The text of a manual · part 37 of 48
SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Appendices, pages 313 to 322
Pages 313 to 322 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual
The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213
Page 313
Appendices z CJ1W-MD263 DC Input/Transistor Output Unit (24 VDC 32 Inputs/32 Outputs) Name
32-point DC Input/32-point Transistor Output Unit with MIL Connectors (Sinking Outputs)
Model
CJ1W-MD263
Output section (CN1)
Input section (CN2)
Rated Voltage
12 to 24 VDC
Rated Input Voltage
24 VDC
Operating Load Voltage Range
10.2 to 26.4 VDC
Operating Input Voltage
20.4 to 26.4 VDC
Maximum Load Current
0.3 A/point, 1.6 A/common, 3.2 A/Unit
Maximum Inrush Current
3.0 A/point, 10 ms max.
Leakage Current Residual Voltage
4.1 mA typical (at 24 VDC)
Input Current
0.1 mA max.
ON Voltage/ON Current
19.0 VDC min./3 mA min.*2
1.5 V max.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
ON Response Time
0.5 ms max.
OFF Response Time
1.0 ms max.
No. of Circuits
32 (16 points/common, 2 circuits)
Fuse
None
External Power Supply
5.6 kΩ
Input Impedance
8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1
ON Response Time
12 to 24 VDC, 30 mA min.
8.0 ms max. (Can be set to between 0 and 32 in
OFF Response Time the PLC Setup.)*1 32 (16 points/common, 2 circuits)
Number of Simultaneously ON Points
75% (24 points) (at 24 VDC)
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (at 100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Internal Current Consumption
5 VDC 140 mA max.
Weight
110 g max.
Accessories
None CN2 (IN)
to IN15
Internal circuits
OUT15
Output indicator
COM2 COM2
COM0 COM0
Indicator switch
+V to COM1 COM1
Wd m+1
Wd m+3 to IN15
24 VDC
30
Input voltage: 26.4 VDC
25 12 points/ common at 55°C
20 15
8 points/ common at 55°C
10 5 0
0
20
40
60 (°C)
Ambient Temperature
A-1-2 Basic I/O Units
OUT15
CJ2 CPU Unit Hardware User’s Manual
IN0
OUT0
Indicator switch Input indicator 5.6 kΩ
35
Number of Simultaneously ON Points vs. Ambient Temperature Characteristic 32 points at 38°C 32 points at 44°C Input voltage:
App
Circuit Configuration
Wd m
Internal circuits to
560 Ω
Wd m+2
OUT0
5.6 kΩ 1000 pF
IN0
560 Ω
+V
1000 pF
Signal Allocated name CIO word
Allocated Signal CIO word name
Number of simultaneously ON points
CN1 (OUT)
A-1 Specifications of Basic I/O Units
No. of Circuits
COM3 COM3
A-51
Page 314
Appendices
CN1 (OUT) Allocated CIO word
Allocated CIO word
Signal name
Signal name
Connector pin
L
OUT0
L
40 39 OUT8 38 37 OUT9
L
OUT1
L
OUT2
L
L
OUT3
36 35 OUT10 34 33 OUT11
L
OUT4 OUT5
32 31 OUT12 30 29 OUT13
L
L L
OUT6 OUT7
28 27 OUT14 26 25 OUT15
L
L
CN2 (IN) Signal Connec- Signal name tor pin name
Allocated CIO word
Allocated CIO word
OUT0
L
OUT1
L
OUT2
L
OUT3
L
OUT4
L
16 15 OUT10 14 13 OUT11
L
IN11 IN10 IN9 IN8
L
NC COM2
L
IN15
L
IN14
L
L
OUT5
12 11 OUT12 10 9 OUT13
L
OUT6
8 7
OUT14
L
L
OUT7
6 5
OUT15
L
COM1
4 3
COM1
+V
2 1
+V
L
IN13 IN12 IN11 24 VDC
12 to 24 VDC
• Be sure to wire both terminals 23 and 24 (COM0) of CN1. • Be sure to wire both terminals 3 and 4 (COM1) of CN1. • Be sure to wire both terminals 21 and 22 (+V) of CN1.
