C500 Programmable Controller Installation Guide, pages 31 to 40

Pages 31 to 40 of 114

The original document is the PDF (1.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C500-BI081/ 3G2A5-BI081 and Omron C500-OD219

Page 31

Section 3

Assembly

Introduction When we speak of a PC, we usually think of it as a single object. But actually even the simplest PCs are usually composed of several different devices. In fact a single PC can be physically spread throughout a building, but we still call it one PC. In this section, we will start with a Backplane and use all the Units discussed in Section 2 Description of All Components to build a PC.

3-1

Mounting the Units There is no single Unit that can be said to constitute a Rack PC. To build a Rack PC, we start with a Backplane. The Backplane for the C500 is shown below.

C500 Backplane

The Backplane is a simple device having two functions. The first is to provide physical support for the Units to be mounted to it. The second is to provide the connectors and electrical pathways necessary for connecting the Units mounted to it. The first device we will add to the Backplane is a Power Supply. The Power Supply fits into the rightmost position on the Backplane and provides electricity at the voltages required by the other Units of the PC. It can also be used to power devices other than the PC if necessary.

Power Supply

The core of the PC is the CPU. The CPU contains the program consisting of the series of steps necessary for the control task. The CPU fits into the position directly to the left of the Power Supply.

CPU

22

Page 32

Section 3

Assembly

Unlike the CPU of the Package-type PC, the CPU of the Rack PC has no I/O points built in. So, in order to complete this kind of PC we need to mount one or more I/O Units to the Backplane. Mount the I/O Units to the Backplane by pressing the I/O Unit firmly into position, making sure the connectors are properly mated. Secure the Unit by tightening the mounting screws located on the top and bottom of the Unit.

Mounting screws Provided at the top and bottom of the Unit Connector Make sure the connectors are properly mated.

The figure below shows one I/O Unit mounted directly to the left slot of the CPU Rack.

I/O Unit

I/O Units are where the control connections are made from the PC to all the various input devices and output devices. As you can see from the figure, there is still some space available on the right side of the Backplane. This space is for any additional I/O Units that may be required.

The figure above shows a total of eight I/O Units mounted to the Backplane. Backplanes are available in different lengths, and can hold a different number of I/O Units accordingly. Of course, not all I/O Units look exactly alike, but the ones in the figure show their typical appearance. This configuration of Backplane, Power Supply, CPU, and I/O Units is called a CPU Rack. This term refers to the Backplane and all the Units mounted to it. However, if we want to include more than eight I/O Units in our configuration we can add an addi-

23

Page 33

Section 3

Assembly tional Backplane. First, though, we have to mount an I/O Control Unit to the leftmost slot of the CPU Rack.

I/O Control Unit

Now we can use a cable to connect the CPU Rack to another Backplane. This Backplane has a Power Supply and I/O Units mounted to it, but it has no CPU of its own. The additional Backplane must also have an I/O Interface Unit mounted to its leftmost position. This configuration of additional Backplane, Power Supply, I/O Units, and I/O Interface Unit is called an Expansion I/O Rack.

CPU Rack

Expansion I/O Rack

I/O Interface Unit

The CPU Rack and Expansion I/O Rack shown above are connected by a cable. Remember that this whole configuration is still referred to as one PC. It is possible to keep adding Expansion I/O Racks in this way until the maximum number of I/O points for the system is reached. Each Expansion I/O Rack needs an I/O Interface Unit.

24

Page 34

Section 3

Assembly

3-2

Memory Packs The CPU has a removable Memory Pack that stores the user program. Two Memory Packs are available, in either RAM or ROM. You can write your own program into the RAM Pack or you can copy a program that has already been written to an EPROM chip and mount it in the ROM Pack. The EPROM Chip must be mounted to the PROM Writer in order for the program to be written to it. Then the EPROM Chip must be mounted to the ROM Pack.

