The text of a manual · part 42 of 48

SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual: Appendices, pages 363 to 372

Pages 363 to 372 of 422, from SYSMAC CJ Series CJ2H-CPU6_-EIP, CJ2H-CPU6_, CJ2M-CPU_ CJ2 CPU Unit Hardware User's Manual

The original document is the PDF (14 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Omron C200H-OD21A, Omron CQM1-ID211, Omron CQM1-ID213, Omron CQM1-OD211 and Omron CQM1-OD213

Page 363

Appendices

A-2-5

I/O Control Unit and I/O Interface Unit CJ1W-IC101 I/O Control Unit

Unit: mm

CJ1W-II101 I/O Interface Unit (140)

(140)

II101

IC101

OUT

69.3

20

2.7

90 2.7

IN

90

OUT

A-2-6

68 65

2.7

2.7

68 65

69.3

31

I/O Memory Card Unit: mm

42.8

A-2-7

Pulse I/O Modules (CJ2M CPU Unit Only) Unit: mm

20

App

66.2

2.7

A-2-5 I/O Control Unit and I/O Interface Unit

90

2.7

65 83.8

CJ2 CPU Unit Hardware User’s Manual

A-2 Dimensions

3.3

36.4

A-101

Page 364

Appendices

A-2-8

Serial Option Boards (CJ2M-CPU3@ Only)

CP1W-CIF01 RS-232C Option Board Unit: mm

0.15

16.5 35.9

5.1

37.3 35.9

13.5

16.5 19.7

CP1W-CIF11 RS-422A/485 Option Board Unit: mm 0.15

16.5 35.9

8.9

37.3 35.9

13.5

15.7 16.5

CP1W-CIF12 RS-422A/485 Option Board 16.5

Unit: mm 0.15 30.3 28.2

37.3 36.4

7.9

36.4

A-102

CJ2 CPU Unit Hardware User’s Manual

Page 365

Appendices

A-3

Fatal and Non-fatal Error Details This appendix describes the fatal and non-fatal errors that can occur in the CPU Unit.

A-3-1

Fatal Errors

Operation will stop if a fatal error occurs. Information on the fatal error is displayed on the Error Tab Page opened from the CX-Programmer's PLC Error Window. Check the details on the error based on the message that is displayed, and the error flags and error information in the Auxiliary Area, and take suitable countermeasures. The following list shows the fatal errors. Fatal error

Cycle Time Exceeded Error (0x809F) I/O Bus Error (0x80C0 to 0x80C7, 0x80CE , or 80CF) I/O Setting Error (0x80E0) Too Many I/O Points Error (0x80E1) Unit Number Duplication Error (0x80E9) Rack Number Duplication Error (0x80EA) Instruction error

Memory Error (0x80F1)

Indirect BCD error

Version Error (0x80F2)

Illegal access error

Memory Card Transfer Error (0x80F4)

No END error

FALS(007) Error (0xC101 to 0xC2FF)

Task error

A-3 Fatal and Non-fatal Error Details

Program Error (0x80F0)

Differentiation overflow error Illegal instruction error UM overflow error

App A-3-1 Fatal Errors

CJ2 CPU Unit Hardware User’s Manual

A-103

Page 366

Appendices

Table of Fatal Errors • The table of fatal errors is arranged in ascending order of error codes. • When two or more errors occur at the same time, the error code of the more serious error will be recorded in A400. • If the IOM Hold Bit hasn't been turned ON to protect I/O memory, all nonretained areas of I/O memory will be cleared when a fatal error other than FALS(007) occurs. • If the IOM Hold Bit is ON, the contents of I/O memory will be retained but all outputs will be turned OFF. Error Cycle Time Exceeded Error

Error code (in A400) 0x809F

Error flag (Auxiliary Area) A401.08: Cycle Time Exceeded Flag

Flag and word data ---

Probable cause The cycle time has exceeded the maximum cycle time (watch cycle time) set in the PLC Setup.

