through 511) 16 bits/word
DM words Control Input Signal
START INPUT (in RUN mode, PC operates when contacts are closed and stops when contacts are opened) Input Voltage: 24 mA 24 VDC
Control Output Signal
RUN INPUT (Contacts are closed while PC is in RUN mode) Max. switching capacity: 2 A 250 VAC (resistive load) 0.5 A 250 VAC (inductive load, cos of phase angle= 0.4) 2 A 24 VDC Status of HR bits, preset value of counters (CNT), and contents of data memory (DM) are retained during power failure. Length of memory protection depends on the Memory Pack model being used (refer to Section 2-8 Memory Packs).
Memory Protection
Battery Life
4 years at 25°C, battery life is shortened at temperatures higher than 25°C. Replace battery with new one within 1 week when ALARM indicator blinks.
Self-diagnostic Functions
CPU failure (watchdog timer) Battery failure Cycle time error Memory failure I/O bus failure, etc.
Program Check
Program check (executed on start of RUN operation): END missing JMP-JME error Coil duplication Circuit error DIFU/DIFD over error IL/ILC error (Program can be checked by Programming Console or GPC.)
58
Page 65
Appendix B
Specifications DC Input Units 3G2A5-ID112
3G2A5-ID213
Input Voltage
5 to 12 VAC)10%/*15%
12 to 24 VAC)10%/*15%
Input Impedance
560 Ω
2.2 kΩ
Input Current
16 mA typical (at 12 VDC)
10 mA typical (at 24 VDC)
ON Voltage
4.0 VDC min.
10.2 VDC min.
OFF Voltage
1.5 VDC max.
3.0 VDC max.
ON Response Time
1.5 ms max.
1.5 ms max.
OFF Response Time
1.5 ms max.
1.5 ms max.
No. of Points
16 (8 points/common, 2 circuits)
16 (8 points/common, 2 circuits)
Internal Current Consumption
10 mA 5 VDC max.
20 mA 5 VDC max.
Weight
450 grams max.
450 grams max.
Circuit Configuration COM
COM 6.8 kΩ
IN 00 560 Ω to IN 06 IN 07
Internal Circuit
COM IN 08 to 560 Ω IN 14 IN 15
6.8 kΩ
IN 00 to 2.2 kΩ IN 06 IN 07
1.8 kΩ
Internal Circuit
COM IN 08 to 2.2 kΩ IN 14 IN 15
1.8 kΩ
Two-wire sensors cannot be connected. Terminal Connections
0
5 to 12 VDC +
5 to 12 VDC +
Dimensions
0 1 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 NC 18 NC 19
0
A-shape
0 1 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 NC 18 NC 19 1 2
1 2
12 to 24 VDC +
12 to 24 VDC +
A-shape
59
Page 66
Appendix B
Specifications DC Input Units Continued 3G2A5-ID212 (Input)
3G2A5-ID212 (Output)
Input Voltage
24 VDC)10%/*15%
Max. Switching Capacity
0.1 A 24 VDC)10%/*15%
Input Impedance
2.2 kΩ
Leakage Current
0.1 mA max.
Input Current
10 mA typical (at 24 VDC)
Residual Voltage
1.5 V max.
ON Voltage
10.2 VDC min.
ON Response Time
0.2 ms max.
OFF Voltage
3.0 VDC max.
OFF Response Time
0.3 ms max.
ON Response Time
1.5 ms max.
Power for External Supply
24 VDC ±10 %
OFF Response Time
1.5 ms max.
Terminal Connections
Circuit Configuration COM (24 V)
A 560
Ω
DATA 0
2.2 kΩ to
560
Ω DATA 7 24 V
2.2 kΩ
STB 0 to STB 7
Internal Circuit
COM (0 V)
Internal Circuit
+ 24 VDC
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
DATA 0 DATA 1 DATA 2 DATA 3 DATA 4 DATA 5 DATA 6 DATA 7 COM (24 V) STB 0 STB 1 STB 2 STB 3 STB 4 STB 5 STB 6 STB 7 COM (0 V) 24 V NC
Refer to page 66 for connection. No. of Points
64
Internal Current Consumption
300 mA 5 VDC max.
Weight
450 grams max.
Dimensions
A-shape
60
Page 67
Appendix B
Specifications DC Input Units Continued 3G2A5-ID215
3G2A5-ID218
Input Voltage
12 to 24 VDC)10%/*15%
Input Impedance
2.2 kΩ
Input Current
10 mA typical (at 24 VDC)
ON Voltage
10.2 VDC min.
OFF Voltage
3.0 VDC max.
ON Response Time
15 ms max.
1.5 ms max.
OFF Response Time
15 ms max.
1.5 ms max.
No. of Points
32 (8 points/common, 4 circuits)
Internal Current Consumption
160 mA 5 VDC max.
Weight
450 grams max.
Circuit Configuration
2.2 kΩ
IN 00 to IN 07
I
ID215: 680 Ω ID218: 750 Ω
COM IN 08 to IN 15 COM
2.2 kΩ
IN 00 to IN 07
II
Internal Circuit
ID215: 680 Ω ID218: 750 Ω
COM IN 08 to IN 15 COM
Terminal Connections
I to 24 VDC
+
+ to 24 VDC +
Dimensions
+
A
B 0
II
0 0 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 7 7 7 7 COM COM 8 8 8 8 9 9 9 9 10 10 10 10 11 11 11 11 12 12 12 12 13 13 13 13 14 14 14 14 15 15 15 15 16 16 COM COM 17 17 18 NC NC 18 0
+
12 to 24 VDC +
+
12 to 24 VDC +
B-shape
61
Page 68
Appendix B
Specifications DC Input Units Continued
3G2A5-ID219 Input Voltage
24 VDC)10%/*15%
Input Impedance
3.3 kΩ
Input Current
7 mA typical (at 24 VDC)
ON Voltage
16.0 VDC min.
OFF Voltage
5.0 VDC max.
ON Response Time
1.5 ms max.