Mounting the EPROM Chip to the ROM Pack Depending on the amount of memory required for your application, use 1, 2, or 3 chips. Refer to Appendix B Specifications for specifications of the EPROM chips. Using the diagram and the table below as a reference, mount the EPROM chips to the correct IC sockets.

64 128

CHIP 0

CHIP 1

CHIP 2

RAM Pack The table below summarizes the programming capacity. Memory size

IC Socket

Jumper setting CHIP 0

8K bytes

128

16K bytes

CHIP 1

CHIP 2

2764

–

–

2764

2764

–

2764

2764

2764

27128

–

–

27128

–

2764

64 24K bytes 16K bytes 128 24K bytes

64

How to Install the Memory Pack Take the following steps to install the Memory Pack in the CPU. 1. ! Caution

Turn the power to the PC OFF.

Do not attempt to install the Memory Pack in the CPU while the power to the PC is ON. Doing so may cause data to be lost, or may damage the CPU or Memory Pack.

25

Page 35

Section 3

Assembly 2.

Using a standard screwdriver, remove the Memory Pack compartment cover located on the front panel of the CPU. Push in the latch on the cover and slide the cover upward.

SYSMAC C500 PROGRAMMABLE CONTROLLER POWER

OMRON

RUN ERR ALARM OUT INMB

•

3.

Use a standard screwdriver to remove the Memory Pack compartment cover.

Insert the Memory Pack (component side facing left) into the Memory compartment. When the Unit is almost completely inserted into the CPU, there may be a slight resistance as the Memory Pack connector mates with the connector inside the CPU. Continue pushing on the Memory Pack until it is inserted completely into the CPU. Memory Unit guide

Memory Pack (ROM or RAM Pack)

4.

Reattach the memory compartment cover.

How to Remove the Memory Pack Follow the steps below to remove the Memory Pack from the CPU.

26

1.

Turn the power to the PC OFF.

2.

Using a standard screwdriver, remove the Memory Pack compartment cover located on the front panel of the CPU. Push in the latch on the cover and slide the cover upward.

3.

Pull the Memory Pack up and out.

Page 36

Section 3

Assembly Note

3-3

Memory in the RAM Pack is erased when the Memory Pack is removed from the CPU and when the CPU Unit is removed from the Rack.

System Configurations The following figure shows an assembled C500 CPU Rack and one Expansion I/O Rack. When three Expansion I/O Racks are connected to a CPU Rack, a maximum of 512 I/O points are available. (Include the Remote I/O Units) CPU

CPU Power Supply I/O Control Unit CPU Rack

Connecting Cable

Programming Console

I/O Interface Unit

Expansion I/O Power Supply

Where I/O Units Can Be Mounted The table below summarizes the Units that can be used in the systems described in this manual. Special I/O Units

Host Link Units

The number of Special I/O Units that can be used depends upon the number of points available and the number of points the Special I/O Unit requires. Up to one Host Link Units can be mounted. Only one Rack-Mounting Host Link Unit can be mounted to the CPU Rack. A CPU-Mounting Host Link Unit can also be mounted directly to the CPU. Host Link Units cannot be mounted to Expansion I/O Racks. However, these Units cannot be mounted when the SYSMAC Net Link Unit is mounted.

I/O Units Memory Packs Remote I/O Master Unit

Standard I/O Units are available with 16, 32, or 64 points. Refer to Section 2 Description of All Components for details. RAM or ROM Packs are available. The ROM Pack requires a separately available EPROM chip. Up to four Remote I/O Master Units can be mounted to both the I/O Rack and the Expansion I/O Racks. When the Remote I/O Unit is mounted to a Rack, a Rack number must be set so that the CPU can identify the Remote I/O Unit. Mount the Remote I/O Slave Unit to the leftmost position (the I/O Interface Unit position) on the Slave Rack. For details, refer to the C500 Operation Manual.

