Page 71
Appendix B
Specifications AC/DC Input Units 3G2A5-IM211
3G2A5-IM212
Input Voltage
12 to 24 VAC/DC)10%/*15% 50/60 Hz
12 to 24 VAC/DC)10%/*15% 50/60 Hz
Input Impedance
1.8 Ω
2.2 kΩ
Input Current
10 mA typical (at 24 VDC)
10 mA typical (at 24 VDC)
ON Voltage
10.2 VDC min.
10.2 VDC min.
OFF Voltage
3.0 VDC max.
3.0 VDC max.
ON Response Time
15 ms max.
15 ms max.
OFF Response Time
15 ms max.
15 ms max.
No. of Points
16 (8 points/common, 2 circuits)
32 (8 points/common, 4 circuits)
Internal Current Consumption
10 mA 5 VDC max.
200 mA 5 VDC max.
Weight
450 grams max.
500 grams max.
Circuit Configuration
IN 00
IN 00 to
1.8 kΩ
2.2 kΩ 680 Ω
IN 07 to 1.8 kΩ
IN 06 IN 07 COM IN 08
I
COM IN 08 to IN 15 COM
Internal Circuit
1.8 kΩ
Internal Circuit
IN 00
2.2 kΩ 680 Ω to to
IN 07
1.8 kΩ
IN 14 IN 15 COM
II
COM IN 08 to IN 15 COM
Terminal Connections
0
0 1 2 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 NC 18
+
12 to 24 VAC/VDC +
~
+
12 to 24 VAC/VDC +
~
NC
Dimensions
A-shape
A
I
1
0
0 1 2 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 NC 18 1
+ ~ + 12 to 24 VAC/VDC
+ ~ + 12 to 24 VAC/VDC
B 0
0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 18 NC
II
+ ~ + 12 to 24 VAC/VDC
+ ~ + 12 to 24 VAC/VDC
19
A-shape
65
Page 72
Appendix B
Specifications DC Input Unit 3G2A5-ID212
In the case where a large number of bits must be controlled, an ID212 DC Input Unit can simplify wiring by controlling up to 64 bits through only 16 points. Using digital switches or a specially wired keyboard, different combinations of points can access specific bits and words. Two examples of connections using digital switches or a keyboard are given.
Connection Example 1 (Keyboard) The table below shows how the ID212 DC Input Unit can be wired using a specially wired keyboard. For example, if A on the keyboard is pressed, the combination of DATA0 and STB 9 turn ON bit 00, word n. Similarly, the combination of DATA 7 and STB 7 turn ON bit 15, word n+3. The value of word n depends on where the Unit is mounted on the Rack. For details, refer to the C500 Operation Manual.
A
0
DATA 0
1
DATA 1
C
2
DATA 2
D
3
DATA 3
4
DATA 4
X
5
DATA 5
Y
6
DATA 6
7
DATA 7
8
COM (24 V)
9
STB 0
10
STB 1
11
STB 2
12
STB 3
13
STB 4
14
STB 5
15
STB 6
16
STB 7
17
COM (0 V)
B
E
Z
+
24 VDC 18 19
24 VDC NC
The table below shows the combinations made possible when the keyboard is wired as shown in the figure above. Point Number
15
14
13
12 word n
11
10
09
08
07
06
05
04
03
02
01
00
E
D
C
B
A word n + 1 word n + 2 word n + 3
Z
Y
X
Note
66
Because the DC Input Unit is operated on an extremely small current, make sure there is adequate distance between the DC Input Unit wires and high-tension equipment or power lines. If this cannot
Page 73
Appendix B
Specifications be avoided, use shielded cables when wiring the DC Input Unit. Be sure to keep the total length of the wires less than 10 m.
Connection Example 2 (Digital Switches) This example shows how the ID212 DC Input Unit can be wired using digital switches. Just as the keys on the keyboard can access different combinations of words and bits, the digital switches can access different combinations of words and bits. For example, the combination of switch no. 1 and point 00 access word bit 00, word n. However, for the sake of simplicity the figure below shows the digital switches wired to control 32 bits instead of 64 bits as was shown in Example 1. Wire STB 4, STB 5, STB 6, and STB 7 to access an additional 32 bits.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 +
16 17
24 VDC
18 19
DATA 0 DATA 1 DATA 2 DATA 3 DATA 4 DATA 5 DATA 6 DATA 7 COM (+24) STB 0 STB 1 STB 2 STB 3 STB 4 STB 5 STB 6 STB 7 COM (0 V) +24 VDC NC
D C B A COM
Switch no.
