Page 1
R
Micro Programmable Controller
CPM1A
The CPM1A series micro controllers solve both basic and semi-complex applications. The brick style models include AC inputs/relay outputs, DC inputs/transistor or relay outputs to meet your design requirements. The base I/O for the CPUs ranges from 10, 20, 30, and 40 I/O points with maximum expansion to 100 I/O. Specialized expansion modules include mixed analog I/O, temperature sensor inputs and serial communications
H 10, 20, 30 and 40 point I/O CPUs H Expandable up to 100 I/O points uC
H Peripheral communications port built in H AC or DC input models H Analog expansion modules available H Temperature sensor input expansion modules available
H Auxiliary 24 VDC supply (AC type only) H Relay or Transistor outputs H UL, CSA, CE approvals Basic Configuration Peripheral port
Connecting cable
CPM1-CIF01/CIF11 Serial Communications Adapter
AC and DC power supply models: 30-point CPU and 40-point CPU only may be expanded up to a maximum of 3 Units.
Expansion I/O Unit
Expansion I/O Unit
Expansion I/O Unit
1
Page 2
CPM1A
CPM1A
Ordering Information J CPU UNITS Number of I/O terminals
Inputs
10
6 DC points
20 30 40
Outputs
12 DC points 18 DC points 24 DC points
4 points 8 points 12 points 16 points
Power supply
Part number Sink type
Source type
AC
CPM1A-10CDR-A
CPM1A-10CDT-A
CPM1A-10CDT1-A
DC
CPM1A-10CDR-D
CPM1A-10CDT-D
CPM1A-10CDT1-D
AC
CPM1A-20CDR-A
CPM1A-20CDT-A
CPM1A-20CDT1-A
DC
CPM1A-20CDR-D
CPM1A-20CDT-D
CPM1A-20CDT1-D
AC
CPM1A-30CDR-A
CPM1A-30CDT-A
CPM1A-30CDT1-A
DC
CPM1A-30CDR-D
CPM1A-30CDT-D
CPM1A-30CDT1-D
AC
CPM1A-40CDR-A
CPM1A-40CDT-A
CPM1A-40CDT1-A
DC
CPM1A-40CDR-D
CPM1A-40CDT-D
CPM1A-40CDT1-D
Relay output
Transistor output
20
12 AC points
8 points
AC
CPM1A-20CAR-A, - 32
20 AC points
12 points
AC
CPM1A-32CAR-A, - J EXPANSION I/O MODULES Description
Max. number of modules
Inputs
Outputs
Part number
20 I/O points
3 max. (See Note.)
24 VDC
Relays
CPM1A-20EDR
24 VDC
Sinking transistors
CPM1A-20EDT
12 inputs, 8 outputs
24 VDC
Sourcing transistors
CPM1A-20EDT1
8 inputs
24 VDC, CPM1A-8ED
8 outputs, Relays
CPM1A-8ER, Sinking transistors
CPM1A-8ET, Sourcing transistors
CPM1A-8ET1
Note: A maximum of 3 expansion modules can be used with the following CPUs: 30-point and 40-point with DC inputs; 20-point and 32-point with AC inputs.
J DEDICATED I/O MODULES Description
Max. number of modules
Inputs
Outputs
Part number
Analog I/O Module 2 analog inputs (2 words) 1 analog output (1 word)
3 max.
2 analog inputs
1 analog output
CPM1A-MAD01
Temperature Sensor Input Modules
Thermocouple inputs
3 max.
2 inputs (Types J and K), CPM1A-TS001
1 max. (See Note.)
4 inputs (Types J and K)
Platinum resistance thermometer inputs
3 max.
2 inputs (Pt100, JPt100)
3 max.
2 inputs (Pt100, JPt100)
1 analog output
CPM1A-TS101-DA
1 max. (See Note.)
4 inputs (Pt100, JPt100), CPM1A-TS102
3 max.
8 bits (Inputs from the Master.)
8 bits CPM1A-SRT21 (Outputs to the Master.)
CompoBus/S I/O Link Module 8 inputs and 8 outputs
CPM1A-TS002 CPM1A-TS101
Flat cable, 4-core, 0.75 mm2; 100 m length
SCA1-4F10
Twisted pair cable, 2-core, 0.75 mm2; available commercially
Belden #9409 cable
Note: Only one CPM1A-TS002/TS102 Temperature Sensor Input Module can be connected to the CPU. If a CPM1A-TS002/102 is connected to the CPU, only one additional Special I/O Module (other than a CPM1A-TS002/102) or one Expansion I/O Module can be connected to the CPU.