OFF Response Time
1.5 ms max.
No. of Points
64 (8 points/common, 8 circuits) (No. of contacts that can be turned ON changes depending on ambient temperature. See the characteristic data below.)
Internal Current Consumption Weight
600 grams max.
Circuit Configuration
I
II
IN 00 to IN 07 COM IN 08 to IN 15 COM IN 00 COM IN 08
III
COM IN 00 COM IN 08
IV
COM IN 00 COM IN 08
(Points) 60 3.3 kΩ
+
24 VDC
Dimensions
62
D-shape
Internal Circuit
No. of points 40 that can be 30 turned ON 20
Temperature is 38°C when 64 points can be turned ON.
10
3.3 kΩ
0 0 10 20 Temperature
II
24 VDC
Up to 35 points can be turned ON at 55°C.
50
560 Ω
Terminal Connections
+
No. of points that can be turned ON vs. temperature
560 Ω
COM
B A 20 20 NC 19 19 NC COM 18 18 15 15 17 17 14 14 16 16 13 13 15 15 12 12 14 14 11 11 13 13 10 10 12 12 9 11 11 9 8 10 10 8 COM COM 9 9 7 7 8 8 6 6 7 7 5 5 6 6 4 4 5 5 3 4 4 3 2 3 3 2 1 1 2 2 0 0 1 1
NC NC COM
30
A B IV 1 1 0 1 2 2 1 2 3 3 2 3 4 4 3 4 5 5 4 5 6 6 5 6 7 7 6 7 8 8 7 COM 9 9 COM 8 10 10 8 9 11 11 9 10 12 12 10 11 13 13 11 12 14 14 12 13 15 15 13 14 16 16 14 15 17 17 15 COM 18 18 COM NC 19 19 NC NC 20 20 NC
40 50 60 (°C)
III
0
I 24 VDC + +
24 VDC
24 VDC + +
24 VDC
24 VDC +
24 VDC +
Page 69
Appendix B
Specifications DC Input Units Continued
3G2A5-ID114 Input Voltage
12 VDC)10%/*15%
Input Impedance
1.6 kΩ
Input Current
7 mA typical (at 12 VDC)
ON Voltage
8.0 VDC min.
OFF Voltage
3.0 VDC max.
ON Response Time
1.5 ms max.
OFF Response Time
1.5 ms max.
No. of Points
64 (8 points/common, 8 circuits) (No. of contacts that can be turned ON changes depending on ambient temperature. See the characteristic data below.)
Internal Current Consumption
340 mA 5 VDC max.
Weight
600 grams max.
Circuit Configuration
I
II
IN 00 to IN 07 COM IN 08 to IN 15 COM IN 00 COM IN 08
III
COM IN 00 COM IN 08
IV
COM IN 00 COM IN 08
(Points) 60
1.5 kΩ
Up to 35 points can be turned ON at 55°C.
50
Internal Circuit
390 Ω
No. of points 40 that can be 30 turned ON 20
1.5 kΩ
Temperature is 38°C when 64 points can be turned ON.
10 0
0 10 20 Temperature
Terminal Connections II
+
12 VDC
+
12 VDC
Dimensions
No. of points that can be turned ON vs. temperature
390 Ω
COM
B A 20 20 NC 19 19 NC COM 18 18 15 15 17 17 14 14 16 16 13 13 15 15 12 12 14 14 11 11 13 13 10 12 12 10 9 11 11 9 8 8 10 10 COM COM 9 9 7 7 8 8 6 6 7 7 5 5 6 6 4 4 5 5 3 4 4 3 2 3 3 2 1 1 2 2 0 0 1 1
NC NC COM
30
A B IV 1 1 0 1 2 2 1 2 3 3 2 3 4 4 3 4 5 5 4 5 6 6 5 6 7 7 6 7 8 8 7 COM 9 9 COM 8 10 10 8 9 11 11 9 10 12 12 10 11 13 13 11 12 14 14 12 13 15 15 13 14 16 16 14 15 17 17 15 COM 18 18 COM NC 19 19 NC NC 20 20 NC
40 50 60 (°C)
III
0
I 12 VDC + +
12 VDC
12 VDC + +
12 VDC
12 VDC +
12 VDC +
D-shape
63
Page 70
Appendix B
Specifications DC Input Units Continued 3G2A5-ID218CN Input Voltage
12 to 24 VAC)10%/*15%
Input Impedance
2.2 kΩ
Input Current
10 mA typical (at 24 VDC)
ON Voltage
10.2 VDC min.
OFF Voltage
3.0 VDC max.
ON Response Time OFF Response Time No. of Points
1.5 ms max.
Internal Current Consumption Weight
200 mA 5 VDC max.
1.5 ms max. 32 (8 points/common, 4 circuits)
450 grams max.
Circuit Configuration
2.2 kΩ
IN 00 to
I
IN 08 to IN 15 COM
Ω
Internal Circuit
2.2 kΩ
IN 00 to
II
470
0.047 µF
IN 07 COM
470
0.047 µF
IN 07 COM
Ω
IN 08 to IN 15 COM
Terminal Connections
B 1 8 1 2 9 1 2 3 10 2 3 4 11 3 4 5 12 4 5 6 13 5 6 7 14 6 7 8 15 7 8 COM 9 COM 9 10 NC NC 10 11 NC NC 11 12 NC NC 12 A
0
+ +
Dimensions
64
E-shape, with no 4-terminal block
12 to 24 VDC
+ +