-
-
-
-
-
-
-
-
8
7
6
5
4
3
2
1
+
+
+
+
+
+
+
+
8
7
6
5
4
3
2
1
The table below shows the combinations made possible when the digital switches are wired as shown in the figure above. Point Number
15 word n
14
13
12
11
Switch no. 4 0
1
0
10
09
08
07
Switch no. 3 0
0
0
1
06
05
1
0
0
1
STB 1 word n + 1 word n + 1
0
0
Switch no. 7 0 STB 3
03
02
01
00
Switch no. 1 1
0
0
0
1
STB 0
Switch no. 8 1
04
Switch no. 2
0
1
1
Switch no. 6 1
0
1
1
Switch no. 5 0
0
1
0
1
STB 2
67
Page 74
Appendix B
Specifications Timing
These pulses are input as data to bits 0 through 7 of word n. Data 0 through 7 4 ms STB 0 STB 1 STB 2 STB 3 STB 4 STB 5 STB 6 STB 7 32 ms
DC Output Unit 3G2A5-OD211 By using the OD211 DC Output Unit, a large number of bits can be controlled through only 16 points. Just like the ID211 DC Input Unit, different combinations of points can access bits and words to control different outputs. Using this type of Unit can simplify wiring when many bits must be controlled. Up to 64 bits can be accessed. Because the output data is positive logic, the terminal output goes high when the output data is logical 1. The strobe output is negative logic, so when a signal is output, the corresponding terminal goes low. Use positive logic output devices for the load of this Unit. The strobe output is cyclically and automatically output. 24 k
Ω1W
Ω1W
24 k
24 VDC
6 5 4 3 7 1
11
Display no.
68
8
7
6
5
4
3
2
1
0
DATA 0
1
DATA 1
2
DATA 2
3
DATA 3
4
DATA 4
5
DATA 5
6
DATA 6
7
DATA 7
8
CON (0 V)
9
STB 0
10
STB 1
11
STB 2
12
STB 3
13
STB 4
14
STB 5
15
STB 6
16
STB 7
17
CON (0 V)
18
24 VDC
19
NC
Page 75
Appendix B
Specifications
The table below shows the combinations made possible when the display is wired as shown in the figure on the preceding page. The value of word n depends on where the Unit is mounted on the Rack. For details, refer to the C500 Operation Manual. Point Number
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Data Number
07
06
05
04
03
02
01
00
07
06
05
04
03
02
01
00
0
0
1
0
0
0 word n
Display no. 4 0
1
0
Display no. 3 0
1
Display no. 2 0
1
STB 1 word n + 1
0
0
Display no. 7 0
0
1
1
Display no. 6 1
0
1
STB 3
Note
0
0
1
STB 0
Display no. 8 1
Display no. 1
1
Display no. 5 0
0
1
0
1
STB 2
Because the DC Input Unit is operated on an extremely small current, make sure there is adequate distance between the DC Input Unit wires and high-tension equipment or power lines. If this cannot be avoided, use shielded cables when wiring the DC Input Unit. Be sure to keep the total length of the wires less than 10 m.
Timing The following timing chart illustrates the operation of the Output Unit when wired as shown on the previous page.
Data 0 Data 1 Data 2 Data 3 Data 4 Data 5 Data 6 Data 7 1 ms
STB 0
2 ms
1 ms
STB 1 STB 2 STB 3 STB 4 STB 5 STB 6 STB 7 4 ms 32 ms
Data of bits 0 through 7 of word n are output as these pulses.
69
Page 76
Appendix B
Specifications TTL Input Units 3G2A5-ID501CN Input Voltage
5 VDC ±10%
Input Impedance
1 kΩ
Input Current
3.5 mA typical (at 24 VDC)
ON Voltage
3 VDC min.
OFF Voltage
1 VDC max.
ON Response Time OFF Response Time No. of Points
1.5 ms max.
Internal Current Consumption Weight
200 mA 5 VDC max.
1.5 ms max. 32 (8 points/common, 4 circuits)
450 grams max.
