The text of a manual · part 5 of 12
C500 Programmable Controller Installation Guide, pages 41 to 50
Pages 41 to 50 of 114
The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C500-BI081/ 3G2A5-BI081 and Omron C500-OD219
Page 41
Section 4
System Connections Special I/O Units Unit A/D Converter Input
Model
Current Consumption (A)
3G2A5-AD001 to- AD005
0.3 each
3G2A5-AD006
0.75 each
3G2A5-AD007 C500-AD101
0.88
C500-AD501
1.2
3G2A5-DA001 to -DA005
0.55 each
C500-DA101
1.3
3G2A5-CT001
0.3
3G2A5-CT012
0.55
C500-CT041
1.0
Magnetic Card Reader
3G2A5-MGC01
1.0
PID
3G2A5-PID01-E
1.4
Position Control
3G2A5-NC103-E
Total 1.4
D/A Converter Output High-speed Counter
3G2A5-TU001-E 3G2A5-NC111-EV1
Total 1.0
3G2A5-TU001-E 3G2A5-NC221-E
Total 1.3
3G2A5-TU001 ASCII
C500-ASC04
0.5 each
ID Sensor
C500-IDS01-V2/IDS02-V1
0.4 each
C500-IDS21/IDS22 Ladder Program I/O
3G2A5-LDP01-V1
0.8
File Memory
C1000H-FMR11
0.35 each
C1000H-FMR21 Cam Positioner
C500-CP131
0.35
Link Units and Remote I/O Units Unit
Model
Current Consumption (A)
I/O Link
3G2A5-LK010-(P)E
0.6
PC Link
C500-LK009-V1
0.9
Host Link
C500-LK103 (-P)
1.0 each
C500-LK203
32
Optical Remote I/O Master
3G2A5-RM001-(P)EV1
0.7
SYSMAC Net Link
C500-SNT31-V4
1.4
Wired Remote I/O Master
C500-RM201
0.3
Page 42
Section 4
System Connections
4-2
I/O Connections Connect the I/O Devices to the I/O Units using AWG (cross-sectional area: 0.3 mm2) for 19-terminal terminal blocks and AWG 22 to lead wire (cross-sectional area: 0.3 to 0.75 mm2) for 10-terminal terminal blocks. The terminals have screws with 3.5-mm diameter heads and self-raising pressure plates. Connect the lead wires to the terminals as shown. Always use solderless (crimp) terminals. Tighten the screws to a torque of 0.8 N S m.
Use M3.5 self-rising screws for the terminal screws of the Power Supply Units. Always attach crimp terminals to the ends of the lead wires before attaching them to the terminals. Never attach loose or twisted wires. Tighten the screws on the terminal block to a torque of 0.8 N S m. Use crimp terminals for M3.5 screws of the dimensions shown below.
7 mm max.
7 mm max.
33
Page 43
Section 4
System Connections Terminal Block
The terminal block of an I/O Unit can be removed by loosening the mounting screws. You do not have to remove the lead wires from the terminal block in order to remove it from an I/O Unit. Note
Putting I/O Lines and high-tension lines or power lines in the same duct or conduit may cause the I/O Lines to be affected by noise. This may cause a malfunction in the I/O Unit or may cause damage to the I/O Unit or I/O devices.
Terminal block mounting screws Loosen the terminal block mounting screws to remove the terminal block from the I/O Unit. Make sure the mounting screws on the terminal block are tightened after wiring is complete, and the terminal block is remounted to the I/O Unit.
Note
When a Triac Output Unit is used to drive a low-current load, the load may not turn completely OFF due to a leakage current. To compensate for the leakage current, connect a bleeder resistor in parallel with the load.
Wiring Examples The following are examples of how to connect I/O devices to I/O Units. During wiring, work slowly and carefully. If an input device is connected to an Output Unit, damage may result. Check all I/O devices to make sure they meet the specifications (refer to Appendix B Specifications). Be sure to allow for leakage current and load inductance.
DC Input Units Contact output
IN
DC input
COM
When using the following configurations, the sensor and Input Unit should receive their power from the same supply.
34
Page 44
Section 4
System Connections NPN current output + Current regulator IN
Output 7 mA
DC input
COM
0V NPN open-collector output +
Sensor Power Supply IN
Output 7 mA
DC input
COM
0V PNP current output +
Sensor Power Supply
Output
IN
AC/DC input
7 mA COM
0V
AC Input Contact output
IN
AC input
COM
AC Switching IN Prox. switch main circuit
Note
AC input
COM
If a reed switch is used as the input contact of the AC Input Unit, the reed switch must have a permissible current capacity of 1 A minimum, otherwise contact weld may result due to inrush current.