IN10 IN9 IN8
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
NC COM3 IN7 IN6 IN5 IN4 IN3 IN2
Wd m+3
IN13 IN12
Wd m+3
L
IN14 Wd m
L
IN15
1 2
IN1 IN0 NC COM2 IN7 IN6 IN5 IN4 IN3 IN2
Wd m+2
L
24 23 COM0 +V 22 21 OUT8 20 19 18 17 OUT9
NC COM3
Wd m+2
Terminal Connections
Wd m+1
COM0 +V
L
Wd m+1
Wd m
24 VDC 12 to 24 VDC
IN1 IN0
• Be sure to wire both pins 23 and 24 (COM2) of CN2, and set the same polarity for both pins.
• Be sure to wire both terminals 1 and 2 (+V) of CN1.
• Be sure to wire both pins 3 and 4 (COM3) of CN2, and set the same polarity for both pins.
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if polarity is reversed.
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if polarity is reversed.
*1 The ON response time will be 120 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor. • Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V). • Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.
A-52
CJ2 CPU Unit Hardware User’s Manual
Page 315
Appendices z CJ1W-MD232 DC Input/Transistor Output Unit (24 VDC, 16 inputs/16 Outputs) Name
16-point DC Input/16-point Transistor Output Unit with MIL Connectors (Sourcing Outputs)
Model
CJ1W-MD232
Output section (CN1)
Input section (CN2) 24 VDC
Rated Input Voltage
24 VDC
Operating Load Voltage Range
20.4 to 26.4 VDC
Operating Input Voltage
20.4 to 26.4 VDC
Maximum Load Current
0.5 A/point, 2.0 A/Unit
Input Impedance
3.3 kΩ
Leakage Current
0.1 mA max.
Input Current
7 mA typical (at 24 VDC)
1.5 V max.
ON Voltage/ON Current
14.4 VDC min./3 mA min.
0.5 ms max.
OFF Voltage/OFF Current
5 VDC max./1 mA max.
1.0 ms max.
ON Response Time
8.0 ms max. (Can be set to between 0 and 32 in the
Rated Voltage
Residual Voltage ON Response Time OFF Response Time
Load Short-circuit Protection
No. of Circuits
Detection current: 0.7 to 2.5 A min.
PLC Setup.)*1 8.0 ms max. (Can be set to between 0 and 32 in the
OFF Response Time
Automatic restart after error clearance. (Refer to page A149.) 16 (16 points/common, 1 circuit)
No. of Circuits
16 (16 points/common, 1 circuit) 75% (at 24 VDC)
External Power Supply
20.4 to 26.4 VDC, 40 mA min.
Insulation Resistance
20 MΩ between the external terminals and the GR terminal (at 100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Weight
100 g max.
Accessories
None CN1 (OUT) Allocated CIO word
Allocated Signal CIO word name to
Wd m+1
OUT0
3.3 kΩ
IN0
Wd m to IN7
OUT7 0V
App
Short-circuit Protection
COM0 (+V)
1000 pF
Signal name
CN2 (IN)
Input indicator Output indicator to
OUT15 0V to IN15
Wd m
470 Ω
OUT8
IN8
1000 pF
Circuit Configuration
Wd m+1
Short-circuit Protection
COM0 (+V)
3.3 kΩ
A-1-2 Basic I/O Units
Internal circuits
COM1
Internal circuits
5 VDC 130 mA max.
470 Ω
Internal Current Consumption
CJ2 CPU Unit Hardware User’s Manual
Number of simultaneously ON points
COM1
ERR indicator
Number of Simultaneously ON Points vs. Ambient Temperature Characteristic 16 points at 33°C 16 points at 45°C
Input voltage: 24 VDC Input voltage: 26.4 VDC
18 16 14 12 10
12 points at 55°C
8 6
9 points at 55°C
4 2 0
0
A-1 Specifications of Basic I/O Units
Number of Simultaneously ON Points
PLC Setup.)*1
20
40
60 (°C)
Ambient Temperature
A-53
Page 316
Appendices
L L
Wd m
L L L L
Terminal Connections
24 VDC
OUT1 OUT2 OUT3 OUT4 OUT5 OUT6
20 19 18 17 16 15 14 13 12 11 10
9
8
7
OUT7 6 L COM0 (+V) 4 0V 2
5 3 1
OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14
Allocated CIO word
Allocated CIO word
L L L L L L L
OUT15
L COM0 (+V) 0V
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if polarity is reversed. • Be sure to wire both terminals 3 and 4 (COM0 (+V)) of CN1.