Circuit Configuration
1 kΩ
IN 00 to
I
3.3 kΩ
IN 07 COM IN 08 to IN 15 COM
1 kΩ
IN 00 to
II
Internal Circuit
3.3 kΩ
IN 07 COM IN 08 to IN 15 COM
Terminal Connections
B 1 8 1 2 9 1 2 3 10 2 3 4 11 3 4 5 12 4 5 6 13 5 6 7 14 6 7 8 15 7 8 9 COM COM 9 10 NC NC 10 11 NC 11 NC 12 NC NC 12 A
5 VDC
+
Use a synchronous TTL buffer. (TTL/LS-TTL/CMOS buffer) IN
1 kΩ
+ 3.3 kΩ COM
Dimensions
70
5 VDC
0
E-shape, with no 4-terminal block
+ +
Page 77
Appendix B
Specifications Triac Output Units 3G2A5-OA121
3G2A5-OA222
Max. switching Capacity
1 A 132 VAC, 50/60 Hz (4 A/common, 5 A/Unit)
1 A 250 VAC, 50/60 Hz (4 A/common, 5 A/Unit)
Min. switching Capacity
10 mA (resistive load) 40 mA (inductive load) 10 VAC
10 mA (resistive load) 40 mA (inductive load) 10 VAC
Leakage Current
3 mA (100 VAC) max.
3 mA (100 VAC) max., 6 mA (200 VAC) max.
Residual Voltage
1.2 V max.
1.2 V max.
ON Response Time
1 ms max.
1 ms max.
OFF Response Time 1/2 of load frequency max.
1/2 of load frequency max.
No. of Points
16 (8 points/common, 2 circuits)
16 (8 points/common, 2 circuits)
Internal Current Consumption
300 mA 5 VDC max.
300 mA 5 VDC max.
Fuse Capacity
5 A 250 V (two fuses)
5 A 250 V (two fuses)
Weight
500 grams max.
500 grams max.
Circuit Configuration
OUT 00
OUT 00
22
Ω 0.022
Internal Circuit
22
Ω to
µF
Fuse/fuse blowout detection circuit
0.022
OUT 06 OUT 07 COM
Internal Circuit
µF
Fuse/fuse blowout detection circuit
OUT 08
0.022
The fuse used in this diagram is 5 A 250 V 6.35 dia. x 32.
Terminal Connections
L
132 VAC max. ~
132 VAC max. ~
Dimensions
A-shape
Ω to
0.022
OUT 14 OUT 15 COM to
µF
Fuse/fuse blowout detection circuit
OUT 14 OUT 15 COM
The fuse used in this diagram is 5 A 250 V 6.35 dia. x 32.
0
0 1 2 2 L 3 3 L 4 4 L 5 5 L 6 L 6 7 7 L COM 8 8 9 L 9 10 L 10 L 11 11 L 12 12 L 13 13 14 L 14 15 L 15 16 L COM 17 NC 18 NC 19 L
22
µF
Fuse/fuse blowout detection circuit
OUT 06 OUT 07 COM OUT 08
22
Ω to
L
250 VAC max. ~
250 VAC max. ~
0
0 1 L 2 3 3 L 4 4 L 5 5 L 6 6 L 7 7 L COM 8 8 9 L 9 10 L 10 11 L 11 12 L 12 13 L 13 L 14 14 L 15 15 16 L COM 17 NC 18 NC 19 L
1
1 2
A-shape
71
Page 78
Appendix B
Specifications Triac Output Units Continued 3G2A5-OA223
C500-OA225
Max. switching Capacity
1 A 250 VAC, 50/60 Hz (4 A/common, 5 A/unit)
1 A 250 VAC, 50/60 Hz (4 A/common, 5 A/unit)
Min. switching Capacity
10 mA (resistive load) 40 mA (inductive load) 10 VAC
10 mA (resistive load) 40 mA (inductive load) 10 VAC
Leakage Current
3 mA (100 VAC) max., 6 mA (200 VAC) max.
2 mA (100 VAC) max., 5 mA (200 VAC) max.
Residual Voltage
1.2 V max.
1.6 V max.
ON Response Time
1 ms max.
1 ms max.
OFF Response Time
1/2 of load frequency max.
1/2 of load frequency max.
No. of Points
24 (8 points/common, 3 circuits)
32 (8 points/common, 4 circuits)
Internal Current Consumption
450 mA 5 VDC max.
200 mA 5 VDC max.
Fuse Capacity
5 A 250 V (three fuses)
Not provided
Power for External Supply
–
320 mA 5 VDC ±10% max.
Weight
600 grams max.
600 grams max.
