For the Omron CPM1A-8ED

Page 9

CPM1A

CPM1A J ANALOG I/O MODULE Item

Specification

Model

CPM1A–MAD01

I/O type

Voltage

Analog inputs

Current

2

Input signal range

0 to 10 V or 1 to 5 V

4 to 20 mA

Maximum rated input

±15 V

±30 mA

External input impedance

1 MΩ min.

250 Ω rated

Resolution

1/256

Overall precision

1.0% of full scale

Converted A/D data

8-bit binary

Number of outputs

1

Output signal range

0 to 10 V or –10 to 10 V

4 to 20 mA

External output max. current

5 mA, External output allowed load resistance, 350 Ω

Resolution

1/256 (1/512 when the output signal range is –10 to 10 V.)

Overall precision

1.0% of full scale

Data setting

8-bit binary with sign bit

Analog output (See Note 1.)

Number of inputs

Conversion time (See Note 2.)

10 ms/Unit max.

Isolation method

Photocoupler isolation between I/O terminals and PC (There is no isolation between the analog I/O signals.)

Note: 1. The voltage output and current output can be used at the same time, but the total output current cannot exceed 21 mA. 2. The conversion time is the total time for 2 analog inputs and 1 analog output.

J TEMPERATURE SENSOR MODULES By connecting a Temperature Sensor Module (CPM1A-TS001/TS002/TS101/TS101A/TS102) to the CPM1A, inputs can be received from thermocouples or temperatureresistance thermometers. Inputs converted to binary data (4-digit hexadecimal) and stored in the IR area.

Specifications Item

Specification

Model

CPM1A-TS001/TS002

CPM1A-TS101/TS102

CPM1A-TS101-DA

Number of inputs

TS001: 2; TS002: 4

TS101: 2; TS102: 4

2

Input types (See Note 1)

Thermocouple types K or J, selectable Platinum resistance thermometer types Pt100 and JPt1100, selectable

Input resolution

0.1°C in 2’s complement format

0.1°C in 2’s complement format

Input accuracy

±0.5% or ±2% of the stored value whichever is larger ±1 digit max. (See Note 2)

±0.5% or ±1% of the stored value whichever is larger ±1 digit max. (See Note 2)

1.0% max. full scale

Number of outputs

None

None

1

Output types, - Voltage or current output

Output resolution, - 1/256 (0 to 10 V) 1/512 (–10 to +10 V) 1/256 (4 to 20 mA)

Output accuracy, - 1.0% max. full scale

Conversion cycle

250 ms for all points

60 ms max. for all points

Converted temperature data

Binary data (4-digit hexadecimal)

Binary data (8-digit hexadecimal)

Isolation method

Photocoupler isolation between I/O terminals and the PLC

Note: 1. The same input type must be used for all inputs. 2. Accuracy for K thermocouples at temperatures less than –100°C: ±4°C ± 1 digit max.

9

Page 10

CPM1A

CPM1A

Input Temperature Ranges for CPM1A-TS001/TS002 The rotary switch can be used to make of the following range and input type settings for CPM1A-TS001/002 models. Thermocouple input

Range (°C)

Range (°F)

Type K

–200 to 1300

–300 to 2300

0.0 to 500.0

0.0 to 900.0

–100 to 850

–100 to 1500

0.0 to 400.0

0.0 to 750.0

Type J

Input Temperature Ranges for CPM1A-TS101/TS101DA/TS102 The rotary switch can be used to make of the following range and input type settings for CPM1A-TS101/102 models. Platinum RTD input

Range (°C)

Range (°F)

Pt100

–200.0 to 650.0

–300 to 1200.0

JPt100

–200.0 to 650.0

–300 to 1200.0

J COMMUNICATIONS ADAPTER RS-232C Adapter and RS-422 Adapter Model

CPM1-CIF01

CPM1-CIF11

Functions

Level conversion between the CMOS level (CPU side) and the RS-232C (peripheral device side)

Level conversion between the CMOS level (CPU side) and the RS-422 (peripheral device side)

Insulation

The RS-232C (peripheral device side) is insulated by a DC/DC converter and photocoupler.

The RS-422 (peripheral device side) is insulated by a DC/DC converter and photocoupler.

Power supply

Power is supplied by the CPU.

Power consumption

0.3 A max.

Transmission speed

38.4 kbits/s max.

