For the Omron CPM1A-8ED

Page 1

R

Micro Programmable Controller

CPM1A

The CPM1A series micro controllers solve both basic and semi-complex applications. The brick style models include AC inputs/relay outputs, DC inputs/transistor or relay outputs to meet your design requirements. The base I/O for the CPUs ranges from 10, 20, 30, and 40 I/O points with maximum expansion to 100 I/O. Specialized expansion modules include mixed analog I/O, temperature sensor inputs and serial communications

H 10, 20, 30 and 40 point I/O CPUs H Expandable up to 100 I/O points uC

H Peripheral communications port built in H AC or DC input models H Analog expansion modules available H Temperature sensor input expansion modules available

H Auxiliary 24 VDC supply (AC type only) H Relay or Transistor outputs H UL, CSA, CE approvals Basic Configuration Peripheral port

Connecting cable

CPM1-CIF01/CIF11 Serial Communications Adapter

AC and DC power supply models: 30-point CPU and 40-point CPU only may be expanded up to a maximum of 3 Units.

Expansion I/O Unit

Expansion I/O Unit

Expansion I/O Unit

1

Page 2

CPM1A

CPM1A

Ordering Information J CPU UNITS Number of I/O terminals

Inputs

10

6 DC points

20 30 40

Outputs

12 DC points 18 DC points 24 DC points

4 points 8 points 12 points 16 points

Power supply

Part number Sink type

Source type

AC

CPM1A-10CDR-A

CPM1A-10CDT-A

CPM1A-10CDT1-A

DC

CPM1A-10CDR-D

CPM1A-10CDT-D

CPM1A-10CDT1-D

AC

CPM1A-20CDR-A

CPM1A-20CDT-A

CPM1A-20CDT1-A

DC

CPM1A-20CDR-D

CPM1A-20CDT-D

CPM1A-20CDT1-D

AC

CPM1A-30CDR-A

CPM1A-30CDT-A

CPM1A-30CDT1-A

DC

CPM1A-30CDR-D

CPM1A-30CDT-D

CPM1A-30CDT1-D

AC

CPM1A-40CDR-A

CPM1A-40CDT-A

CPM1A-40CDT1-A

DC

CPM1A-40CDR-D

CPM1A-40CDT-D

CPM1A-40CDT1-D

Relay output

Transistor output

20

12 AC points

8 points

AC

CPM1A-20CAR-A, - 32

20 AC points

12 points

AC

CPM1A-32CAR-A, - J EXPANSION I/O MODULES Description

Max. number of modules

Inputs

Outputs

Part number

20 I/O points

3 max. (See Note.)

24 VDC

Relays

CPM1A-20EDR

24 VDC

Sinking transistors

CPM1A-20EDT

12 inputs, 8 outputs

24 VDC

Sourcing transistors

CPM1A-20EDT1

8 inputs

24 VDC, CPM1A-8ED

8 outputs, Relays

CPM1A-8ER, Sinking transistors

CPM1A-8ET, Sourcing transistors

CPM1A-8ET1

Note: A maximum of 3 expansion modules can be used with the following CPUs: 30-point and 40-point with DC inputs; 20-point and 32-point with AC inputs.

J DEDICATED I/O MODULES Description

Max. number of modules

Inputs

Outputs

Part number

Analog I/O Module 2 analog inputs (2 words) 1 analog output (1 word)

3 max.

2 analog inputs

1 analog output

CPM1A-MAD01

Temperature Sensor Input Modules

Thermocouple inputs

3 max.

2 inputs (Types J and K), CPM1A-TS001

1 max. (See Note.)

4 inputs (Types J and K)

Platinum resistance thermometer inputs

3 max.

2 inputs (Pt100, JPt100)

3 max.

2 inputs (Pt100, JPt100)

1 analog output

CPM1A-TS101-DA

1 max. (See Note.)

