Page 313

Appendices z CJ1W-MD263 DC Input/Transistor Output Unit (24 VDC 32 Inputs/32 Outputs) Name

32-point DC Input/32-point Transistor Output Unit with MIL Connectors (Sinking Outputs)

Model

CJ1W-MD263

Output section (CN1)

Input section (CN2)

Rated Voltage

12 to 24 VDC

Rated Input Voltage

24 VDC

Operating Load Voltage Range

10.2 to 26.4 VDC

Operating Input Voltage

20.4 to 26.4 VDC

Maximum Load Current

0.3 A/point, 1.6 A/common, 3.2 A/Unit

Maximum Inrush Current

3.0 A/point, 10 ms max.

Leakage Current Residual Voltage

4.1 mA typical (at 24 VDC)

Input Current

0.1 mA max.

ON Voltage/ON Current

19.0 VDC min./3 mA min.*2

1.5 V max.

OFF Voltage/OFF Current

5 VDC max./1 mA max.

ON Response Time

0.5 ms max.

OFF Response Time

1.0 ms max.

No. of Circuits

32 (16 points/common, 2 circuits)

Fuse

None

External Power Supply

5.6 kΩ

Input Impedance

8.0 ms max. (Can be set to between 0 and 32 in the PLC Setup.)*1

ON Response Time

12 to 24 VDC, 30 mA min.

8.0 ms max. (Can be set to between 0 and 32 in

OFF Response Time the PLC Setup.)*1 32 (16 points/common, 2 circuits)

Number of Simultaneously ON Points

75% (24 points) (at 24 VDC)

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (at 100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Internal Current Consumption

5 VDC 140 mA max.

Weight

110 g max.

Accessories

None CN2 (IN)

to IN15

Internal circuits

OUT15

Output indicator

COM2 COM2

COM0 COM0

Indicator switch

+V to COM1 COM1

Wd m+1

Wd m+3 to IN15

24 VDC

30

Input voltage: 26.4 VDC

25 12 points/ common at 55°C

20 15

8 points/ common at 55°C

10 5 0

0

20

40

60 (°C)

Ambient Temperature

A-1-2 Basic I/O Units

OUT15

CJ2 CPU Unit Hardware User’s Manual

IN0

OUT0

Indicator switch Input indicator 5.6 kΩ

35

Number of Simultaneously ON Points vs. Ambient Temperature Characteristic 32 points at 38°C 32 points at 44°C Input voltage:

App

Circuit Configuration

Wd m

Internal circuits to

560 Ω

Wd m+2

OUT0

5.6 kΩ 1000 pF

IN0

560 Ω

+V

1000 pF

Signal Allocated name CIO word

Allocated Signal CIO word name

Number of simultaneously ON points

CN1 (OUT)

A-1 Specifications of Basic I/O Units

No. of Circuits

COM3 COM3

A-51

Page 314

Appendices

CN1 (OUT) Allocated CIO word

Allocated CIO word

Signal name

Signal name

Connector pin

L

OUT0

L

40 39 OUT8 38 37 OUT9

L

OUT1

L

OUT2

L

L

OUT3

36 35 OUT10 34 33 OUT11

L

OUT4 OUT5

32 31 OUT12 30 29 OUT13

L

L L

OUT6 OUT7

28 27 OUT14 26 25 OUT15

L

L

CN2 (IN) Signal Connec- Signal name tor pin name

Allocated CIO word

Allocated CIO word

OUT0

L

OUT1

L

OUT2

L

OUT3

L

OUT4

L

16 15 OUT10 14 13 OUT11

L

IN11 IN10 IN9 IN8

L

NC COM2

L

IN15

L

IN14

L

L

OUT5

12 11 OUT12 10 9 OUT13

L

OUT6

8 7

OUT14

L

L

OUT7

6 5

OUT15

L

COM1

4 3

COM1

+V

2 1

+V

L

IN13 IN12 IN11 24 VDC

12 to 24 VDC

• Be sure to wire both terminals 23 and 24 (COM0) of CN1. • Be sure to wire both terminals 3 and 4 (COM1) of CN1. • Be sure to wire both terminals 21 and 22 (+V) of CN1.

