Page 71

Appendix B

Specifications AC/DC Input Units 3G2A5-IM211

3G2A5-IM212

Input Voltage

12 to 24 VAC/DC)10%/*15% 50/60 Hz

12 to 24 VAC/DC)10%/*15% 50/60 Hz

Input Impedance

1.8 Ω

2.2 kΩ

Input Current

10 mA typical (at 24 VDC)

10 mA typical (at 24 VDC)

ON Voltage

10.2 VDC min.

10.2 VDC min.

OFF Voltage

3.0 VDC max.

3.0 VDC max.

ON Response Time

15 ms max.

15 ms max.

OFF Response Time

15 ms max.

15 ms max.

No. of Points

16 (8 points/common, 2 circuits)

32 (8 points/common, 4 circuits)

Internal Current Consumption

10 mA 5 VDC max.

200 mA 5 VDC max.

Weight

450 grams max.

500 grams max.

Circuit Configuration

IN 00

IN 00 to

1.8 kΩ

2.2 kΩ 680 Ω

IN 07 to 1.8 kΩ

IN 06 IN 07 COM IN 08

I

COM IN 08 to IN 15 COM

Internal Circuit

1.8 kΩ

Internal Circuit

IN 00

2.2 kΩ 680 Ω to to

IN 07

1.8 kΩ

IN 14 IN 15 COM

II

COM IN 08 to IN 15 COM

Terminal Connections

0

0 1 2 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 NC 18

+

12 to 24 VAC/VDC +

~

+

12 to 24 VAC/VDC +

~

NC

Dimensions

A-shape

A

I

1

0

0 1 2 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 NC 18 1

+ ~ + 12 to 24 VAC/VDC

+ ~ + 12 to 24 VAC/VDC

B 0

0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 COM 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 COM 17 18 NC

II

+ ~ + 12 to 24 VAC/VDC

+ ~ + 12 to 24 VAC/VDC

19

A-shape

65

Page 72

Appendix B

Specifications DC Input Unit 3G2A5-ID212

In the case where a large number of bits must be controlled, an ID212 DC Input Unit can simplify wiring by controlling up to 64 bits through only 16 points. Using digital switches or a specially wired keyboard, different combinations of points can access specific bits and words. Two examples of connections using digital switches or a keyboard are given.

Connection Example 1 (Keyboard) The table below shows how the ID212 DC Input Unit can be wired using a specially wired keyboard. For example, if A on the keyboard is pressed, the combination of DATA0 and STB 9 turn ON bit 00, word n. Similarly, the combination of DATA 7 and STB 7 turn ON bit 15, word n+3. The value of word n depends on where the Unit is mounted on the Rack. For details, refer to the C500 Operation Manual.

A

0

DATA 0

1

DATA 1

C

2

DATA 2

D

3

DATA 3

4

DATA 4

X

5

DATA 5

Y

6

DATA 6

7

DATA 7

8

COM (24 V)

9

STB 0

10

STB 1

11

STB 2

12

STB 3

13

STB 4

14

STB 5

15

STB 6

16

STB 7

17

COM (0 V)

B

E

Z

+

24 VDC 18 19

24 VDC NC

The table below shows the combinations made possible when the keyboard is wired as shown in the figure above. Point Number

15

14

13

12 word n

11

10

09

08

07

06

05

04

03

02

01

00

E

D

C

B

A word n + 1 word n + 2 word n + 3

Z

Y

X

Note

66

Because the DC Input Unit is operated on an extremely small current, make sure there is adequate distance between the DC Input Unit wires and high-tension equipment or power lines. If this cannot

Page 73

Appendix B

Specifications be avoided, use shielded cables when wiring the DC Input Unit. Be sure to keep the total length of the wires less than 10 m.

Connection Example 2 (Digital Switches) This example shows how the ID212 DC Input Unit can be wired using digital switches. Just as the keys on the keyboard can access different combinations of words and bits, the digital switches can access different combinations of words and bits. For example, the combination of switch no. 1 and point 00 access word bit 00, word n. However, for the sake of simplicity the figure below shows the digital switches wired to control 32 bits instead of 64 bits as was shown in Example 1. Wire STB 4, STB 5, STB 6, and STB 7 to access an additional 32 bits.

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 +

16 17

24 VDC

18 19

DATA 0 DATA 1 DATA 2 DATA 3 DATA 4 DATA 5 DATA 6 DATA 7 COM (+24) STB 0 STB 1 STB 2 STB 3 STB 4 STB 5 STB 6 STB 7 COM (0 V) +24 VDC NC

D C B A COM

Switch no.

