Page 21

Section 2

Description of All Components

2-2

CPU Power Supply The CPU Power Supply is mounted to the rightmost slot of the CPU Rack. Three models of Power Supplies are available: 100 to 120 VAC, 200 to 240 VAC, and 24 VDC. The following table summarizes the output capacity of the three models and the current available for I/O Units mounted on the CPU Rack. Model

Output Capacity

Available Current for I/O Units

24 VDC Output Terminal

3G2A5-PS221-E 100 to 120/ 200 to 240 VAC 3G2A5-PS223-E (selectable)

7 A 5 VDC

5A

Provided

12 A 5 VDC

10 A

Not provided

3G2A5-PS213-E 24 VDC

9 A 5 VDC

5A

Not provided

Note

Supply Voltage

Be sure to keep the total power consumed by all the Units mounted on a Rack within the value stated in the table above. For example, do not mount I/O Units with a total current consumption of 6 A to a Rack supplied by a 7 A Power Supply. As shown in the table above, the available current for I/O Units is only 5 A. For details concerning current consumption, refer to Section 4 System Connections.

3G2A5-PS221-E Mounting screw Do not loosen this screw.

•

Fuse holder Contains a MF61NR fuse (3 A, 250 V, 6.35-dia. x32)

AC input

Connect a 100 to 120 VAC or 200 to 240 VAC power source.

POWER indicator Lights when power is supplied.

Voltage selector Short: 100 to 120 V Open: 200 to 240 V

Short these terminals to select 100 to 120 VAC. Open them to select 200 to 240 VAC.

LG

Ground this terminal at a resistance of less than 100 Ω to improve noise immunity or prevent electric shock.

Terminals for external connections GR +

+ 0.8 A, 24 VDC output –

START input

RUN output Mounting screw Do not loosen this screw.

12

Ground this terminal at a resistance of less than 100 Ω to prevent electric shock. Use these terminals to supply power to DC Input Units. Use a separate Power Supply if the I/O Unit requires more than 0.8 A. If a current higher than 0.8 A is output, the PC stops. These terminals are short-circuited as a factory-set condition. Remove the short-circuit bracket to start or stop the PC with an external signal. Normally, leave them short-circuited. These terminals are turned ON during RUN operation.

Page 22

Section 2

Description of All Components 3G2A5-PS223-E Mounting screw Do not loosen this screw.

•

Fuse holder Contains a MF61NR fuse (3 A, 250 V, 6.35-dia. x32)

AC input

POWER indicator Lights when power is supplied.

Voltage selector Short: 100 to 120 V Open: 200 to 240 V

LG Terminals for external connections GR

Connect a 100 to 120 VAC or 200 to 240 VAC power source.

Short these terminals to select 100 to 120 VAC. Open them to select 200 to 240 VAC. Ground this terminal at a resistance of less than 100 Ω to improve noise immunity or prevent electric shock. Ground this terminal at a resistance of less than 100 Ω to prevent electric shock. 24 VDC output terminals are not provided.

START input

Mounting screw Do not loosen this screw.

These terminals are short-circuited as a factory-set condition. Remove the short-circuit bracket to start or stop the PC with an external signal. Normally, leave them shortcircuited.

RUN output

These terminals are turned ON during RUN operation.

24 VDC input

Connect a 24 VDC power source (2.3 A min.)

3G2A5-PS213-E Mounting screw Do not loosen this screw.

•

Fuse holder Contains a MF61NR fuse (3 A, 250 V, 6.35-dia. x32)

+

-

POWER indicator Lights when power is supplied.

LG Terminals for external connections GR

Ground this terminal at a resistance of less than 100 Ω to improve noise immunity or prevent electric shock. Ground this terminal at a resistance of less than 100 Ω to prevent electric shock. 24 VDC output terminals are not provided.

START input

RUN output Mounting screw Do not loosen this screw.

These terminals are short-circuited as a factory-set condition. Remove the short-circuit bracket to start or stop the PC with an external signal. Normally, leave them shortcircuited. These terminals are turned ON during RUN operation.

13

Page 23

Section 2

Description of All Components

2-3

Expansion I/O Backplane The Expansion I/O Backplane shown in the following diagram, can be used to expand the C500 PC. An Expansion I/O Rack is just like a CPU Rack, except a CPU is not mounted. However, a Power Supply is needed for each Expansion I/O Rack. There are three models of Expansion I/O Backplane available.

Expansion I/O Power Supply I/O Units I/O Interface Unit An I/O Interface Unit must be mounted to an Expansion I/O Rack in order to connect the Expansion I/O Rack to another Expansion I/O Rack. Expansion I/O Backplane

2-4

I/O Power Supply Just as a Power Supply must be mounted to the CPU Rack, a Power Supply must also be mounted to each Expansion I/O Backplane. There are two Power Supplies available; 100 to 120/200 to 240 VAC and 24 VDC, both of which are explained below. For details, refer to Appendix B Specifications. Model

Supply Voltage

3G2A5-PS222-E

100 to 120/200 to 240 VAC (selectable)

7A 5 VDC

6.5 A

Provided

3G2A5-PS212-E

24 VDC

7 A 5 VDC

6.5 A

Not provided

Note

14

Output Capacity

Available Current for I/O Units

240 VDC Output Terminal

Be sure to keep the total power consumed by all the Units mounted on a Rack within the value stated in the table above. For example, do not mount I/O Units with a total current consumption of 7A to a Rack supplied by a 7 A Power Supply. As shown in the table above, the available current for I/O Units is only 6.5 A. For details concerning current consumption, refer to Section 4 System Connections.