Possible remedy Change the program to reduce the cycle time or change the maximum cycle time setting. Check the Maximum Interrupt Task Processing Time in A440 and see if the Cycle Time Watch Time can be changed.*2 The cycle time can be reduced by dividing unused parts of the program into tasks, jumping unused instructions in tasks, and disabling cyclic refreshing of Special I/O Units that don't require frequent refreshing.

I/O Bus Error

0x80C0 to 0x80C7, 0x80CE, or 0x80CF

A401.14: I/O Bus Error Flag

A404: I/O Bus Error Slot and Rack Numbers

Error has occurred in the bus line between the CPU and I/O Units or the End Cover is not connected to the CPU Rack or an Expansion Rack.*1 A404.08 to A404.15 contain the error rack number (00 to 03) in binary. 0F hex indicates that the rack cannot be determined.0E hex indicates the End Cover is not connected to the CPU Rack or an Expansion Rack.

Try turning the power OFF and ON again. If the error isn't corrected, turn the power OFF and check cable connections between the I/O Units and Racks and the End Covers. Check for damage to the cable or Units. Turn the Rack's power supply OFF and then ON again.

*1 A404.00 to A404.07 contain the error slot number (00 to 09) in binary. “0F hex” indicates that the slot cannot be determined. “0B hex” indicates a bus error occurred for the built-in EtherNet/IP port. “0E hex” indicates the End Cover is not connected to the CPU Rack or an Expansion Rack. *2 The maximum processing time for an interrupt task will not be stored in A440 if High-speed interrupt function is enabled in the PLC Setup.

A-104

CJ2 CPU Unit Hardware User’s Manual

Page 367 read from a scan by OCR; it may hold reading errors

Appendices

Error Error flag Flag and Error code (Auxiliary word data Probable cause Possible remedy (inA400) Area) /O Setting Ox80EO A401.10: I/O A405.08 The Units that are connected do not ¢ If the number of Units is not correct, turn OFF the Error Setting Error agree with the registered I/O tables power supply and correctly connect the proper Flag or the number of Units that are con- Units. nected does not agree with the num- | « with the CJ2 CPU Unit, if the I/O verification oper-ber in the registered I/O table. * ation’! is performed when the number of Units is incorrect, mismatch errors will be detected for all Units registered in the I/O tables. If this occurs even when the number of Units is correct, it is possible that a Unit has failed and is not being correctly recognized. Generate new I/O tables, and then read the I/O tables and check for Units that are not being recognized. ¢ If the number of Units is correct, confirm the Unit in discrepancy, turn OFF the power supply, and then correct the Unit connections. ¢ If there is a mistake in the I/O tables, generate new |/O tables or edit the tables to correct the mistake. An Interrupt Input Unit has been ¢ When an Interrupt Input Unit is used, A405.08 will mounted in the wrong slot, i.e., not in turn ON if the Interrupt Input Unit is in the wrong one of the following slots on the CPU position or is registered in the wrong position. Rack, or has been registered inthe | « If the Unit is connected in a slot on the CPU Rack registered I/O tables in any slots that is not in the specified range, move the Unit to other than the following slots. one of the specified CPU Rack slots. ¢ CJ2H-CPU6LI-EIP: CPU Rack ¢ If the Unit is mounted in a slot on the CPU Rack slots 0 to 3 that is not in the specified range, correct the I/O ¢ CJ2H-CPU6L] or CU2M-CPU3L): tables so that the Interrupt Input Unit is correctly Slots 0 to 4 in CPU Rack registered to one of the specified slots. Registered I/O tables for the CJ2H- Delete or correct the I/O tables using the CX-Pro- CPU6LI-EIP or CJ2M-CPU3L] were grammer. downloaded to the CJ2M-CPU6At or CJ2M-CPU1L1. Or, registered I/O tables for the CJZH-CPU6L] or CJ2M-CPU1L] were downloaded to the CJ2M-CPU6LI-EIP or CJ2M- CPU3L. Too Many I/O | 0x80E1 A401.11: Too A407.13 to One of the following values exceeds_ | Correct the problem and then turn the power supply Points Error Many I/O A407.15: Too | the maximum or is allocated to more | OFF and back ON. Points Flag Many I/O than one Unit. Points, Details | 4 The total number of I/O points 2 set in the I/O tables exceeds the maximum allowed for the CPU Unit (bits: 000) 2. There are more than 32 interrupt inputs (bits: 001). 3. Three or more Pulse I/O Mod- ules were connected to a CJU2M CPU Unit (bits: 100). 4. The number of Expansion Racks exceeds the maximum (bits: 101). 5. More than 10 I/O Units are con- nected to one Rack (bits: 111)."4 Unit/Rack Ox80E9 A401.13: Dupli- | A410: CPU The same number has been allo- Check the unit numbers, eliminate the duplications, Number cation Error Bus Unit cated to more than one CPU Bus and turn the Rack's power supply OFF and then ON Duplication Flag Duplicated Unit.”> again. Error Number Flags