-

-

-

-

-

-

-

-

8

7

6

5

4

3

2

1

+

+

+

+

+

+

+

+

8

7

6

5

4

3

2

1

The table below shows the combinations made possible when the digital switches are wired as shown in the figure above. Point Number

15 word n

14

13

12

11

Switch no. 4 0

1

0

10

09

08

07

Switch no. 3 0

0

0

1

06

05

1

0

0

1

STB 1 word n + 1 word n + 1

0

0

Switch no. 7 0 STB 3

03

02

01

00

Switch no. 1 1

0

0

0

1

STB 0

Switch no. 8 1

04

Switch no. 2

0

1

1

Switch no. 6 1

0

1

1

Switch no. 5 0

0

1

0

1

STB 2

67

Page 74

Appendix B

Specifications Timing

These pulses are input as data to bits 0 through 7 of word n. Data 0 through 7 4 ms STB 0 STB 1 STB 2 STB 3 STB 4 STB 5 STB 6 STB 7 32 ms

DC Output Unit 3G2A5-OD211 By using the OD211 DC Output Unit, a large number of bits can be controlled through only 16 points. Just like the ID211 DC Input Unit, different combinations of points can access bits and words to control different outputs. Using this type of Unit can simplify wiring when many bits must be controlled. Up to 64 bits can be accessed. Because the output data is positive logic, the terminal output goes high when the output data is logical 1. The strobe output is negative logic, so when a signal is output, the corresponding terminal goes low. Use positive logic output devices for the load of this Unit. The strobe output is cyclically and automatically output. 24 k

Ω1W

Ω1W

24 k

24 VDC

6 5 4 3 7 1

11

Display no.

68

8

7

6

5

4

3

2

1

0

DATA 0

1

DATA 1

2

DATA 2

3

DATA 3

4

DATA 4

5

DATA 5

6

DATA 6

7

DATA 7

8

CON (0 V)

9

STB 0

10

STB 1

11

STB 2

12

STB 3

13

STB 4

14

STB 5

15

STB 6

16

STB 7

17

CON (0 V)

18

24 VDC

19

NC

Page 75

Appendix B

Specifications

The table below shows the combinations made possible when the display is wired as shown in the figure on the preceding page. The value of word n depends on where the Unit is mounted on the Rack. For details, refer to the C500 Operation Manual. Point Number

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Data Number

07

06

05

04

03

02

01

00

07

06

05

04

03

02

01

00

0

0

1

0

0

0 word n

Display no. 4 0

1

0

Display no. 3 0

1

Display no. 2 0

1

STB 1 word n + 1

0

0

Display no. 7 0

0

1

1

Display no. 6 1

0

1

STB 3

Note

0

0

1

STB 0

Display no. 8 1

Display no. 1

1

Display no. 5 0

0

1

0

1

STB 2

Because the DC Input Unit is operated on an extremely small current, make sure there is adequate distance between the DC Input Unit wires and high-tension equipment or power lines. If this cannot be avoided, use shielded cables when wiring the DC Input Unit. Be sure to keep the total length of the wires less than 10 m.

Timing The following timing chart illustrates the operation of the Output Unit when wired as shown on the previous page.

Data 0 Data 1 Data 2 Data 3 Data 4 Data 5 Data 6 Data 7 1 ms

STB 0

2 ms

1 ms

STB 1 STB 2 STB 3 STB 4 STB 5 STB 6 STB 7 4 ms 32 ms

Data of bits 0 through 7 of word n are output as these pulses.

69

Page 76

Appendix B

Specifications TTL Input Units 3G2A5-ID501CN Input Voltage

5 VDC ±10%

Input Impedance

1 kΩ

Input Current

3.5 mA typical (at 24 VDC)

ON Voltage

3 VDC min.

OFF Voltage

1 VDC max.

ON Response Time OFF Response Time No. of Points

1.5 ms max.

Internal Current Consumption Weight

200 mA 5 VDC max.

1.5 ms max. 32 (8 points/common, 4 circuits)

450 grams max.

