Page 53
1 Overview
With the CJ2M CPU Units, up to two Pulse I/O Modules can be mounted. This enables input functions, such as normal inputs, interrupt inputs, high-speed counter inputs, and quick-response inputs, and output functions, such as normal outputs, pulse outputs, and variable duty factor pulse outputs. This provides support for many different types of applications. Pulse I/O Modules
1-1 Overview of CJ2 CPU Units
Use Pulse I/O and Interrupt Inputs (CJ2M CPU Units Only)
1 1-1-2 CJ2 CPU Unit Features
• Normal outputs: 12 (6 per Pulse I/O Module) • Normal inputs: 20 (10 per Pulse I/O Module) • Pulse outputs: 4 (2 per Pulse I/O Module) • Interrupt inputs: 8 (4 per Pulse I/O Module) • High-speed counter inputs: 4 (2 per Pulse I/O Module) • Variable duty factor pulse outputs: 4 (2 per Pulse I/O Module) • Quick-response inputs: 8 (4 per Pulse I/O Module)
CJ2 CPU Unit Hardware User’s Manual
1-11
Page 54
1 Overview
1-2
Basic Operating Procedure In general, use the following procedure. 1. Setting Devices and Hardware Mount the Power Supply Unit, the CPU Unit, the other Units, and the End Covers. Set the DIP switch and rotary switches as required.
Refer to Section 3 Nomenclature and Functions and Section 5 Installation in the CJ2 CPU Unit Hardware User’s Manual (Cat. No. W472).
2. Wiring Wire the power supply, I/O, and communications. Refer to the following manuals.
Refer to Section 5 Installation in the CJ2 CPU Unit Hardware User’s Manual (Cat. No. W472). Refer to Section 11 Programming Devices and Communications in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473). Refer to Section 3 I/O Specifications and Wiring for Pulse I/O Module in the CJ2M CPU Unit Pulse I/O Module User's Manual (Cat. No. W486).
3. Connecting Online to the PLC Connect the personal computer online to the PLC.
Refer to Section 4 Support Software in the CJ2 CPU Unit Hardware User’s Manual (Cat. No. W472)
4. I/O Allocations Using the CX-Programmer, allocate I/O memory in the CPU Unit to the mounted Units.
Refer to Section 8 I/O Allocations and Unit Settings in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473) Refer to Section 2 I/O Application Procedures and Function Allocations in the CJ2M CPU Unit Pulse I/O Module User's Manual (Cat. No. W486).
5. Software Setup Make the PLC software settings.
• CPU Unit initialization: Refer to Section 4 CPU Unit Initialization in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473). • DM Area Settings for Special I/O Units and CPU Bus Units: Refer to Section 8 I/O Allocations and Unit Settings in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473). • PLC Setup: Refer to Section 9 PLC Setup in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).
6. Creating the Program Create the program using the CX-Programmer. Refer to Section 5 Understanding Programming in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).
7. Checking Operation Check the I/O wiring and the AR Area settings, and perform trial operation. The CX-Programmer can be used for monitoring and debugging.
Refer to 10-7 Debugging in the CJ2 CPU Unit Software User’s Manual (Cat. No. W473).
8. Basic Program Operation Set the operating mode to RUN mode to start operation.
1-12
CJ2 CPU Unit Hardware User’s Manual
Page 55
1 Overview
Specifications
1-3-1
General Specifications
1-3 Specifications
1-3
CJ2H-
CJ2M-
Item CPU64(-EIP)
CPU65(-EIP)
Mounted in a panel
Grounding
Less than 100 Ω
CPU Unit Dimensions
Weight
Current Consumption
Use Environment
CPU67(-EIP)
CJ2H-CPU6@-EIP:
90 mm × 65 mm × 80 mm (H × D × W)
CJ2H-CPU6@:
90 mm × 65 mm × 49 mm (H × D × W)
CJ2H-CPU6@-EIP:
280 g or less
CJ2H-CPU6@:
190 g or less
CJ2H-CPU6@-EIP:
5 VDC, 0.82 A
CJ2H-CPU6@:
5 VDC, 0.42 A
Ambient Operating Temperature
0 to 55°C
Ambient Operating Humidity
10% to 90% (with no condensation)
Atmosphere
Must be free from corrosive gases.
Ambient Storage Temperature
−20 to 70°C (excluding battery)
Altitude
2,000 m or less
Pollution Degree
2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise Immunity
2 kV on power supply line (Conforms to IEC 61000-4-4.)
Overvoltage Category
Category II: Conforms to JIS B3502 and IEC 61131-2.