IN10 IN9 IN8

3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

NC COM3 IN7 IN6 IN5 IN4 IN3 IN2

Wd m+3

IN13 IN12

Wd m+3

L

IN14 Wd m

L

IN15

1 2

IN1 IN0 NC COM2 IN7 IN6 IN5 IN4 IN3 IN2

Wd m+2

L

24 23 COM0 +V 22 21 OUT8 20 19 18 17 OUT9

NC COM3

Wd m+2

Terminal Connections

Wd m+1

COM0 +V

L

Wd m+1

Wd m

24 VDC 12 to 24 VDC

IN1 IN0

• Be sure to wire both pins 23 and 24 (COM2) of CN2, and set the same polarity for both pins.

• Be sure to wire both terminals 1 and 2 (+V) of CN1.

• Be sure to wire both pins 3 and 4 (COM3) of CN2, and set the same polarity for both pins.

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if polarity is reversed.

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if polarity is reversed.

*1 The ON response time will be 120 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays. Note Observe the following restrictions when connecting to a 2-wire sensor. • Make sure the input power supply voltage is larger than the ON voltage (19 V) plus the residual voltage of the sensor (approx. 3 V). • Use a sensor with a minimum load current of 3 mA min. • Connect bleeder resistance if you connect a sensor with a minimum load current of 5 mA or higher.

A-52

CJ2 CPU Unit Hardware User’s Manual

Page 315

Appendices z CJ1W-MD232 DC Input/Transistor Output Unit (24 VDC, 16 inputs/16 Outputs) Name

16-point DC Input/16-point Transistor Output Unit with MIL Connectors (Sourcing Outputs)

Model

CJ1W-MD232

Output section (CN1)

Input section (CN2) 24 VDC

Rated Input Voltage

24 VDC

Operating Load Voltage Range

20.4 to 26.4 VDC

Operating Input Voltage

20.4 to 26.4 VDC

Maximum Load Current

0.5 A/point, 2.0 A/Unit

Input Impedance

3.3 kΩ

Leakage Current

0.1 mA max.

Input Current

7 mA typical (at 24 VDC)

1.5 V max.

ON Voltage/ON Current

14.4 VDC min./3 mA min.

0.5 ms max.

OFF Voltage/OFF Current

5 VDC max./1 mA max.

1.0 ms max.

ON Response Time

8.0 ms max. (Can be set to between 0 and 32 in the

Rated Voltage

Residual Voltage ON Response Time OFF Response Time

Load Short-circuit Protection

No. of Circuits

Detection current: 0.7 to 2.5 A min.

PLC Setup.)*1 8.0 ms max. (Can be set to between 0 and 32 in the

OFF Response Time

Automatic restart after error clearance. (Refer to page A149.) 16 (16 points/common, 1 circuit)

No. of Circuits

16 (16 points/common, 1 circuit) 75% (at 24 VDC)

External Power Supply

20.4 to 26.4 VDC, 40 mA min.

Insulation Resistance

20 MΩ between the external terminals and the GR terminal (at 100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Weight

100 g max.

Accessories

None CN1 (OUT) Allocated CIO word

Allocated Signal CIO word name to

Wd m+1

OUT0

3.3 kΩ

IN0

Wd m to IN7

OUT7 0V

App

Short-circuit Protection

COM0 (+V)

1000 pF

Signal name

CN2 (IN)

Input indicator Output indicator to

OUT15 0V to IN15

Wd m

470 Ω

OUT8

IN8

1000 pF

Circuit Configuration

Wd m+1

Short-circuit Protection

COM0 (+V)

3.3 kΩ

A-1-2 Basic I/O Units

Internal circuits

COM1

Internal circuits

5 VDC 130 mA max.

470 Ω

Internal Current Consumption

CJ2 CPU Unit Hardware User’s Manual

Number of simultaneously ON points

COM1

ERR indicator

Number of Simultaneously ON Points vs. Ambient Temperature Characteristic 16 points at 33°C 16 points at 45°C

Input voltage: 24 VDC Input voltage: 26.4 VDC

18 16 14 12 10

12 points at 55°C

8 6

9 points at 55°C

4 2 0

0

A-1 Specifications of Basic I/O Units

Number of Simultaneously ON Points

PLC Setup.)*1

20

40

60 (°C)

Ambient Temperature

A-53

Page 316

Appendices

L L

Wd m

L L L L

Terminal Connections

24 VDC

OUT1 OUT2 OUT3 OUT4 OUT5 OUT6

20 19 18 17 16 15 14 13 12 11 10

9

8

7

OUT7 6 L COM0 (+V) 4 0V 2

5 3 1

OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14

Allocated CIO word

Allocated CIO word

L L L L L L L

OUT15

L COM0 (+V) 0V

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if polarity is reversed. • Be sure to wire both terminals 3 and 4 (COM0 (+V)) of CN1.