Wd m+1
L
OUT0
Wd m
Allocated CIO word
CN2 (IN)
24 VDC
Signal Connec- Signal name name tor pin NC
1
2
NC
COM1
3
4
COM1
IN15
5
6
IN7
IN14
7
8
IN6
IN13
9
10
IN5
IN12
11 12
IN4
IN11
13 14
IN3
IN10
15 16
IN2
IN9
17 18
IN1
IN8
19 20
IN0
Allocated CIO word
Wd m+1
CN1 (OUT) Signal Connec- Signal name name tor pin
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if polarity is reversed. • Be sure to wire both pins 3 and 4 (COM1) of CN2, and set the same polarity for both pins.
• Be sure to wire both terminals 1 and 2 ((0 V)) of CN1.
*1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays.
A-54
CJ2 CPU Unit Hardware User’s Manual
Page 317
Appendices z CJ1W-MD563 TTL I/O Unit (32 Inputs/32 Outputs) Name
32-point Input /32-point Output TTL I/O Unit with MIL Connectors
Model
CJ1W-MD563
Output section (CN1) Rated Voltage Operating Load Voltage Range
Input section (CN2) 5 VDC±10%
Rated Input Voltage
4.5 to 5.5 VDC
Input Impedance
5 VDC±10% 1.1 kΩ
Maximum Load Current
35 mA/point, 560 mA/common, 1.12 A/Unit
Input Current
Leakage Current
0.1 mA max.
ON Voltage
3.0 VDC min.
Residual Voltage
0.4 V max.
OFF Voltage
1.0 VDC max.
0.2 ms max.
ON Response Time
8.0 ms max. (Can be set to between 0 and 32 in the
ON Response Time
Approx. 3.5 mA (at 5 VDC)
PLC Setup.)*1 8.0 ms max. (Can be set to between 0 and 32 in the
OFF Response Time
0.3 ms max.
No. of Circuits
32 points (16 points/common, 2 circuits)
Fuse
None
No. of Circuits
32 points (16 points/common, 2 circuits)
5 VDC±10%, 40 mA min. (1.2 mA × No. of ON points)
Number of Simultaneously ON Points
100% (16 points/common)
External Power Supply Insulation Resistance
20 MΩ between the external terminals and the GR terminal (at 100 VDC)
Dielectric Strength
1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.
Signal name
CN2 (IN) Allocated CIO word
Allocated CIO word
Signal name
Wd m+2
IN0 to IN15
+V
Circuit Configuration
Internal circuits
5.6 kΩ
Output indicator
OUT0 to OUT15
Wd m
1.1 kΩ
COM2 COM2
COM0 COM0
Indicator switch Input indicator
Indicator switch
1.1 kΩ
+V OUT0 to OUT15 COM1 COM1
Wd m+3 Wd m+1
IN0 to IN15
App
5.6 kΩ
Internal circuits
CN1 (OUT)
2.2 kΩ
None
2.2 kΩ
110 g max.