Vibration resistance

10 to 57 Hz with an amplitude of 0.075 mm, and 57 to 150 Hz with an acceleration of 1 G in the X, Y and Z directions for 80 minutes each (i.e. for 8 minutes each, 10 times).

Shock resistance Ambient temperature

1.5 G in the X, Y and Z directions 3 times each. Operating

0°C to 55°C (32°F to 131°F)

0°C to 55°C (32°F to 131°F)

Storage

–20°C to 75°C (–4°F to 167°F)

–20°C to 75°C (–4°F to 167°F)

Ambient humidity

Operating

10% to 90% RH (with no condensation)

Ambient environment

Operating

With no corrosive gas

Weight

10

200 g max.

Page 11

CPM1A

CPM1A J COMPOBUS/S I/O LINK MODULE

The CPM1A controller can function as a Slave to a CompoBus/S Master Module (or SRM1 CompoBus/S Master Control Module) when a CPM1A-SRT21 CompoBus/S I/O Link Module is connected. The CompoBus/S I/O Link Module establishes an I/O link of 8 inputs and 8 outputs between the Master Module and the CPM1A. Up to 3 Expansion I/O Modules or Expansion Modules can be connected to a CPM1A CPU Unit. CompoBus/S Master Module (or SRM1 CompoBus/S Master Control Module)

CPM1A-SRT21 CompoBus/S I/O Link Module

CPM1A CPU Unit

CS1j, C200Hj, CQM1 (H), or SRM1 PC Up to 16 Slaves can be connected. (Up to 8 Slaves with the CQM1-SRM21-V1.)

Flat cable SCA1-4F10 or twisted pair Belden #9409 cable

Specifications Model

CPM1A-SRT21

Master/Slave

CompoBus/S Slave

Number of I/O bits

8 input bits, 8 output bits

Number of words occupied in CPM2A I/O memory

1 input word, 1 output word (Allocated in the same way as other Expansion I/O Modules or Expansion Modules)

Node number setting

Set using the DIP switch.

Note: See the CompoBus/S section of Omron’s Remote I/O and Wiring Solutions Catalog (GC RIO1) for more details on CompoBus/S communications.

Dimensions Unit: mm (inch)

J CPU, EXPANSION I/O AND SPECIAL I/O MODULES

90 (3.54)

W

50 (1.97) DC power supply 85 (3.35) AC power supply

Model

W

CPM1A-10CDj-A/D

66 (2.60)

CPM1A-20CDj-A/D

86 (3.39)

CPM1A-30CDj-A/D

130 (5.12)

CPM1A-40CDj-A/D

150 (5.91)

CPM1A-20CAR-A

130 (51.2)

CPM1A-32CAR-A

150 (5.91)

CPM1A-20EDj

86 (3.39)

CPM1A-8Ej

66 (2.60)

CPM1A-SRT21

66 (2.60)

CPM1A-MAD01

66 (2.60)

CPM1A-TSjjj

86 (3.39)

11

Page 12

CPM1A

CPM1A

Unit: mm (inch)

J COMMUNICATION ADAPTER MODULES CPM1-CIF01

CPM1-CIF11 30 (1.18)

30 (1.18) 56 (2.20) 50

21

21

90 (3.54)

90 (3.54)

81

81

J DIMENSIONS WITH PERIPHERAL DEVICES ATTACHED Approx. 90 (3.54)

12

Approx. 125 (4.92)

61 (2.40) 50

Page 13

CPM1A

CPM1A

Functions J CONFIGURATION The CPM1A CPU units feature a compact, one-piece construction that includes 10, 20, 30 or 40 built-in I/O terminals. Three output models are available: Relay outputs, sinking (NPN) transistor output and sourcing (PNP) transistor output.

CPM1A-10CDj-j (10 I/O terminals)

CPM1A-20CDj-j (20 I/O terminals)

CPM1A-30CDj-j (30 I/O terminals)

CPM1A-40CDj-j (40 I/O terminals)

Expansion Up to three Expansion I/O Modules can be connected to a 30-point or 40-point CPU Unit to add an extra 8 or 20 I/O points for each, for a maximum of up to 100 I/O points.

Dedicated I/O Modules Up to 3 Analog I/O Modules or Temperature Sensor Input Modules can be used with 30-point and 40-point CPU Units. Each analog I/O module provides 2 analog inputs and 1 analog output, so a maximum of 6 analog inputs and 3 analog outputs can be achieved by connecting 3 Analog I/O Modules. Each Temperature Sensor Module provides two temperature sensor inputs from either thermocouples or platinum resistance thermometers. Up to 6 inputs can be connected.