Page 24

Section 2

Description of All Components 3G2A5-PS222-E Mounting screw Do not loosen this screw.

•

Fuse holder Contains a MF61NR fuse (3 A, 250 V, 6.35-dia. x32)

AC input

POWER indicator Lights when power is supplied.

Voltage selector Short: 100 to 120 V Open: 200 to 240 V

Connect a 100 to 120 VAC or 200 to 240 VAC power source

Short these terminals to select 100 to 120 VAC. Open them to select 200 to 240 VAC.

LG

Ground this terminal at a resistance of less than 100 Ω to improve noise immunity or prevent electric shock.

GR

Ground this terminal at a resistance of less than 100 Ω to prevent electric shock.

Terminals for external connections + 0.8 A, 24 VDC output -

Use these terminals to supply power to DC Input Units. Use a separate Power Supply if the I/O Unit operate on more than 0.8 A. If a current higher than 0.8 A is output, the PC stops. These terminals are used to supply external DC Input Units. If the Unit requires more than 0.8 A a separate supply must be used. The PC shuts off automatically if a current of more than 0.8 A is drawn from the supply.

Mounting screw Do not loosen this screw.

3G2A5-PS212-E Mounting screw Do not loosen this screw. +

•

Fuse holder Contains a MF61NR fuse (3 A, 250 V, 6.35-dia. x32)

24 VDC input

Connect a 24-VDC power source (2.3 A min.)

LG

Ground this terminal at a resistance of less than 100 Ω to improve noise immunity or prevent electric shock.

GR

Ground this terminal at a resistance of less than 100 Ω to prevent electric shock.

-

POWER indicator Lights when power is supplied.

Terminals for external connections

Mounting screw Do not loosen this screw.

15

Page 25

Section 2

Description of All Components

2-5

I/O Control Unit An I/O Control Unit must be mounted to the CPU Rack in order to connect the CPU Rack to an Expansion I/O Rack. An I/O Control Unit can be mounted even if no Expansion I/O Rack is used.

2-6

I/O Interface Unit An I/O Interface Unit is needed on each Expansion I/O Rack, in order to expand the PC. If there is not an I/O Interface Unit on each Expansion I/O Rack, data communication cannot take place. The I/O Interface Unit is mounted to the leftmost I/O position on the Expansion I/O Backplane.

2-7

I/O Units I/O Units come in 5 shapes; A-shape, B-shape, C-shape, D-shape, and Eshape. Refer to Appendix B Specifications for the dimensions of each Unit.

A-shape Mounting screw Provided at top and bottom Nameplate Fuse blowout alarm indicator Provided on OD411/OA121/ OD217/OA222 I/O indicators Indicate ON/OFF status points Terminal block mounting screw Provided at top and bottom 20-terminal terminal block Removable

16

Page 26

Section 2

Description of All Components B-shape Mounting screw Provided at top and bottom Nameplate I/O indicators Indicate ON/OFF status of I/O signal Terminal block mounting screw Provided at top and bottom

38-terminal terminal block Removable

C-shape Mounting screw Provided at top and bottom Nameplate I/O indicators Indicate ON/OFF status of points Terminal block mounting screw Provided at top and bottom

38-terminal terminal block Removable

17

Page 27

Section 2

Description of All Components D-shape Mounting screw Provided at top and bottom Nameplate I/O indicators Indicate ON/OFF status of points

Two 40-terminal terminal block connectors Removable

E-shape Mounting screw Provided at top and bottom Nameplate I/O indicators Indicate ON/OFF status of points

Two 24-terminal terminal block plugs

4-terminal terminal block

18

Page 28

Section 2

Description of All Components

2-8

Memory Packs The Memory Pack fits into the slot located on the left side of the CPU. Because the Memory Pack is not provided with the PC upon delivery, a Memory Pack must be selected and installed in the CPU. There are two Memory Packs available, either RAM or ROM, that can be used in the C500H PC.

RAM Pack Data can be randomly written to and read from the RAM Pack, making it possible to enter your own program into the CPU. However, because this is not a fixed program, the memory of the RAM Pack is erased when power is not supplied to the CPU or when the RAM Pack is removed from the CPU. ! Caution

Do not remove the battery in the CPU when the RAM Pack has been removed from the CPU.

64 128

CHIP 0

CHIP 1

CHIP 2

RAM Pack Two models of RAM Packs are available, which vary in memory capacity: 16K, and 24K words. Refer to Appendix C Standard Models for model numbers. Using a Programming Console, execute FUN (01) and a search operation to check the amount of memory available.

19

Page 29

Section 2

Description of All Components ROM Pack

Data contained in the ROM Pack is stored on EPROM chips and cannot be altered or erased during the CPU’s operation. Write the user’s program to the EPROM chips and mount the chips (3 max.) on the ROM chip. The entire pack is installed in the CPU. Once the data is written to the chip the data will not be lost when the power to the PC is OFF.

64 128

CHIP 0

CHIP 1

RAM Pack

20

CHIP 2

Page 30 read from a scan by OCR; it may hold reading errors

SECTION 3

Assembly 3-1 Mounting the Units... 0... 2. cence eee nee ‘| 3-2. Memory Packs ........ 0. ec eee eee teen eee bene oO 3-3 System Configurations ..... 0.0... cee nee teen e eens im

21