A411 to A416: Special I/O Unit Dupli- cated Num- ber Flags

The same number has been allo- cated to more than one Special I/O

Unit."6

Check the unit numbers, eliminate the duplications, and turn the Rack's power supply OFF and then ON again.

CJ2 CPU Unit Hardware User’s Manual

A-105 s]!2]9q 40119 [e}eJ-UON pue jeye4 ¢-V

SIOUF [eye L-E-V

Page 368

Appendices

Error Expansion Rack Duplicated Rack Number

Program Error

Error code (inA400)

Error flag (Auxiliary Area)

0x80EA

A401.13: Duplication Error Flag

0x80F0

A401.09: Program Error Flag

Flag and word data A409: Expansion Rack Duplicated Rack Number

A294 to A299: Program Error Information

Probable cause The same I/O word has been allocated to more than one Basic I/O Unit.

Check allocations to Units on the rack number whose bit is ON in A409.00 to A409.03. Correct the allocations so that no words are allocated more than once, including to Units on other Racks, and turn the Rack's power supply OFF and then ON again.

An Expansion Rack's starting word address exceeds CIO 0901.The corresponding bit in A409.00 to A409.03 (Racks 0 to 3) will be turned ON.

Check the first word setting for the Rack indicated in A409.00 to A409.03 and change the setting to a valid word address below CIO 0900 with a Programming Device (such as a CX-Programmer).

The program is incorrect. See the following rows of this table for details. The address at which the program stopped will be output to A298 and A299.

Check the program using A298/A299 and the error flags to find the mistake, and correct the program. Correct the program and then clear the error.

A295.11: No END error

Be sure that there is an END(001) instruction at the end of the task specified in A294 (program stop task number).

A295.15: UM overflow error The last address in UM (user program memory) has been exceeded.

Transfer the program again.

A295.13: Differentiation overflow error Too many differentiated instructions have been inserted or deleted during online editing.

Return to PROGRAM mode and transfer the program again.

A295.12: Task error A task error has occurred. The following conditions will generate a task error.

Check the startup cyclic task attributes. Check the execution status of each task as controlled by TKON(820) and TKOF(821).Make sure that all of the task numbers specified in TKON(820), TKOF(821), and MSKS(690) instructions have corresponding tasks. Use MSKS(690) to mask any I/O or scheduled interrupt tasks that are not being used and that do not have programs set for them.

1.

There is no executable cyclic task.

2.

There is no task that corresponds to the interrupt that was input. (Only when the Stop CPU on Instruction Error parameter in the PLC Setup is set to Stop.)

A295.10: Illegal access error An illegal access error has occurred and the PLC Setup has been set to stop operation for an instruction error. The following are illegal access errors:

A-106

Possible remedy

1.

Reading/writing a parameter area.

2.

Writing memory that is not installed.