27

Page 37

Section 3

Assembly

The following table summarizes specific Units that can and cannot be mounted in the CPU and Expansion Racks and the number that can be used in each PC. For more information about the Units, refer to the C500 Operation Manual. Unit

CPU Rack

Expansion Rack

16-, 32-, 64-point I/O

YES

YES

Special I/O

YES

YES

I/O Link

YES

YES

PC Link

YES (2 max.)

NO

Host Link

YES (2 max.)*

NO

SYSMAC Net Link

YES (1 max.)

NO

Remote I/O Master

YES

YES

Remote I/O Slave

NO

YES

*One Rack-mounting Host Link Unit can be mounted to the CPU Rack and one CPU-mounting Host Link Unit can be mounted directly to the CPU Unit.

28

Notes 1.

The Position Control Unit and the PID Unit each require two I/O slots on the CPU Rack and the Expansion I/O Racks

2.

The following Units can only be mounted to one of the three or five rightmost slots on the CPU Backplane, depending on which Backplane is used. PC Link Host Link SYSMAC Net Link

3.

When two or more PCs are linked by the PC Link Unit, a maximum of 32 PC Link Units can be used (linking 31 PCs), in any number of subsystems.

4.

SYSMAC Net Link and Host Link cannot be mounted simultaneously.

Page 38 read from a scan by OCR; it may hold reading errors

SECTION 4

System Connections

4-1 Current Consumption ......... 0.0.0.0 cece e eee eee ‘| 4-2 WOConnections .... 0.0... eee ene eee e nen eben eee eee oO

29

Page 39

Section 4

System Connections

Introduction In the preceding sections we have covered all the parts of a PC and how they should be assembled. This section provides detailed information on PC connections.

4-1

Current Consumption The Power Supplies are limited in the total current they can supply to I/O Units. The following table shows the maximum currents allowed.

Power Supplies Unit CPU Power Supply

I/O Power Supply

Model

Output Capacity

Current Available for I/O Units 5A

3G2A5-PS221-E 3G2A5-PS211-E

7 A 5 VDC

3G2A5-PS213-E

9 A 5 VDC

3G2A5-PS223-E

12 A 5 VDC

10 A

3G2A5-PS222-E

7 A 5 VDC

6.5 A

3G2A5-PS212-E

Note

Do not exceed the maximum current ratings for each of the voltages supplied by any single Unit listed above. In addition, do not exceed the total maximum power output for any single Unit listed above. Refer to the tables on the following page for the current consumption of individual I/O Units.

Input Units Unit DC Input

AC Input

30

Model

Current Consumption (A)

3G2A5-ID112

0.01

3G2A5-ID114

0.34

3G2A5-ID213

0.02

3G2A5-ID215

0.16

3G2A5-ID218

0.16

3G2A5-ID218CN

0.2

3G2A5-ID212

0.3

3G2A5-ID219

0.34

3G2A5-IA121

0.01

3G2A5-IA222

0.012

3G2A5-IA223

0.06

3G2A5-IA122

0.06

TTL Input

3G2A5-ID501CN

0.2

AC/DC Input

3G2A5-IM211

0.01

3G2A5-IM212

0.2

Page 40

Section 4

System Connections Output Units Unit Contact Output

Model

Current Consumption (A)

3G2A5-OC221

0.1

3G2A5-OC223

0.1

3G2A5-OC224

0.2

3G2A5-OD411

0.16

3G2A5-OD215

0.2

3G2A5-OD412

0.23

3G2A5-OD212

0.23

3G2A5-OD211

0.3

3G2A5-OD213

0.46

3G2A5-OD217

0.16

C500-OD218

0.23

C500-OD219

0.16

3G2A5-OD415CN

0.23

3G2A5-OA121

0.3

3G2A5-OA222

0.3

3G2A5-OA223

0.45

C500-OA225

0.2

C500-OA226

0.45

TTL Output

C500-OD501CN

0.25

DC Input/Transistor Output Unit

3G2A5-MD211CN

0.26

Dummy I/O

3G2A5-DUM01

0.035

Transistor Output

Triac Output

31