Circuit Configuration
OUT 00 to
OUT 00
* Fuse/fuse blowout detection circuit
Internal Circuit
OUT 06 OUT 07 COM OUT 04
OUT 14 OUT 15 COM OUT 00 to
Fuse/fuse blowout detection circuit x
Internal Circuit
Internal Circuit to Fuse/fuse blowout detection circuit to OUT 07 COM OUT 08
I
I to OUT 15 COM OUT 00 to
*
OUT 07 COM OUT 08
II
OUT 06 OUT 07 COM Fuse blowout output to
II
OUT 15 COM 24 VDC 0V
* G3S-201PL 24 VDC
Terminal Connections
B II A I 0 L 0 0 L 0 1 L 1 1 250 VAC L 1 2 2 L 250 VAC 2 max. L 2 3 3 L max. 3 L 3 4 4 L 4 ~ L 4 5 L ~ 5 5 L 5 6 L 6 6 L 7 L 6 7 7 L 7 COM 8 COM 8 9 NC 8 L 9 10 NC 9 L 10 250 VAC 11 NC 10 L 11 12 max. NC 11 L 12 13 NC 12 L 13 ~ 14 NC Fuse blowout 13 L 14 output 2A 15 NC 14 L 15 250 VAC/ 16 NC 15 L 16 24 VDC 17 NC COM 17 18 L 18 V ~ +
A
I
250 VAC ~ max.
0
II
L 0 0 L 1 L 1 1 L 1 2 2 L 2 L 2 3 3 L 3 3 L 4 L 4 4 4 L 5 L 5 5 5 L 6 L 6 6 6 L 7 L 7 7 7 L 8 COM COM 8 8 L 9 8 9 L 9 L 10 9 10 L 10 L 11 10 11 L 11 12 L 11 12 L 12 L 13 12 13 L 13 L 14 13 L 14 14 L 15 14 L 15 15 L 16 15 16 L COM 17 COM 24 VDC 17 0V 18 18 + 0
250 VAC ~ max.
B
24 VDC
Dimensions
72
C-shape
C-shape
250 VAC ~ max.
~
250 VAC max.
Page 79
Appendix B
Specifications C500-OA226 Max. Switching Capacity
1.2 A 250 VAC, 50/60 Hz (4 A/common, 5 A/unit)
Max. Surge Current
15 A for 100 ms pulse width, 30 A for 10 ms pulse width
Min. Switching Capacity
100 mA at 10 VAC, 50 mA at 24 VAC 10 mA at 100 VAC, 10 mA at 240 VAC
Leakage Current
1.5 mA (120 VAC, 60 Hz) max., 3.0 mA (240 VAC, 60 Hz) max.
Residual Voltage
1.5 VAC max. for 100 to 600 mA, 1.5 VAC for 50 to 100 mA, 5.0 VAC for 10 to 50 mA
ON Response Time
1 ms max.
OFF Response Time
1/2 of load frequency + 1 ms max.
No. of Points
16 (8 points/common, 2 circuits)
Internal Current Consumption
450 mA at 5 VDC max.
Fuse Capacity
5 A, 250 V; 6.35 mm dia. x 32 mm (two fuses)
Power for External Supply
–
Weight
600 grams max.
Circuit Configuration 47 Ω
47 Ω
0.022 µF
Internal Circuit
Fuse/fuse blowout detection circuit 47 Ω
47 Ω
0.022 µF
Dimensions to OUT 06 OUT 07 COM OUT 08 to
Fuse/fuse blowout detection circuit
Terminal Connections
OUT 00
OUT 14 OUT 15 COM
0 1 2 3 4 5 6 7
0 1 2 3 250 VAC 4 ~ max. 5 6 7 COM 8 8 L 9 9 L 10 10 L 11 11 L 12 12 250 VAC ~ L 13 13 L max. 14 14 L 15 15 L 16 COM 17 NC 18 NC 19 L L L L L L L L
A-shape
73
Page 80
Appendix B
Specifications Special Considerations for C500-OA225
The maximum current value allowed per point differs depending on the ambient temperature and the number of points per common that are ON simultaneously. The graph below shows the relationship between the allowable current per point and the number of points ON per common. Be sure not to exceed the values depicted in the graph. Environment temperature 25°C
1.0
Current value 0.8 per point (A) 0.6
40°C 55°C
0.4 0.2
0
1
2
3
4
5
6
7
8
Number of points per common that can be turned ON simultaneously.
Number of Points Per Common Turned ON Simultaneously The graph below shows the value of an surge current and the time it takes the current to level to a steady stream of current (current-carrying time). The curved line in the graph represents the maximum value of surge current at which the Unit can operate properly. It is suggested that when opening and closing a load with a large surge current, to keep the value of the surge current to half the value shown the graph (within the shaded area). Inrush 15 Current (A. Peak) 10
5
0 10
30
50
100 200
500
1,000
5.000
Current-carrying time (ms)
74