J INTERRUPT INPUTS There are two input interrupts in the CPM1A 10-point I/O CPU and four in the 20-, 30-, and 40-point I/O CPUs. Input interrupts are available in two modes.. In addition to normal interrupt inputs, the CPM1A has a counter mode that counts high-speed input signals and triggers interrupts at fixed count multiples.

Application Example: 10 point I/O CPU

20, 30, and 40 point I/O CPU

Cutting Metal Sheets to Specified Lengths The proximity sensor detects the edge of a metal plate to operate the cutter. Metal sheets can be cut continuously to the specified lengths at a high speed. Metal sheets

Cutter

Cutter operation signal

Conveyor

Proximity sensor Input interrupt

CPM1A

Input Interrupt Mode If an input interrupt occurs, the regular program shuts down irrelevant of the cycle time, and the interrupt processing program is executed immediately.

Regular program

Regular program

Interrupt program

Input interrupt

13

Page 14

CPM1A

CPM1A

Counter Mode When the number of external signals counted at high speed reaches a specified number of counts, the regular program shuts down, and the interrupt processing program is executed at fixed counts. The count can be set between 0 and 65535.

Regular program

Regular program

Interrupt program

Input interrupt

Counter setting

J QUICK-RESPONSE INPUTS Quick-response inputs can detect input signals with a pulse width as short as 0.2 ms regardless of their timing during the scan cycle. Quick-response inputs and interrupt inputs use the same input terminals.

CPU

Input no.

Minimum input pulse width

10 point I/O CPU

00003 to 00004

0.2 ms

20 point, 30 point, 40 point I/O CPU

00003 to 00006

Application Example: Overseeing processes

Program execution

0.2 ms min Input signal (00003)

I/O refreshing

Overseeing Program processes execution

I/O refreshing

Calculating the Number of Chips The metal sensor counts the number of parts that have passed. Steady counting can be achieved even when the input-ON time is short. CPM1A

IR 00003 One cycle F2LP-WK4 F2LP-W

14

Page 15

CPM1A

CPM1A J HIGH-SPEED COUNTER The CPM1A has a high-speed counter function that can be used in the incrementing and up/down mode. Using this function together with the input interrupts enables zone comparison control or target value control irrelevant of the cycle time.

Counting mode

Incrementing mode

Up/Down mode

Input no.

00000

Count input

A-phase input

00001, B-phase input

00002

Reset input

Z-phase input

Input method

Single-phase input

Phase-difference, 4× inputs

Count frequency

5.0 kHz

2.5 kHz

Count range

0 to 65535

–32767 to 32767

Note: When using in the incrementing mode, the input 00001 can be used as an input contact. Count input

00000 00001 00002

Reset input Solenoid

Sensor

Rotary encoder

Inverter, etc.

15

Page 16

CPM1A

CPM1A

J INTERVAL TIMER INTERRUPTS The CPM1A has one interval timer. The interval timer shuts down the regular program regardless of the point in the cycle once the time is up, and immediately executes an interrupt processing program. Interval timers are used in the following two modes. Item

One-shot mode

Scheduled interrupt mode

Operation

An interrupt is executed only once when the time is up.

Interrupts are executed repeatedly at fixed periods.

Setting time

0.5 ms to 319,968 ms (0.1-ms units)

Application Example:

Normal program

Computing the Sheet Speed The number of pulse inputs is computed in the interrupt mode at a fixed time to calculate the speed.

Interval timer MOV(21) ADD(30)

CPM1A

Interrupt processing program Encoder SBN(92) 00

MOV(21)

RET(93) END(01)

J ANALOG SETTING The CPM1A contains two analog setting controls that can be used for a broad range of analog timer and counter settings. Turning the setting control stores values of 0 to 200 (BCD data) in the SR area. Analog setting

Storage area

Setting value (BCD)

Analog setting 0

SR 250

0000 to 0200

Analog setting 1

SR 251

Application Example: Analog setting 0 Analog setting 1 *Phillips screwdriver is required.

Tact Operation Control of Conveyor Lines A conveyor can be stopped temporarily as required for assembly processes. When the timer function and limit switches are used in a combination, conveyors can be stopped for a fixed time or can be run at a constant speed for a fixed distance. Fine adjustment of the stopping time can be easily done by using the analog setting controls.

CPM1A LS

Motor

16