Circuit Configuration

1 kΩ

IN 00 to

I

3.3 kΩ

IN 07 COM IN 08 to IN 15 COM

1 kΩ

IN 00 to

II

Internal Circuit

3.3 kΩ

IN 07 COM IN 08 to IN 15 COM

Terminal Connections

B 1 8 1 2 9 1 2 3 10 2 3 4 11 3 4 5 12 4 5 6 13 5 6 7 14 6 7 8 15 7 8 9 COM COM 9 10 NC NC 10 11 NC 11 NC 12 NC NC 12 A

5 VDC

+

Use a synchronous TTL buffer. (TTL/LS-TTL/CMOS buffer) IN

1 kΩ

+ 3.3 kΩ COM

Dimensions

70

5 VDC

0

E-shape, with no 4-terminal block

+ +

Page 77

Appendix B

Specifications Triac Output Units 3G2A5-OA121

3G2A5-OA222

Max. switching Capacity

1 A 132 VAC, 50/60 Hz (4 A/common, 5 A/Unit)

1 A 250 VAC, 50/60 Hz (4 A/common, 5 A/Unit)

Min. switching Capacity

10 mA (resistive load) 40 mA (inductive load) 10 VAC

10 mA (resistive load) 40 mA (inductive load) 10 VAC

Leakage Current

3 mA (100 VAC) max.

3 mA (100 VAC) max., 6 mA (200 VAC) max.

Residual Voltage

1.2 V max.

1.2 V max.

ON Response Time

1 ms max.

1 ms max.

OFF Response Time 1/2 of load frequency max.

1/2 of load frequency max.

No. of Points

16 (8 points/common, 2 circuits)

16 (8 points/common, 2 circuits)

Internal Current Consumption

300 mA 5 VDC max.

300 mA 5 VDC max.

Fuse Capacity

5 A 250 V (two fuses)

5 A 250 V (two fuses)

Weight

500 grams max.

500 grams max.

Circuit Configuration

OUT 00

OUT 00

22

Ω 0.022

Internal Circuit

22

Ω to

µF

Fuse/fuse blowout detection circuit

0.022

OUT 06 OUT 07 COM

Internal Circuit

µF

Fuse/fuse blowout detection circuit

OUT 08

0.022

The fuse used in this diagram is 5 A 250 V 6.35 dia. x 32.

Terminal Connections

L

132 VAC max. ~

132 VAC max. ~

Dimensions

A-shape

Ω to

0.022

OUT 14 OUT 15 COM to

µF

Fuse/fuse blowout detection circuit

OUT 14 OUT 15 COM

The fuse used in this diagram is 5 A 250 V 6.35 dia. x 32.

0

0 1 2 2 L 3 3 L 4 4 L 5 5 L 6 L 6 7 7 L COM 8 8 9 L 9 10 L 10 L 11 11 L 12 12 L 13 13 14 L 14 15 L 15 16 L COM 17 NC 18 NC 19 L

22

µF

Fuse/fuse blowout detection circuit

OUT 06 OUT 07 COM OUT 08

22

Ω to

L

250 VAC max. ~

250 VAC max. ~

0

0 1 L 2 3 3 L 4 4 L 5 5 L 6 6 L 7 7 L COM 8 8 9 L 9 10 L 10 11 L 11 12 L 12 13 L 13 L 14 14 L 15 15 16 L COM 17 NC 18 NC 19 L

1

1 2

A-shape

71

Page 78

Appendix B

Specifications Triac Output Units Continued 3G2A5-OA223

C500-OA225

Max. switching Capacity

1 A 250 VAC, 50/60 Hz (4 A/common, 5 A/unit)

1 A 250 VAC, 50/60 Hz (4 A/common, 5 A/unit)

Min. switching Capacity

10 mA (resistive load) 40 mA (inductive load) 10 VAC

10 mA (resistive load) 40 mA (inductive load) 10 VAC

Leakage Current

3 mA (100 VAC) max., 6 mA (200 VAC) max.

2 mA (100 VAC) max., 5 mA (200 VAC) max.

Residual Voltage

1.2 V max.

1.6 V max.

ON Response Time

1 ms max.

1 ms max.

OFF Response Time

1/2 of load frequency max.

1/2 of load frequency max.

No. of Points

24 (8 points/common, 3 circuits)

32 (8 points/common, 4 circuits)

Internal Current Consumption

450 mA 5 VDC max.

200 mA 5 VDC max.

Fuse Capacity

5 A 250 V (three fuses)

Not provided

Power for External Supply

–

320 mA 5 VDC ±10% max.

Weight

600 grams max.

600 grams max.