2
Page 3
CPM1A
CPM1A J PERIPHERAL DEVICES Product
Description
Part number
Programming console
Hand-held programming console with cable attached, 2 m length
CQM1-PRO01–E
Hand-held programming console with back light (cable not included)
C200H-PRO27-E
Connects C200H programming console to peripheral port, 2 m length
C200H-CN222
Connects C200h programming console to peripheral port, 4 m length
C200H–CN422
Connecting cable
J SUPPORT SOFTWARE Product
Functions
Part number
CX-Programmer Jr.
Windows-based programming software; reduced instruction set and networking commands. OS: Windows 95/98/NT
WS02-CXPC1-EJR-V2.0
CX-Programmer
Full programming software package programs micro, small and larger controllers.
WS02-CXPC1-EV2.0
J COMMUNICATIONS ADAPTERS AND CABLES Description
Function
Part number
RS-232C adapter
Converts data communications from peripheral port for RS-232C devices.
CPM1-CIF01
RS-232C cable
RS-232C to RS-232C; PC connection for program download; cable length 2 m
C200HS-CN220-EU
RS-232C to RS-232C for PLC communication; cable length 2 m
C200H-CN320-EU
Converts data communications from peripheral port for RS-422/RS-485 devices.
CPM1-CIF11
RS-422/RS-485 adapter
J PROGRAM TRANSFER EQUIPMENT Product
Description
Part number
Expansion Memory Unit
Uploads and downloads program and setup memory areas to and from the controller.
CPM1-EMU01-V1
EEPROM (256 kbits)
Used with the Expansion Memory Unit
CPM1-EEPROM-EMU01
Product
Description
Part number
Operation manual
CPM1A DC Input CPUs operation manual
W317
CPM1A AC Input CPUs operation manual
P12FAZ1
CPM1/CPM1A programming manual
W353
J MANUALS
Programming manual
3
Page 4
CPM1A
CPM1A
Specifications J GENERAL SPECIFICATIONS Input type
DC input
CPU type
10-point I/O
AC input 20-point I/O
30-point I/O
40-point I/O
20-point I/O
Power supply voltage/frequency
AC power supply
100 to 240 VAC, 50/60 Hz
DC power supply
24 VDC
Operating voltage range
AC power supply
85 to 264 VAC
DC power supply
20.4 to 26.4 VDC
Power consumption
AC power supply
30 VA max.
60 VA max.
30 VA max.
DC power supply
6 W max.
20 W max., 30 A max.
60 A max.
30 A max.
Inrush current External power supply (AC only)
Power supply voltage
24 VDC
Power supply output capacity
200 mA
32-point I/O, - 60 VA max. 60 A max.
300 mA
Insulation resistance
20 MΩ min. at 500 VDC between the AC terminals and the protective earth terminal.
Dielectric strength
2,300 VAC at 50/60 Hz for one minute with a leakage current of 10 mA max. between all the external AC terminals and the protective earth terminal.
Noise resistance
Conforms to IEC61000-4-4, 2 kV (power lines) 1500 Vp-p, pulse width 0.1 to 1 µs, rise time: 1 ns (via noise simulation)
Vibration resistance
10 to 61.2 Hz with an amplitude of 0.075 mm, and 57 to 150 Hz with an acceleration of 1.5 G in the X, Y, and Z directions for 10 sweeps of minutes each.
Shock resistance
147 m/s2 in the X, Y and Z directions 3 times each.
Ambient temperature
Operating
0°C to 55°C (32°F to 131°F)
Storage
–20°C to 75°C (–4°F to 167°F)
Ambient humidity
Operating
10% to 90% RH no condensation
Ambient environment
Operating
With no corrosive gas
20 G the X, Y and Z directions 3 times each.
Terminal screw size
M3
Power supply holding time
10 ms min. for AC models, and 2 ms min. for DC models
Weight
AC models
400 g max.
500 g max..
600 g max..
700 g max.
500 g max.
575 g max.
DC models
300 g max.
400 g max.
500 g max.
600 g max., - Note: The specifications of the Expansion I/O Modules are the same as for the CPU except that the power is supplied from the CPU and the weight is 300 g.
4
Page 5
CPM1A
CPM1A J CHARACTERISTICS Input type
DC input
CPU type
10-point I/O
AC input
Control method
Stored program method
I/O control method
Combination of the cyclic scan and immediate refresh processing methods.
Programming language
Ladder diagram
Instruction word
1 step per instruction, 1 to 5 words per instruction
20-point I/O
Types of instructions
Basic instructions
14 types
Special instructions
79 types, 139 instructions
Instruction execution time
Basic instructions
0.72 to 16.2 µs
Special instructions
MOV instruction = 16.3 µs
30-point I/O
40-point I/O
20-point I/O
32-point I/O
Program capacity
2,048 words
User data memory
1,024 words
Maximum I/O points
CPU only
10 points (6 input/ 4 output points)
20 points (12 input/ 8 output points)
30 points (18 input/ 12 output points)
40 points (24 input/ 16 output points)
20 points (12 input/ 8 output points)
32 points (20 input/ 12 output points
With Expansion I/O Module, - Up to 90 points (54 input/ 36 output points)
Up to 100 points (60 input/ 40 output points)
Up to 80 points (48 input/ 32 output points)
Up to 92 points (56 input/ 36 output points)
Memory protection
Maintains the contents of the HR, AR, Counter and Data Memory Areas.