Wd m+1

L

OUT0

Wd m

Allocated CIO word

CN2 (IN)

24 VDC

Signal Connec- Signal name name tor pin NC

1

2

NC

COM1

3

4

COM1

IN15

5

6

IN7

IN14

7

8

IN6

IN13

9

10

IN5

IN12

11 12

IN4

IN11

13 14

IN3

IN10

15 16

IN2

IN9

17 18

IN1

IN8

19 20

IN0

Allocated CIO word

Wd m+1

CN1 (OUT) Signal Connec- Signal name name tor pin

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if polarity is reversed. • Be sure to wire both pins 3 and 4 (COM1) of CN2, and set the same polarity for both pins.

• Be sure to wire both terminals 1 and 2 ((0 V)) of CN1.

*1 The ON response time will be 20 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays.

A-54

CJ2 CPU Unit Hardware User’s Manual

Page 317

Appendices z CJ1W-MD563 TTL I/O Unit (32 Inputs/32 Outputs) Name

32-point Input /32-point Output TTL I/O Unit with MIL Connectors

Model

CJ1W-MD563

Output section (CN1) Rated Voltage Operating Load Voltage Range

Input section (CN2) 5 VDC±10%

Rated Input Voltage

4.5 to 5.5 VDC

Input Impedance

5 VDC±10% 1.1 kΩ

Maximum Load Current

35 mA/point, 560 mA/common, 1.12 A/Unit

Input Current

Leakage Current

0.1 mA max.

ON Voltage

3.0 VDC min.

Residual Voltage

0.4 V max.

OFF Voltage

1.0 VDC max.

0.2 ms max.

ON Response Time

8.0 ms max. (Can be set to between 0 and 32 in the

ON Response Time

Approx. 3.5 mA (at 5 VDC)

PLC Setup.)*1 8.0 ms max. (Can be set to between 0 and 32 in the

OFF Response Time

0.3 ms max.

No. of Circuits

32 points (16 points/common, 2 circuits)

Fuse

None

No. of Circuits

32 points (16 points/common, 2 circuits)

5 VDC±10%, 40 mA min. (1.2 mA × No. of ON points)

Number of Simultaneously ON Points

100% (16 points/common)

External Power Supply Insulation Resistance

20 MΩ between the external terminals and the GR terminal (at 100 VDC)

Dielectric Strength

1,000 VAC between the external terminals and the GR terminal for 1 minute at a leakage current of 10 mA max.

Signal name

CN2 (IN) Allocated CIO word

Allocated CIO word

Signal name

Wd m+2

IN0 to IN15

+V

Circuit Configuration

Internal circuits

5.6 kΩ

Output indicator

OUT0 to OUT15

Wd m

1.1 kΩ

COM2 COM2

COM0 COM0

Indicator switch Input indicator

Indicator switch

1.1 kΩ

+V OUT0 to OUT15 COM1 COM1

Wd m+3 Wd m+1

IN0 to IN15

App

5.6 kΩ

Internal circuits

CN1 (OUT)

2.2 kΩ

None

2.2 kΩ

110 g max.

Accessories

1000 pF

Weight

1000 pF

5 VDC 190 mA max.

PLC Setup.)*1

A-1 Specifications of Basic I/O Units

Internal Current Consumption

OFF Response Time

COM3 COM3

A-1-2 Basic I/O Units

CJ2 CPU Unit Hardware User’s Manual

A-55

Page 318

Appendices

CN1 (OUT) Allocated CIO word

Signal name

Connector pin

CN2 (IN)