Accessories
1000 pF
Weight
1000 pF
5 VDC 190 mA max.
PLC Setup.)*1
A-1 Specifications of Basic I/O Units
Internal Current Consumption
OFF Response Time
COM3 COM3
A-1-2 Basic I/O Units
CJ2 CPU Unit Hardware User’s Manual
A-55
Page 318
Appendices
CN1 (OUT) Allocated CIO word
Signal name
Connector pin
CN2 (IN)
Signal name
Allocated CIO word
Allocated CIO word
Signal name
Connector pin
Signal name
Allocated CIO word
40 39
OUT8
L
OUT1
38 37
OUT9
L
COM3
L
OUT2
36 35
OUT10
L
IN15
L
OUT3
34 33
OUT11
L
IN14
L
OUT4
32 31
OUT12
L
IN13
L
OUT5
30 29
OUT13
L
L
OUT6
28 27
OUT14
L
L
OUT7
26 25
OUT15
L
COM0
22 21
Wd m+3
Wd m
IN12 IIN11 IN10
COM0
IN9
+V
IN8
L
OUT0
20 19
OUT8
L
NC
L
OUT1
18 17
OUT9
L
COM2
L
OUT2
16 15
OUT10
L
IN15
L
OUT3
14 13
OUT11
L
IN14
L
OUT4
12 11
OUT12
L
L
OUT5
10 9
OUT13
L
L
OUT6
8
7
OUT14
L
L
OUT7
6
5
OUT15
L
COM1
4
3
COM1
+V
2
1
+V
IN13 IN12 Wd m+2
Terminal Connections
Wd m+1
+V
24 23
NC
5 VDC
IN11 IN10 5 VDC
5 VDC
IN9 IN8
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
NC COM3 IN7 IN6 IN5 IN4 IN3 IN2
Wd m+3
OUT0
L
IN1 IN0 NC COM2 IN7 IN6 IN5 IN4 IN3 IN2
Wd m+2
L
Wd m+1
Wd m
5 VDC
IN1 IN0
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.
• Be sure to wire both terminals 23 and 24 (COM0) of CN1.
• Be sure to wire both pins 23 and 24 (COM2) of CN2, and set the same polarity for both pins.
• Be sure to wire both terminals 3 and 4 (COM1) of CN1.
• Be sure to wire both pins 3 and 4 (COM3) of CN2, and set the same polarity for both pins.
• Be sure to wire both terminals 21 and 22 (+V) of CN1. • Be sure to wire both terminals 1 and 2 (+V) of CN1.
*1 The ON response time will be 120 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays.
A-56
CJ2 CPU Unit Hardware User’s Manual
Page 319
Appendices
A-1-3
Precautions on Contact Output Units
Service Life Expectancy of CJ1W-OC201/211 Relays The service life expectancy of the relays (NY-24W-K-IE) in the CJ1W-OC201/211 Contact Output Units is shown in the following diagrams. Use the diagrams to calculate the relay service life based on the operating conditions, and replace the relay before the end of its service life.
Contact Current vs. Service Life Characteristic Service Life with AC Load
100
240 VAC, resistive load
50 30 20
240 VAC cos φ = 0.4
10 120 VAC cos f = 0.4
5
24 VDC τ = 7 ms
300 200
120 VAC, resistive load
Service life (×104)
Service life (×104)
300 200
Service Life with DC Load
100 50 24 VDC, resistive load
30 20 10 5 3 2
3 2
0.2
0.3
0.5 0.7
1
2
3
5
Contact current (A)
0.1
0.2
0.3
0.5 0.7
1
2
3
5
Contact current (A) Switching frequency: 1,800 operations/hour max.
Precautions for Correct Use The diagrams show the life expectancy of the relay itself. Do not use a contact current, therefore, that exceeds the maximum switching capacity specified in the specifications for each Contact Output Unit. If a switching capacity exceeding the specifications is used, the reliability and life expectancy of other parts will be reduced and the Unit may malfunction.
Be sure to connect a diode in parallel with every DC inductive load that is connected to the Contact Output Unit.
Contact Protection Circuit Arc killers are used with the Contact Output Unit in order to prolong the life of each Relay mounted to the Contact Output Unit, prevent noise, and reduce the generation of carbide and nitrate deposits. However, if arc killers are used incorrectly, they can reduce relay life. Using an arc killer can also cause a delay in the resetting time (shut-off time). Arc killer circuit examples are listed in the following table.
CJ2 CPU Unit Hardware User’s Manual
A-57
A-1-3 Precautions on Contact Output Units
The life of the Relay varies with the load inductance. If any inductive load is connected to the Contact Output Unit, use an arc killer with the Contact Output Unit using an inductive load. (See next page.)