Memory backup
Flash memory: Super capacitor:
User program, data memory (Read only) and PLC setup area are backed up without a battery. Data memory (Read/Write), holding bits, auxiliary memory bits, counter values, error log area are backed up by a capacitor for 20-days at an ambient temperature of 25°C.
Self-diagnostic function
CPU error (watchdog timer), memory errors, I/O bus errors
Program check
No END instruction programming errors (constantly checked during operation)
Pulse output
1 point:
High-speed counter
1 point: Single phase at 5 kHz or two-phase at 2.5 kHz (linear counting method) Incremental mode: 0 to 65535 (16-bit) Decremental mode: –32767 to 32767 (16-bit)
Quick-response inputs
Together with the external interrupt input (minimum pulse width of 0.2 ms)
Input time constant
Can be set at 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, or 128 ms.
Interrupt processing: External interrupt
2 points (Response time of 0.3 ms max.)
Analog settings
2 points: (0 to 200 BCD)
2 kHz
4 points (Response time of 0.3 ms max.)
4 points (Response time of 5 ms max.)
J I/O ALLOCATION Input bits
00000 to 00915; words not used for input or output bits can be used for work bits.
Output bits
01000 to 01915; words not used for input or output bits can be used for work bits.
Work bits (IR Area)
512: IR 20000 to IR 23115 (IR 200 to IR 231)
Special bits (SR Area)
384: SR 23200 to SR 25515 (SR 232 to SR 255)
Temporary bits (TR Area)
8: TR 0 to TR 7
Holding bits (HR Area)
320: HR 0000 to HR 1915 (HR 00 to HR 19)
Auxiliary bits (AR Area)
256: AR 0000 to AR 1515 (AR 00 to AR 15)
Link bits (LR Area)
256: LR 0000 to LR 1515 (LR 00 to LR 15)
Timers/Counters
128: TIM/CNT 000 to 127 100-ms timer: TIM 000 to TIM 127 10-ms timer: TIM 000 to TIM 127 Decremental counter, reversible counter
Data memory
Read/Write
1,024 words (DM 0000 to DM 1023)
Read only
512 words (DM 6144 to DM 6655)
5
Page 6
CPM1A
CPM1A
J I/O SPECIFICATIONS CPU Unit AC-Input Item
Specification
Input voltage
120 VAC/DC nominal, range 85 to 132
Input impedance
17 kΩ AC @ 60Hz, 69kΩ DC
Input current
7.2 mA AC, 1.7 mA DC @ 120 V typical for: CPM1A-20CAR-A, Inputs 00 to 11 CPM1A-32CAR-A, Ch 0 Inputs 00 to 11 and CPM1A-32CAR-A, Ch 1 Inputs 00 to 03 1.9 mA AC or DC @ 120 V typical for: CPM1A-32CAR-A, Ch 1 Inputs 04 to 07 only
ON voltage
65 VAC/DC
OFF voltage
25 VAC/DC
ON delay
1 to 128 ms max. Default: 8 ms (See Note.)
OFF delay
1 to 128 ms max. Default: 8 ms (See Note.)
Circuit configuration 470 Ω 120 VAC
Input LED
CPM1A-20CAR-A Inputs 00-11
Internal circuits
CPM1A-32CAR-A Inputs Ch 0: 00-11 Inputs Ch 1: 00-03
68 Ω 0.15 µF
2.2 kΩ
Input LED 68 Ω 2.2 kΩ
120 VAC
CPM1A-32CAR-A only Inputs Ch 1: 04-07
Internal circuits
Note: Using the PLC Setup, 1, 2, 4, 8, 16, 32, 64, or 128 ms can be selected. When IN00000 through IN00002 are used as high-speed counter inputs, the delays are as shown in the following table. Typically for AC inputs, the delay is set at the default, 8 ms. Input
Increment mode
Differential phase mode
IN00000 (A-phase)
20 Hz
20 Hz
IN00001 (B-phase)
Normal input
IN00002 (Z-phase)
ON: 5 ms min.; OFF delay: 5 ms min.
The minimum delay is as follows. Increment Mode (20 Hz max.)
100 ms min. 50 ms min.
ON A-phase OFF
50 ms min.
Differential Phase Mode (20 Hz max.) IN00000 (A phase), IN00001 (B phase) 100 ms min. ON
IN00002 (Z phase) 5 ms min. ON Z-phase
A-phase OFF ON B-phase OFF
OFF 50 ms min. T1
T2
T3
T4 T1 T2 T3 T4 : 20 ms min.