3.

Writing an EM bank that is EM file memory.

4.

Writing to a read-only area.

5.

Indirect DM/EM address that is not in BCD when BCD mode is specified.

Find the program address where the error occurred (A298/A299) and correct the instruction.

Indirect DM/EM BCD Error Flag (A295.09) turned ON: An indirect DM/EM BCD error has occurred, causing the AER Flag to turn ON. Also, the PLC Setup has been set to stop operation for an instruction error.

Find the program address where the error occurred using A298/A299 and correct the indirect addressing (the indirect address or the word holding the indirect address) or change to binary mode.

Instruction Error Flag (A295.08) turned ON: Incorrect data values were provided in an operand when an attempt was made to execute an instruction, causing the ER Flag to turn ON, and the PLC Setup has been set to stop operation for an instruction error.

Check the Program Error Position (A298/A299) to find the reason that the ER Flag turned ON and correct the operand data according to the descriptions of the instructions in the Instructions Reference Manual (Cat. No. W474).

A295.14: Illegal instruction error The program contains an instruction that cannot be executed.

Retransfer the program to the CPU Unit.

CJ2 CPU Unit Hardware User’s Manual

Page 369

Appendices

Error Memory Error

Version Error

Memory Card Transfer Error

0x80F1

0x80F2

0x80F4

0xC101 to 0xC2FF

Error flag (Auxiliary Area) A401.15: Memory Error Flag

A401.05: Version Error Flag

A401.03: Memory Card Error Flag

A401.06: FALS Error Flag

Flag and word data

Probable cause

A403: Memory Error Location

An error has occurred in memory. A bit in A403 will turn ON to show the location of the error as listed below.

See below.

A403.00 ON: A checksum error has occurred in the user program memory. The power was turned OFF while storing data to the flash memory (backup memory).

Transfer the program again.

A403.04 ON: A checksum error has occurred in the PLC Setup.

Clear the entire PLC Setup to 0000 and reenter the settings.

A403.05 ON: A checksum error has occurred in the registered I/O tables.

Initialize the registered I/O table and generate a new I/O table.

A403.07 ON: A checksum error has occurred in the routing tables.

Initialize the routing tables and reenter the tables.

A403.08 ON: A checksum error has occurred in the CPU Bus Unit Setup.

Initialize the CPU Bus Unit setup and reenter the settings.

The user program that was transferred includes functions that are not supported by the unit version of the CPU Unit.

• Check whether the unit version supports the user program.

When A401.03 is ON: The contents of the Memory Card cannot be correctly read to the CPU Unit when the power is ON.

Check whether the files required for executing the automatic transfer function are available.

An attempt was made to transfer a user program (OBJ file) that includes network symbols when the power supply was turned ON (CJ2HCPU6@ only).

Transfer a user program (OBJ file) that does not include network symbols.

FALS(007) has been executed in the program. The error code in A400 will indicate the FAL number. The leftmost digit of the code will be C and the rightmost 3 digits of the code will be from100 to 2FF hex and will correspond to FAL numbers 001 to 511.

Correct according to cause indicated by the FAL number (set by user).

A293

---

---

Possible remedy

• Upgrade the unit version of the CPU Unit.

*1 Execute the I/O verification operation by selecting Options − Compare with Project from the I/O Table Menu of the CXProgrammer.

*4 Bits A410.00 to A410.15 correspond to unit numbers 0 to F. *5 Bits A411.00 to A416.15 correspond to unit numbers 0 to 95.

CJ2 CPU Unit Hardware User’s Manual

A-107

A-3-1 Fatal Errors

*3 Regardless of the error that occurred, the three bits in parentheses will be stored in A407.13 to A407.15. The value will simultaneously be stored in A407.00 to A407.12.