Output Units A fuse placed in the output circuit will protect the output element, circuit board, etc., in the event of a short circuit in the output circuit.
OUT
Relay, solenoid, etc.
+
COM
35
Page 45
SECTION 5
Installation Environment
5-1 Cooling 5-2 Mounting Requirements 5-3 Duct Work 2.0... eect eee teen eee 5-4 Preventing Noise
OOOO
37
Page 46
Section 5
Installation Environment
Introduction This section details the necessary environment and conditions for installation of the PC. For specific instructions on mounting Units and wiring for I/O and power, refer to Section 3-3 System Configurations and 4-2 I/O Connections. ! Caution
5-1
Static electricity can cause damage to PC components. Your body can carry an electrostatic charge, especially when the humidity is low. Before touching the PC be sure to first touch a grounded metallic object, such as a water pipe, in order to discharge any static build-up.
Cooling There are two points to consider in order to ensure that the PC does not overheat. The first is the clearance between the Racks, and the second is installation of a cooling fan.
Clearance Between Racks The Racks need to have sufficient room between each other to allow for I/O wiring, and additional room to ensure that the I/O wiring does not hamper cooling. However, the Racks must be mounted so that the length of the connecting cable does not exceed 2 m, and the total length of the Connecting Cables between all Racks does not exceed 12 m. For details about cable lengths, refer to Appendix C Standard Models. As a general rule, about 70 to 120 mm should be left between any two Racks.
Cooling Fan A cooling fan is not always necessary, but may be needed in some installations. Try to avoid mounting the PC in a warm area, or over a source of heat. A cooling fan is needed if the ambient temperature may become higher than that specified (refer to Appendix B Specifications). If the PC is mounted in an enclosure install a cooling fan, as shown in the following diagram, to maintain the ambient temperature within specifications. Fan
PC
Louver
5-2
Mounting Requirements The PC consists of from one to nine Racks. Each Rack must be mounted vertically, that is with the printing on the front panels oriented as it would normally read. The Racks should be mounted one above the other with the CPU Rack uppermost. The PC may be directly mounted to any sturdy support meeting the environmental specifications (refer to Appendix B Specifications).
38
Page 47
Section 5
Installation Environment
The duct work shown in the following diagram is not used for mounting the Racks. Although optional, the duct work can be used to house the wires from the I/O Units that run along the sides of the Racks, keeping the wires from becoming entangled with other machines. The figures illustrate the correct way to mount the Racks.
CPU Rack
Expansion I/O Rack
The following figure shows a side view of a mounted CPU and two Expansion I/O Racks. There should be a distance of 70 to 120 mm between the mounted Units.
CPU Duct
70 to 120 mm
I/O Duct
70 to 120 mm
I/O
Approx. 100 mm
39
Page 48
Section 5
Installation Environment
5-3
Duct Work If power cables carrying more than 10 A 400 V, or 20 A 220 V must be run alongside the I/O wiring (that is, parallel to it), leave at least 300 mm between the power cables and the I/O wiring as shown below. Low current cable 1 300 mm min. Control cable 2
Power cable
300 mm min.
3
Grounding at resistance of less than 100 Ω
1 = I/O wiring 2 = General control wiring 3 = Power cables If the I/O wiring and power cables must be placed in the same duct (for example, where they are connected to the equipment), shield them from each other using grounded metal plates. Metal plate (iron) 200 mm min. 1
2
3
Grounding at resistance of less than 100 Ω
1 = I/O wiring 2 = General control wiring 3 = Power cables
40
Page 49
Section 5
Installation Environment
5-4
Preventing Noise In order to prevent noise from interfering with the operation of the PC, use AWG 14 twisted-pair cables (cross-sectional area: 2 mm2 min.). Avoid mounting the PC close to high-power equipment, and make sure the point of installation is at least 200 mm away from power cables as shown below. Power lines
200 mm min. PC 200 mm min.
Whenever possible, use wiring conduit to hold the I/O wiring. Standard wiring conduit should be used, and it should be long enough to completely contain the I/O wiring and keep it separated from other cables.
41
Page 50
SECTION 6 Power Considerations
43