4 inputs (Pt100, JPt100), CPM1A-TS102

3 max.

8 bits (Inputs from the Master.)

8 bits CPM1A-SRT21 (Outputs to the Master.)

CompoBus/S I/O Link Module 8 inputs and 8 outputs

CPM1A-TS002 CPM1A-TS101

Flat cable, 4-core, 0.75 mm2; 100 m length

SCA1-4F10

Twisted pair cable, 2-core, 0.75 mm2; available commercially

Belden #9409 cable

Note: Only one CPM1A-TS002/TS102 Temperature Sensor Input Module can be connected to the CPU. If a CPM1A-TS002/102 is connected to the CPU, only one additional Special I/O Module (other than a CPM1A-TS002/102) or one Expansion I/O Module can be connected to the CPU.

2

Page 3

CPM1A

CPM1A J PERIPHERAL DEVICES Product

Description

Part number

Programming console

Hand-held programming console with cable attached, 2 m length

CQM1-PRO01–E

Hand-held programming console with back light (cable not included)

C200H-PRO27-E

Connects C200H programming console to peripheral port, 2 m length

C200H-CN222

Connects C200h programming console to peripheral port, 4 m length

C200H–CN422

Connecting cable

J SUPPORT SOFTWARE Product

Functions

Part number

CX-Programmer Jr.

Windows-based programming software; reduced instruction set and networking commands. OS: Windows 95/98/NT

WS02-CXPC1-EJR-V2.0

CX-Programmer

Full programming software package programs micro, small and larger controllers.

WS02-CXPC1-EV2.0

J COMMUNICATIONS ADAPTERS AND CABLES Description

Function

Part number

RS-232C adapter

Converts data communications from peripheral port for RS-232C devices.

CPM1-CIF01

RS-232C cable

RS-232C to RS-232C; PC connection for program download; cable length 2 m

C200HS-CN220-EU

RS-232C to RS-232C for PLC communication; cable length 2 m

C200H-CN320-EU

Converts data communications from peripheral port for RS-422/RS-485 devices.

CPM1-CIF11

RS-422/RS-485 adapter

J PROGRAM TRANSFER EQUIPMENT Product

Description

Part number

Expansion Memory Unit

Uploads and downloads program and setup memory areas to and from the controller.

CPM1-EMU01-V1

EEPROM (256 kbits)

Used with the Expansion Memory Unit

CPM1-EEPROM-EMU01

Product

Description

Part number

Operation manual

CPM1A DC Input CPUs operation manual

W317

CPM1A AC Input CPUs operation manual

P12FAZ1

CPM1/CPM1A programming manual

W353

J MANUALS

Programming manual

3

Page 4

CPM1A

CPM1A

Specifications J GENERAL SPECIFICATIONS Input type

DC input

CPU type

10-point I/O

AC input 20-point I/O

30-point I/O

40-point I/O

20-point I/O

Power supply voltage/frequency

AC power supply

100 to 240 VAC, 50/60 Hz

DC power supply

24 VDC

Operating voltage range

AC power supply

85 to 264 VAC

DC power supply

20.4 to 26.4 VDC

Power consumption

AC power supply

30 VA max.

60 VA max.

30 VA max.

DC power supply

6 W max.

20 W max., 30 A max.

60 A max.

30 A max.

Inrush current External power supply (AC only)

Power supply voltage

24 VDC

Power supply output capacity

200 mA

32-point I/O, - 60 VA max. 60 A max.

300 mA

Insulation resistance

20 MΩ min. at 500 VDC between the AC terminals and the protective earth terminal.

Dielectric strength

2,300 VAC at 50/60 Hz for one minute with a leakage current of 10 mA max. between all the external AC terminals and the protective earth terminal.