App

*2 The CJ1W-ID201 (8-point DC Input Unit), CJ1W-OC201 (8-point Contact Output Unit), CJ1W-IA201 (8-point AC Input Unit), CJ1W-OA201 (8-point Triac Output Unit), and CJ1W-OD201/202/203/204 (8-point Triac Output Units) are allocated one word each, so set them as 16-point Input Units or 16-point Output Units in the I/O tables when manually setting the I/O tables from the CX-Programmer. An I/O setting error will occur if they are set as 8-point Input Units or 8-point Output Units.

A-3 Fatal and Non-fatal Error Details

FALS(007) Error

Error code (inA400)

Page 370

Appendices

A-3-2

Non-fatal Errors

Operation continues when a non-fatal error occurs. Connect the CX-Programmer to display the error message in the Error Log Dialog Box on the CX-Programmer. The cause of the error can be determined from the error message and related Auxiliary Area flags and words. The following list shows the non-fatal errors. Non-fatal errors

Duplicated Refreshing Error (CJ1: Interrupt task error) (0x008B) Basic I/O Error (0x009A) PLC Setup Error (0x009B) Backup Memory Error (0x00F1) Tag Memory Error (0x00F2) System Work Error (0x00F3) Battery Error (0x00F7) CPU Bus Unit Error (0x0200 to 0x020F) Special I/O Unit Error (0x0300 to 0x035F or 0x03FF) CPU Bus Unit Setting Error (0x0400 to 0x040F) Special I/O Unit Setting Error (0x0500 to 0x055F) FAL(006) Error (0x4104 to 0x42FF)

A-108

CJ2 CPU Unit Hardware User’s Manual

Page 371

Appendices

Table of Non-fatal Errors • The table of non-fatal errors is arranged in ascending order of error codes. • When two or more errors occur at the same time, the error code of the more serious error will be recorded in A400. • When the IOM Hold Bit is set to ON, I/O memory will be retained and outputs to the Output Unit will turn OFF. Error Duplicated Refreshing Error (CJ1: Interrupt task error)

Error code (in A400) 0x008B

Error flag (Auxiliary Area) A402.13: Duplicated Refresh Error Flag

Flag and word data A426: Unit number where duplicated refresh error occurred

Probable cause

Possible remedy

ON when the Detect Duplicated Refresh Errors setting in the PLC Setup is set to Detect and one of the following occurs for the same Special I/O Unit.

Check the program. Either disable detection of duplicated refresh errors in the PLC Setup or correct the problem in the program.

• IORF(097), FIORF(225), IORD(222) or IOWR(223) in a cyclic task are competing with FIORF(225), IORF(097), IORD(222) or IOWR(223) in an interrupt task. • IORF(097), FIORF(225), IORD(222) or IOWR(223) was executed in an interrupt task when I/O was being refreshed.*1

0x009A

A402.12: CJseries Basic I/O Unit Error Flag

A408: Basic I/O Unit Error, Slot Number

An error has occurred in a Basic I/O Unit.*2

Check the Basic I/O Unit to see whether a fuse needs to be replaced.

PLC Setup Error

0x009B

A402.10: PLC Setup Error Flag

---

There is a setting error in the PLC Setup.

Change the indicated setting to a valid setting.

Option Board Error

0x00D1

A315.13 Option Board Error Flag A402.00 Other Non-fatal Error Flag

---

The Option Board was removed while the system was operating.

Check the mating of the Option Board connector and reconnect the connector. If the Option Board still fails, replace it.

Option Board failure

0x00F1

A315.15: Backup Memory Error Flag

---

Writing to the built-in flash memory failed.

Operation may not be possible the next time power is restored after a power interruption. Replace the CPU Unit.

Tag Memory

0x00F2

A315.12: Tag Memory Error Flag

---

An error occurred in memory where network tags are stored.

Transfer the program again.

0x00F3

A315.04: System Work Error Flag

---

An error occurred in the memory for online editing.

Operation may not be possible the next time power is restored after a power interruption. Transfer the program again.