Signal name

Allocated CIO word

Allocated CIO word

Signal name

Connector pin

Signal name

Allocated CIO word

40 39

OUT8

L

OUT1

38 37

OUT9

L

COM3

L

OUT2

36 35

OUT10

L

IN15

L

OUT3

34 33

OUT11

L

IN14

L

OUT4

32 31

OUT12

L

IN13

L

OUT5

30 29

OUT13

L

L

OUT6

28 27

OUT14

L

L

OUT7

26 25

OUT15

L

COM0

22 21

Wd m+3

Wd m

IN12 IIN11 IN10

COM0

IN9

+V

IN8

L

OUT0

20 19

OUT8

L

NC

L

OUT1

18 17

OUT9

L

COM2

L

OUT2

16 15

OUT10

L

IN15

L

OUT3

14 13

OUT11

L

IN14

L

OUT4

12 11

OUT12

L

L

OUT5

10 9

OUT13

L

L

OUT6

8

7

OUT14

L

L

OUT7

6

5

OUT15

L

COM1

4

3

COM1

+V

2

1

+V

IN13 IN12 Wd m+2

Terminal Connections

Wd m+1

+V

24 23

NC

5 VDC

IN11 IN10 5 VDC

5 VDC

IN9 IN8

1

2

3

4

5

6

7

8

9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40

NC COM3 IN7 IN6 IN5 IN4 IN3 IN2

Wd m+3

OUT0

L

IN1 IN0 NC COM2 IN7 IN6 IN5 IN4 IN3 IN2

Wd m+2

L

Wd m+1

Wd m

5 VDC

IN1 IN0

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.

• When wiring, pay careful attention to the polarity of the external power supply. The load may operate incorrectly if the polarity is reversed.

• Be sure to wire both terminals 23 and 24 (COM0) of CN1.

• Be sure to wire both pins 23 and 24 (COM2) of CN2, and set the same polarity for both pins.

• Be sure to wire both terminals 3 and 4 (COM1) of CN1.

• Be sure to wire both pins 3 and 4 (COM3) of CN2, and set the same polarity for both pins.

• Be sure to wire both terminals 21 and 22 (+V) of CN1. • Be sure to wire both terminals 1 and 2 (+V) of CN1.

*1 The ON response time will be 120 µs maximum and OFF response time will be 400 µs maximum even if the response times are set to 0 ms due to internal element delays.

A-56

CJ2 CPU Unit Hardware User’s Manual

Page 319

Appendices

A-1-3

Precautions on Contact Output Units

Service Life Expectancy of CJ1W-OC201/211 Relays The service life expectancy of the relays (NY-24W-K-IE) in the CJ1W-OC201/211 Contact Output Units is shown in the following diagrams. Use the diagrams to calculate the relay service life based on the operating conditions, and replace the relay before the end of its service life.

Contact Current vs. Service Life Characteristic Service Life with AC Load

100

240 VAC, resistive load

50 30 20

240 VAC cos φ = 0.4

10 120 VAC cos f = 0.4

5

24 VDC τ = 7 ms

300 200

120 VAC, resistive load

Service life (×104)

Service life (×104)

300 200

Service Life with DC Load

100 50 24 VDC, resistive load

30 20 10 5 3 2

3 2

0.2

0.3

0.5 0.7

1

2

3

5

Contact current (A)

0.1

0.2

0.3

0.5 0.7

1

2

3

5

Contact current (A) Switching frequency: 1,800 operations/hour max.

Precautions for Correct Use The diagrams show the life expectancy of the relay itself. Do not use a contact current, therefore, that exceeds the maximum switching capacity specified in the specifications for each Contact Output Unit. If a switching capacity exceeding the specifications is used, the reliability and life expectancy of other parts will be reduced and the Unit may malfunction.

Be sure to connect a diode in parallel with every DC inductive load that is connected to the Contact Output Unit.

Contact Protection Circuit Arc killers are used with the Contact Output Unit in order to prolong the life of each Relay mounted to the Contact Output Unit, prevent noise, and reduce the generation of carbide and nitrate deposits. However, if arc killers are used incorrectly, they can reduce relay life. Using an arc killer can also cause a delay in the resetting time (shut-off time). Arc killer circuit examples are listed in the following table.

CJ2 CPU Unit Hardware User’s Manual

A-57

A-1-3 Precautions on Contact Output Units

The life of the Relay varies with the load inductance. If any inductive load is connected to the Contact Output Unit, use an arc killer with the Contact Output Unit using an inductive load. (See next page.)