Noise resistance

Conforms to IEC61000-4-4, 2 kV (power lines) 1500 Vp-p, pulse width 0.1 to 1 µs, rise time: 1 ns (via noise simulation)

Vibration resistance

10 to 61.2 Hz with an amplitude of 0.075 mm, and 57 to 150 Hz with an acceleration of 1.5 G in the X, Y, and Z directions for 10 sweeps of minutes each.

Shock resistance

147 m/s2 in the X, Y and Z directions 3 times each.

Ambient temperature

Operating

0°C to 55°C (32°F to 131°F)

Storage

–20°C to 75°C (–4°F to 167°F)

Ambient humidity

Operating

10% to 90% RH no condensation

Ambient environment

Operating

With no corrosive gas

20 G the X, Y and Z directions 3 times each.

Terminal screw size

M3

Power supply holding time

10 ms min. for AC models, and 2 ms min. for DC models

Weight

AC models

400 g max.

500 g max..

600 g max..

700 g max.

500 g max.

575 g max.

DC models

300 g max.

400 g max.

500 g max.

600 g max., - Note: The specifications of the Expansion I/O Modules are the same as for the CPU except that the power is supplied from the CPU and the weight is 300 g.

4

Page 5

CPM1A

CPM1A J CHARACTERISTICS Input type

DC input

CPU type

10-point I/O

AC input

Control method

Stored program method

I/O control method

Combination of the cyclic scan and immediate refresh processing methods.

Programming language

Ladder diagram

Instruction word

1 step per instruction, 1 to 5 words per instruction

20-point I/O

Types of instructions

Basic instructions

14 types

Special instructions

79 types, 139 instructions

Instruction execution time

Basic instructions

0.72 to 16.2 µs

Special instructions

MOV instruction = 16.3 µs

30-point I/O

40-point I/O

20-point I/O

32-point I/O

Program capacity

2,048 words

User data memory

1,024 words

Maximum I/O points

CPU only

10 points (6 input/ 4 output points)

20 points (12 input/ 8 output points)

30 points (18 input/ 12 output points)

40 points (24 input/ 16 output points)

20 points (12 input/ 8 output points)

32 points (20 input/ 12 output points

With Expansion I/O Module, - Up to 90 points (54 input/ 36 output points)

Up to 100 points (60 input/ 40 output points)

Up to 80 points (48 input/ 32 output points)

Up to 92 points (56 input/ 36 output points)

Memory protection

Maintains the contents of the HR, AR, Counter and Data Memory Areas.

Memory backup

Flash memory: Super capacitor:

User program, data memory (Read only) and PLC setup area are backed up without a battery. Data memory (Read/Write), holding bits, auxiliary memory bits, counter values, error log area are backed up by a capacitor for 20-days at an ambient temperature of 25°C.

Self-diagnostic function

CPU error (watchdog timer), memory errors, I/O bus errors

Program check

No END instruction programming errors (constantly checked during operation)

Pulse output

1 point:

High-speed counter

1 point: Single phase at 5 kHz or two-phase at 2.5 kHz (linear counting method) Incremental mode: 0 to 65535 (16-bit) Decremental mode: –32767 to 32767 (16-bit)

Quick-response inputs

Together with the external interrupt input (minimum pulse width of 0.2 ms)

Input time constant

Can be set at 1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, or 128 ms.

Interrupt processing: External interrupt

2 points (Response time of 0.3 ms max.)

Analog settings

2 points: (0 to 200 BCD)

2 kHz

4 points (Response time of 0.3 ms max.)

4 points (Response time of 5 ms max.)

J I/O ALLOCATION Input bits

00000 to 00915; words not used for input or output bits can be used for work bits.

Output bits

01000 to 01915; words not used for input or output bits can be used for work bits.