When IN00003 through IN00006 are used as interrupt inputs, the delay is 0.3 ms max. The delay is measured from the time that the input goes ON until the interrupt subroutine is executed.
6
Page 7
CPM1A
CPM1A CPU Unit DC Input Item
Specifications
Input voltage
24 VDC +10%/–15%
Input impedance
IN0000 to IN0002: 2 kΩ Others: 4.7 kΩ
Input current (typical)
IN0000 to IN0002: 12 mA Others: 5 mA
ON voltage
14.4 VDC min.
OFF voltage
5.0 VDC max.
ON delay (See Note 1)
1 to 128 ms max. (default: 8 ms) (See Note 1)
OFF delay (See Note 1)
1 to 128 ms max. (default: 8 ms) (See Note 1)
Circuit Input LED 4.7 kΩ IN
Internal Circuits
4.7 kΩ
COM
Note: The polarity of the input power supply can be either positive or negative.
Note: 1. The actual ON/OFF delay includes an input constant of 1, 2, 4, 8, 16, 32, 64, or 128 ms (default: 8 ms). 2. When IN0000 to IN0006 are used for the high-speed counter inputs, the delays are as shown below: Input
Increment mode
Differential phase mode
IN0000 (A-phase)
5 kHz
2.5 kHz
IN0001 (B-phase)
Normal input
IN0002 (Z-phase)
ON: 100 µs max. OFF: 500 µs max.
IN0003 to IN0006
0.3 ms max. (From the time of input ON until the interrupt subroutine is executed.)
Expansion I/O Unit Item
Specifications
Input voltage
24 VDC, +10%/–15%
Input impedance
4.7 kΩ
Input current (typical)
5 mA
ON voltage
14.4 VDC min.
OFF voltage
5.0 VDC max.
ON delay
1 to 128 ms max. (default: 8 ms) (See Note)
OFF delay
1 to 128 ms max. (default: 8 ms) (See Note)
Circuit Input LED 4.7 kΩ IN COM
Internal Circuits
4.7 kΩ
Note: The polarity of the input power supply can be either positive or negative.
Note: The actual ON/OFF delay includes an input constant of 1, 2, 4, 8, 16, 32, 64, or 128 ms (default: 8 ms).
J OUTPUT SPECIFICATIONS (CPU UNIT AND EXPANSION I/O MODULES) Relay Output Item
Specifications
Maximum switching capacity
2 A, 250 VAC (cos φ =1) 2 A, 24 VDC (4 A/common)
Minimum switching capacity
10 mA, 5 VDC
Relay service life
Resistance load
300,000 times
Inductive load
100,000 times
Electrical
Mechanical
Circuit Output LED
Internal Circuits
OUT
OUT COM
10 million times
ON delay
15 ms max.
OFF delay
15 ms max.
Maximum 250 VAC: 2 A 24 VDC: 2 A
7
Page 8
CPM1A
CPM1A
Transistor Output (Sink Type/Source Type) Item
Specifications
Circuit
Maximum switching capacity
300 mA, 24 VDC +10%/–15% (See Note 1)
Sink Type Output LED
Leakage current
0.1 mA max.
Internal Circuits
OUT
OUT
24 VDC
COM (–) Residual voltage
1.5 V max. Source Type Output LED
ON delay
0.1 ms max. COM (+) Internal Circuits
OFF delay
OUT
24 VDC
1 ms max. (See Note 2)
OUT Note: 1. The maximum switching capacity of the CPM1A with transistor outputs (sink type and source type) are limited to the currents shown in the following table for the common and for the Unit. Part number
Max. switching capacity
CPM1A-10CDT, CPM1A-10CDT1-A, CPM1A-10CDT1-D
0.9 A/Unit
CPM1A-20CDT-D, CPM1A-20CDT1-A, CPM1A-20CDT1-D
0.9 A/common; 1.8 A/Unit
CPM1A-30CDT-D, CPM1A-30CDT1-A, CPM1A-30CDT1-D
0.9 A/common; 2.7 A/Unit
CPM1A-40CDT-D, CPM1A-40CDT1-A, CPM1A-40CDT1-D
0.9 A/common; 3.6 A/Unit
CPM1A-20EDT, CPM1A-20EDT1
0.9 A/common; 1.8 A/Unit
CPM1A-8ET, CPM1A-8ET1
0.9 A/common; 1.8 A/Unit
2. When using the pulse output function of the CPM1A with transistor outputs (sink type and source type): The output current must be within a range from 100 to 200 mA when using the output 01000 or 01001 as a pulse output with the maximum frequency of 2 kHz. The outputs 01000 and 01001 will vary depending on the output current.
8
Load current
OFF delay
100 to 200 mA
0.2 ms max.
0 to 300 mA except for the above range
0.5 ms max.