App

Inductive Load

A-1 Specifications of Basic I/O Units

0.05

0.1

Page 320

Appendices

Current

Circuit

Power supply

DC

Yes

Yes

Inductive load

CR method

AC

C R

Characteristic

Required element

If the load is a relay or solenoid, there is a time lag between the moment the circuit is opened and the moment the load is reset.

The capacitance of the capacitor must be 1 to 0.5 µF per contact current of 1 A and resistance of the resistor must be 0.5 to 1 Ω per contact voltage of 1 V. These values, however, vary with the load and the characteristics of the relay. Decide these values from experiments, and take into consideration that the capacitance suppresses spark discharge when the contacts are separated and the resistance limits the current that flows into the load when the circuit is closed again.

If the supply voltage is 24 or 48 V, insert the arc killer in parallel with the load. If the supply voltage is 100 to 200 V, insert the arc killer between the contacts.

The dielectric strength of the capacitor must be 200 to 300 V. If the circuit is an AC circuit, use a capacitor with no polarity. No

Yes

Inductive load

Diode method Power supply

Yes

Power supply

Inductive load

Varistor method

Yes

The diode connected in parallel with the load changes energy accumulated by the coil into a current, which then flows into the coil so that the current will be converted into Joule heat by the resistance of the inductive load. This time lag, between the moment the circuit is opened and the moment the load is reset, caused by this method is longer than that caused by the CR method.

The reversed dielectric strength value of the diode must be at least 10 times as large as the circuit voltage value. The forward current of the diode must be the same as or larger than the load current.

The varistor method prevents the imposition of high voltage between the contacts by using the constant voltage characteristic of the varistor. There is time lag between the moment the circuit is opened and the moment the load is reset.

---

The reversed dielectric strength value of the diode may be two to three times larger than the supply voltage if the arc killer is applied to electronic circuits with low circuit voltages.

If the supply voltage is 24 or 48 V, insert the varistor in parallel with the load. If the supply voltage is 100 to 200 V, insert the varistor between the contacts.

Do not connect a capacitor as an arc killer in parallel with an inductive load as shown in the following diagram. This arc killer is very effective for preventing spark discharge at the moment when the circuit is opened. However, when the contacts are closed, the contacts may be welded due to the current charged in the capacitor. DC inductive loads can be more difficult to switch than resistive loads. If appropriate arc killers are used, however, DC inductive loads will be as easy to switch as resistive loads.

A-58

Power supply

C

Inductive load

Precautions for Correct Use

CJ2 CPU Unit Hardware User’s Manual

Page 321

Appendices

A-1-4

Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals

Patterns for Combining Connector-Terminal Block Conversion Units and I/O Relay Terminals The following patterns can be used to connect Basic I/O Units with Connectors to OMRON ConnectorTerminal Block Conversion Units and I/O Relay Terminals using OMRON Connecting Cables.

z Connection Patterns for Connector-Terminal Block Conversion Units Pattern A

Configuration

Number of connectors 1

Connecting Cable

Branching None

Connector-Terminal Block Conversion Unit

40 or 60 terminals

B

2 branches

Connecting Cable with two branches Connector-Terminal Block Conversion Unit

C

A-1 Specifications of Basic I/O Units

20 terminals

20 terminals

2

Connecting Cable

None

Connector-Terminal Block Conversion Unit

20 terminals

D

20 terminals

Connecting Cable Connector-Terminal Block Conversion Unit

40 or 60 terminals

F

Connecting Cable with two branches

App

40 or 60 terminals

2 branches

Connector-Terminal Block Conversion Unit

CJ2 CPU Unit Hardware User’s Manual

A-1-4 Connecting Connector-Terminal Block Conversion Units and I/O Relay Terminals

20 terminals 20 terminals

20 terminals 20 terminals

A-59

Page 322

Appendices z Connection Patterns for I/O Relay Terminals Pattern

Configuration

A Connecting Cable

I/O Relay Terminal

B I/O Relay Terminal

I/O Relay Terminal

Connecting Cable

E

I/O Relay Terminal

I/O Relay Terminal

Connecting Cable

F Connecting Cable

I/O Relay Terminal

A-60

CJ2 CPU Unit Hardware User’s Manual