App
Inductive Load
A-1 Specifications of Basic I/O Units
0.05
0.1
Page 320
Appendices
Current
Circuit
Power supply
DC
Yes
Yes
Inductive load
CR method
AC
C R
Characteristic
Required element
If the load is a relay or solenoid, there is a time lag between the moment the circuit is opened and the moment the load is reset.
The capacitance of the capacitor must be 1 to 0.5 µF per contact current of 1 A and resistance of the resistor must be 0.5 to 1 Ω per contact voltage of 1 V. These values, however, vary with the load and the characteristics of the relay. Decide these values from experiments, and take into consideration that the capacitance suppresses spark discharge when the contacts are separated and the resistance limits the current that flows into the load when the circuit is closed again.
If the supply voltage is 24 or 48 V, insert the arc killer in parallel with the load. If the supply voltage is 100 to 200 V, insert the arc killer between the contacts.
The dielectric strength of the capacitor must be 200 to 300 V. If the circuit is an AC circuit, use a capacitor with no polarity. No
Yes
Inductive load
Diode method Power supply
Yes
Power supply
Inductive load
Varistor method
Yes
The diode connected in parallel with the load changes energy accumulated by the coil into a current, which then flows into the coil so that the current will be converted into Joule heat by the resistance of the inductive load. This time lag, between the moment the circuit is opened and the moment the load is reset, caused by this method is longer than that caused by the CR method.
The reversed dielectric strength value of the diode must be at least 10 times as large as the circuit voltage value. The forward current of the diode must be the same as or larger than the load current.
The varistor method prevents the imposition of high voltage between the contacts by using the constant voltage characteristic of the varistor. There is time lag between the moment the circuit is opened and the moment the load is reset.
---
The reversed dielectric strength value of the diode may be two to three times larger than the supply voltage if the arc killer is applied to electronic circuits with low circuit voltages.
If the supply voltage is 24 or 48 V, insert the varistor in parallel with the load. If the supply voltage is 100 to 200 V, insert the varistor between the contacts.
Do not connect a capacitor as an arc killer in parallel with an inductive load as shown in the following diagram. This arc killer is very effective for preventing spark discharge at the moment when the circuit is opened. However, when the contacts are closed, the contacts may be welded due to the current charged in the capacitor. DC inductive loads can be more difficult to switch than resistive loads. If appropriate arc killers are used, however, DC inductive loads will be as easy to switch as resistive loads.
A-58
Power supply
C
Inductive load
Precautions for Correct Use
CJ2 CPU Unit Hardware User’s Manual
Page 321
Appendices
A-1-4
Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals
Patterns for Combining Connector-Terminal Block Conversion Units and I/O Relay Terminals The following patterns can be used to connect Basic I/O Units with Connectors to OMRON ConnectorTerminal Block Conversion Units and I/O Relay Terminals using OMRON Connecting Cables.
z Connection Patterns for Connector-Terminal Block Conversion Units Pattern A
Configuration
Number of connectors 1
Connecting Cable
Branching None
Connector-Terminal Block Conversion Unit
40 or 60 terminals
B
2 branches
Connecting Cable with two branches Connector-Terminal Block Conversion Unit
C
A-1 Specifications of Basic I/O Units
20 terminals
20 terminals
2
Connecting Cable
None
Connector-Terminal Block Conversion Unit
20 terminals
D
20 terminals
Connecting Cable Connector-Terminal Block Conversion Unit
40 or 60 terminals
F
Connecting Cable with two branches
App
40 or 60 terminals
2 branches
Connector-Terminal Block Conversion Unit
CJ2 CPU Unit Hardware User’s Manual
A-1-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals
20 terminals 20 terminals
20 terminals 20 terminals
A-59
Page 322
Appendices z Connection Patterns for I/O Relay Terminals Pattern
Configuration
A Connecting Cable
I/O Relay Terminal
B I/O Relay Terminal
I/O Relay Terminal
Connecting Cable
E
I/O Relay Terminal
I/O Relay Terminal
Connecting Cable
F Connecting Cable
I/O Relay Terminal
A-60
CJ2 CPU Unit Hardware User’s Manual