Circuit Configuration

OUT 00 to

OUT 00

* Fuse/fuse blowout detection circuit

Internal Circuit

OUT 06 OUT 07 COM OUT 04

OUT 14 OUT 15 COM OUT 00 to

Fuse/fuse blowout detection circuit x

Internal Circuit

Internal Circuit to Fuse/fuse blowout detection circuit to OUT 07 COM OUT 08

I

I to OUT 15 COM OUT 00 to

*

OUT 07 COM OUT 08

II

OUT 06 OUT 07 COM Fuse blowout output to

II

OUT 15 COM 24 VDC 0V

* G3S-201PL 24 VDC

Terminal Connections

B II A I 0 L 0 0 L 0 1 L 1 1 250 VAC L 1 2 2 L 250 VAC 2 max. L 2 3 3 L max. 3 L 3 4 4 L 4 ~ L 4 5 L ~ 5 5 L 5 6 L 6 6 L 7 L 6 7 7 L 7 COM 8 COM 8 9 NC 8 L 9 10 NC 9 L 10 250 VAC 11 NC 10 L 11 12 max. NC 11 L 12 13 NC 12 L 13 ~ 14 NC Fuse blowout 13 L 14 output 2A 15 NC 14 L 15 250 VAC/ 16 NC 15 L 16 24 VDC 17 NC COM 17 18 L 18 V ~ +

A

I

250 VAC ~ max.

0

II

L 0 0 L 1 L 1 1 L 1 2 2 L 2 L 2 3 3 L 3 3 L 4 L 4 4 4 L 5 L 5 5 5 L 6 L 6 6 6 L 7 L 7 7 7 L 8 COM COM 8 8 L 9 8 9 L 9 L 10 9 10 L 10 L 11 10 11 L 11 12 L 11 12 L 12 L 13 12 13 L 13 L 14 13 L 14 14 L 15 14 L 15 15 L 16 15 16 L COM 17 COM 24 VDC 17 0V 18 18 + 0

250 VAC ~ max.

B

24 VDC

Dimensions

72

C-shape

C-shape

250 VAC ~ max.

~

250 VAC max.

Page 79

Appendix B

Specifications C500-OA226 Max. Switching Capacity

1.2 A 250 VAC, 50/60 Hz (4 A/common, 5 A/unit)

Max. Surge Current

15 A for 100 ms pulse width, 30 A for 10 ms pulse width

Min. Switching Capacity

100 mA at 10 VAC, 50 mA at 24 VAC 10 mA at 100 VAC, 10 mA at 240 VAC

Leakage Current

1.5 mA (120 VAC, 60 Hz) max., 3.0 mA (240 VAC, 60 Hz) max.

Residual Voltage

1.5 VAC max. for 100 to 600 mA, 1.5 VAC for 50 to 100 mA, 5.0 VAC for 10 to 50 mA

ON Response Time

1 ms max.

OFF Response Time

1/2 of load frequency + 1 ms max.

No. of Points

16 (8 points/common, 2 circuits)

Internal Current Consumption

450 mA at 5 VDC max.

Fuse Capacity

5 A, 250 V; 6.35 mm dia. x 32 mm (two fuses)

Power for External Supply

–

Weight

600 grams max.

Circuit Configuration 47 Ω

47 Ω

0.022 µF

Internal Circuit

Fuse/fuse blowout detection circuit 47 Ω

47 Ω

0.022 µF

Dimensions to OUT 06 OUT 07 COM OUT 08 to

Fuse/fuse blowout detection circuit

Terminal Connections

OUT 00

OUT 14 OUT 15 COM

0 1 2 3 4 5 6 7

0 1 2 3 250 VAC 4 ~ max. 5 6 7 COM 8 8 L 9 9 L 10 10 L 11 11 L 12 12 250 VAC ~ L 13 13 L max. 14 14 L 15 15 L 16 COM 17 NC 18 NC 19 L L L L L L L L

A-shape

73

Page 80

Appendix B

Specifications Special Considerations for C500-OA225

The maximum current value allowed per point differs depending on the ambient temperature and the number of points per common that are ON simultaneously. The graph below shows the relationship between the allowable current per point and the number of points ON per common. Be sure not to exceed the values depicted in the graph. Environment temperature 25°C

1.0

Current value 0.8 per point (A) 0.6

40°C 55°C

0.4 0.2

0

1

2

3

4

5

6

7

8

Number of points per common that can be turned ON simultaneously.

Number of Points Per Common Turned ON Simultaneously The graph below shows the value of an surge current and the time it takes the current to level to a steady stream of current (current-carrying time). The curved line in the graph represents the maximum value of surge current at which the Unit can operate properly. It is suggested that when opening and closing a load with a large surge current, to keep the value of the surge current to half the value shown the graph (within the shaded area). Inrush 15 Current (A. Peak) 10

5

0 10

30

50

100 200

500

1,000

5.000

Current-carrying time (ms)

74