Work bits (IR Area)

512: IR 20000 to IR 23115 (IR 200 to IR 231)

Special bits (SR Area)

384: SR 23200 to SR 25515 (SR 232 to SR 255)

Temporary bits (TR Area)

8: TR 0 to TR 7

Holding bits (HR Area)

320: HR 0000 to HR 1915 (HR 00 to HR 19)

Auxiliary bits (AR Area)

256: AR 0000 to AR 1515 (AR 00 to AR 15)

Link bits (LR Area)

256: LR 0000 to LR 1515 (LR 00 to LR 15)

Timers/Counters

128: TIM/CNT 000 to 127 100-ms timer: TIM 000 to TIM 127 10-ms timer: TIM 000 to TIM 127 Decremental counter, reversible counter

Data memory

Read/Write

1,024 words (DM 0000 to DM 1023)

Read only

512 words (DM 6144 to DM 6655)

5

Page 6

CPM1A

CPM1A

J I/O SPECIFICATIONS CPU Unit AC-Input Item

Specification

Input voltage

120 VAC/DC nominal, range 85 to 132

Input impedance

17 kΩ AC @ 60Hz, 69kΩ DC

Input current

7.2 mA AC, 1.7 mA DC @ 120 V typical for: CPM1A-20CAR-A, Inputs 00 to 11 CPM1A-32CAR-A, Ch 0 Inputs 00 to 11 and CPM1A-32CAR-A, Ch 1 Inputs 00 to 03 1.9 mA AC or DC @ 120 V typical for: CPM1A-32CAR-A, Ch 1 Inputs 04 to 07 only

ON voltage

65 VAC/DC

OFF voltage

25 VAC/DC

ON delay

1 to 128 ms max. Default: 8 ms (See Note.)

OFF delay

1 to 128 ms max. Default: 8 ms (See Note.)

Circuit configuration 470 Ω 120 VAC

Input LED

CPM1A-20CAR-A Inputs 00-11

Internal circuits

CPM1A-32CAR-A Inputs Ch 0: 00-11 Inputs Ch 1: 00-03

68 Ω 0.15 µF

2.2 kΩ

Input LED 68 Ω 2.2 kΩ

120 VAC

CPM1A-32CAR-A only Inputs Ch 1: 04-07

Internal circuits

Note: Using the PLC Setup, 1, 2, 4, 8, 16, 32, 64, or 128 ms can be selected. When IN00000 through IN00002 are used as high-speed counter inputs, the delays are as shown in the following table. Typically for AC inputs, the delay is set at the default, 8 ms. Input

Increment mode

Differential phase mode

IN00000 (A-phase)

20 Hz

20 Hz

IN00001 (B-phase)

Normal input

IN00002 (Z-phase)

ON: 5 ms min.; OFF delay: 5 ms min.

The minimum delay is as follows. Increment Mode (20 Hz max.)

100 ms min. 50 ms min.

ON A-phase OFF

50 ms min.

Differential Phase Mode (20 Hz max.) IN00000 (A phase), IN00001 (B phase) 100 ms min. ON

IN00002 (Z phase) 5 ms min. ON Z-phase

A-phase OFF ON B-phase OFF

OFF 50 ms min. T1

T2

T3

T4 T1 T2 T3 T4 : 20 ms min.

When IN00003 through IN00006 are used as interrupt inputs, the delay is 0.3 ms max. The delay is measured from the time that the input goes ON until the interrupt subroutine is executed.

6

Page 7

CPM1A

CPM1A CPU Unit DC Input Item

Specifications

Input voltage

24 VDC +10%/–15%

Input impedance

IN0000 to IN0002: 2 kΩ Others: 4.7 kΩ

Input current (typical)

IN0000 to IN0002: 12 mA Others: 5 mA

ON voltage

14.4 VDC min.

OFF voltage

5.0 VDC max.

ON delay (See Note 1)

1 to 128 ms max. (default: 8 ms) (See Note 1)

OFF delay (See Note 1)

1 to 128 ms max. (default: 8 ms) (See Note 1)

Circuit Input LED 4.7 kΩ IN

Internal Circuits

4.7 kΩ

COM

Note: The polarity of the input power supply can be either positive or negative.