Error*3 System Work Error

A402.00: Other Non-fatal Error Flag Battery Error

0x00F7

A402.04: Battery Error Flag

---

This error occurs when the PLC Setup has been set to detect battery errors and the CPU Unit's backup battery is missing or its voltage has dropped.

Check battery and replace if necessary. Change the PLC Setup setting if battery-free operation is being used.

CPU Bus Unit Error

0x0200 to 0x020F

A402.07: CPU Bus Unit Error Flag

A417: CPU Bus Unit Error, Unit Number Flags

An error occurred in a data exchange between

Check the Unit indicated in A417. Refer to the Unit's operation manual to find and correct the cause of the error. Restart the Unit by toggling its Restart Bit or turn the power OFF and ON again. Replace the Unit if it won't restart.

Special I/O Unit Error

0x0300 to 0x035F or 0x03FF

A402.06: Special I/O Unit Error Flag

A418 to A423: Special I/O Unit Error, Unit Number Flags

An error occurred in a data exchange between

CJ2 CPU Unit Hardware User’s Manual the CPU Unit and a CPU Bus Unit.*4 the CPU Unit and a Special I/O Unit.*5

Check the Unit indicated in A418 to A423. Refer to the Unit's operation manual to find and correct the cause of the error. Restart the Unit by toggling its Restart Bit or turn the power OFF and ON again. Replace the Unit if it won't restart.

A-109

App

Backup Memory Error

A-3 Fatal and Non-fatal Error Details

Basic I/O Error

Page 372

Appendices

Error

Error code (in A400)

Error flag (Auxiliary Area)

Flag and word data

Probable cause

Possible remedy Change the registered I/O table.

CPU Bus Unit Setting Error

0x0400 to 0x040F

A402.03: CPU Bus Unit Setting Error Flag

A427: CPU Bus Unit Setting Error, Unit Number Flags

An installed CPU Bus Unit does not match the

Special I/O Unit Setting Error

0x0500 to 0x055F

A402.02: Special I/O Unit Setting Error Flag

A428 to A433: Special I/O Unit Setting Error, Unit Number Flags

An installed Special I/O Unit does not match the

CPU Bus Unit registered in the I/O tables.*6

Change the registered I/O table.

Special I/O Unit registered in the I/O tables.*7 • A Unit that is specified for synchronous unit operation does not support synchronous unit operation. *7 • A Unit that is specified for synchronous unit

Correct the settings for synchronous unit operation in the PLC Setup and transfer the PLC Setup again.

operation does not exist.*7 A Synchronous Unit that is specified for synchronous unit operation is not on the CPU Rack (the Synchronous Unit is on an Expansion Rack).*7 FAL(006) Error

0x4101 to 0x42FF

A402.15: FAL Error Flag

A360 to A391: Executed FAL Number Flags

FAL(006) has been executed in program.*8

Move the Synchronous Unit to the CPU Rack. If I/O tables have been registered, correct the settings in the registered I/O tables. Correct according to cause indicated by FAL number (set by user).

*1 If cyclic refreshing is not disabled in the PLC Setup for a Special I/O Unit and IORF(097), FIORF(225), IORD(222) or IOWR(223) is executed for the same Special I/O Unit in an interrupt task, a duplicate refreshing status will occur and an duplicated refreshing error will occur. *2 A408 contains the errant rack/slot number. *3 CJ2H-CPU6@-EIP or CJ2M-CPU3@ only. *4 The corresponding flag in A417 is turned ON to indicate the problem Unit. *5 The corresponding flag in A418 to A423 is turned ON to indicate the problem Unit. *6 The corresponding flag in A427 will be ON. *7 The corresponding flag in A428 to A433 will be ON. *8 Executed FAL Number Flags in consecutive bits in A360 to A391 correspond to FAL numbers 001 to 511. The error code in A400 will indicate the FAL number. The leftmost digit of the code will be 4 and the rightmost 3 digits of the code will be from 101 to 2FF hex and will correspond to FAL numbers 001 to 511.

A-110