Note: 1. The actual ON/OFF delay includes an input constant of 1, 2, 4, 8, 16, 32, 64, or 128 ms (default: 8 ms). 2. When IN0000 to IN0006 are used for the high-speed counter inputs, the delays are as shown below: Input

Increment mode

Differential phase mode

IN0000 (A-phase)

5 kHz

2.5 kHz

IN0001 (B-phase)

Normal input

IN0002 (Z-phase)

ON: 100 µs max. OFF: 500 µs max.

IN0003 to IN0006

0.3 ms max. (From the time of input ON until the interrupt subroutine is executed.)

Expansion I/O Unit Item

Specifications

Input voltage

24 VDC, +10%/–15%

Input impedance

4.7 kΩ

Input current (typical)

5 mA

ON voltage

14.4 VDC min.

OFF voltage

5.0 VDC max.

ON delay

1 to 128 ms max. (default: 8 ms) (See Note)

OFF delay

1 to 128 ms max. (default: 8 ms) (See Note)

Circuit Input LED 4.7 kΩ IN COM

Internal Circuits

4.7 kΩ

Note: The polarity of the input power supply can be either positive or negative.

Note: The actual ON/OFF delay includes an input constant of 1, 2, 4, 8, 16, 32, 64, or 128 ms (default: 8 ms).

J OUTPUT SPECIFICATIONS (CPU UNIT AND EXPANSION I/O MODULES) Relay Output Item

Specifications

Maximum switching capacity

2 A, 250 VAC (cos φ =1) 2 A, 24 VDC (4 A/common)

Minimum switching capacity

10 mA, 5 VDC

Relay service life

Resistance load

300,000 times

Inductive load

100,000 times

Electrical

Mechanical

Circuit Output LED

Internal Circuits

OUT

OUT COM

10 million times

ON delay

15 ms max.

OFF delay

15 ms max.

Maximum 250 VAC: 2 A 24 VDC: 2 A

7

Page 8

CPM1A

CPM1A

Transistor Output (Sink Type/Source Type) Item

Specifications

Circuit

Maximum switching capacity

300 mA, 24 VDC +10%/–15% (See Note 1)

Sink Type Output LED

Leakage current

0.1 mA max.

Internal Circuits

OUT

OUT

24 VDC

COM (–) Residual voltage

1.5 V max. Source Type Output LED

ON delay

0.1 ms max. COM (+) Internal Circuits

OFF delay

OUT

24 VDC

1 ms max. (See Note 2)

OUT Note: 1. The maximum switching capacity of the CPM1A with transistor outputs (sink type and source type) are limited to the currents shown in the following table for the common and for the Unit. Part number

Max. switching capacity

CPM1A-10CDT, CPM1A-10CDT1-A, CPM1A-10CDT1-D

0.9 A/Unit

CPM1A-20CDT-D, CPM1A-20CDT1-A, CPM1A-20CDT1-D

0.9 A/common; 1.8 A/Unit

CPM1A-30CDT-D, CPM1A-30CDT1-A, CPM1A-30CDT1-D

0.9 A/common; 2.7 A/Unit

CPM1A-40CDT-D, CPM1A-40CDT1-A, CPM1A-40CDT1-D

0.9 A/common; 3.6 A/Unit

CPM1A-20EDT, CPM1A-20EDT1

0.9 A/common; 1.8 A/Unit

CPM1A-8ET, CPM1A-8ET1

0.9 A/common; 1.8 A/Unit

2. When using the pulse output function of the CPM1A with transistor outputs (sink type and source type): The output current must be within a range from 100 to 200 mA when using the output 01000 or 01001 as a pulse output with the maximum frequency of 2 kHz. The outputs 01000 and 01001 will vary depending on the output current.

8

Load current

OFF delay

100 to 200 mA

0.2 ms max.

0 to 300 mA except for the above range

0.5 ms max.