EMC Immunity Level
Zone B
Vibration Resistance
CPU68(-EIP)
CPU1@
CPU3@
90 mm × 75 mm × 31 mm (H × D × W)
90 mm × 75 mm × 62 mm (H × D × W)
130 g or less
190 g or less*
5 VDC, 0.5 A
5 VDC, 0.7 A
Conforms to IEC60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock Resistance
Conforms to IEC60068-2-27. 147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units)
Battery
Life
5 years at 25°C
Model
CJ1W-BAT01
Applicable Standards
Conforms to cULus, NK, LR, and EC Directives.
* Without a Serial Option Board
CJ2 CPU Unit Hardware User’s Manual
1-13
1 1-3-1 General Specifications
Enclosure
CPU66(-EIP)
Page 56
1 Overview
1-3-2
Performance Specifications CJ2HItems
CJ2M-
CPU64 (-EIP)
CPU65 (-EIP)
CPU66 (-EIP)
CPU67 (-EIP)
CPU68 (-EIP)
User Memory
50K steps
100K steps
150K steps
250K steps
400K steps
I/O Bits
2,560 bits
Processing Speed
CJ2H-CPU@@-EIP:200 µs
CPU 11/31 5K steps
CPU 12/32 10K steps
20K steps
CPU 14/34 30K steps
CPU 15/35 60K steps
CJ2M-CPU3@: 270 µs
Overhead Processing Time*1
Normal Mode:
Execution Time
Basic Instructions: 0.016 µs min.; Special Instructions: 0.048 µs min.
Basic Instructions: 0.04 µs min.; Special Instructions: 0.06 µs min.
Interrupts
I/O Interrupts and External Interrupts
Interrupt task startup time: 26 µs or 17 µs*2 (30 µs for unit version 1.0) Return times to cyclic tasks: 11 µs or 8 µs*2 (15 µs for unit version 1.0)
Interrupt task startup time: 31 µs Return times to cyclic tasks: 10 µs
Scheduled Interrupts
Minimum time interval: 0.2 ms or 0.1 ms*2 (set in 0.1-ms increments)
Minimum time interval: 0.4 ms (set in 0.1-ms increments)
Interrupt task startup time: 22 µs or 13 µs*2 (27 µs for unit version 1.0) Return time to cyclic task: 11 µs or 8 µs*2 (15 µs for unit version 1.0)
Interrupt task startup time: 30 µs Return time to cyclic task: 11 µs
Maximum Number of Connectable Units
CJ2H-CPU@@:
Normal Mode:
CPU 13/33
100 µs
CJ2M-CPU1@: 160 µs
Total per CPU Rack or Expansion Rack: 10 Units max.; Total per PLC: 40 Units max.
Basic I/O Units
No limit However, a maximum of two CJ1W-INT01 Interrupt Input Units can be mounted.
Special I/O Units
Units for up to 96 unit numbers can be mounted. (Unit numbers run from 0 to 95. Units are allocated between 1 and 8 unit numbers.)
CPU Bus Units
CJ2H-CPU6@-EIP: 15 Units max. CJ2H-CPU6@: 16 Units max.
CJ2M-CPU3@: 15 Units max. CJ2M-CPU1@: 16 Units max.
Pulse I/O Modules
---
2 max.*3
Slots for which interrupts can be used
CJ2H-CPU6@-EIP: Slots 0 to 3 on CPU Rack CJ2H-CPU6@: Slots 0 to 4 on CPU Rack
Slots 0 to 4 on CPU Rack
Maximum Number of Expansion Racks
3 max.
CIO Area
2,560 bits (160 words): Words CIO 0000 to CIO 0159
I/O Area Link Area
3,200 bits (200 words): Words CIO 1000 to CIO 1199
Synchronous Data Refresh Area
1,536 bits (96 words): Words CIO 1200 to CIO 1295
---
CPU Bus Unit Area
6,400 bits (400 words): Words CIO 1500 to CIO 1899
Special I/O Unit Area
15,360 bits (960 words): Words CIO 2000 to CIO 2959
Pulse I/O Area
---
20 inputs, 12 outputs (CIO 2960 to CIO 2963)
Serial PLC Link Words
---
1,440 bits (90 words): Words CIO 3100 to CIO 3189
DeviceNet Area
9,600 bits (600 words): Words CIO 3200 to CIO 3799
Internal I/O Area
3,200 bits (200 words): Words CIO 1300 to CIO 1499 (Cannot be used for external I/O.) 37,504 bits (2,344 words): Words CIO 3800 to CIO 6143 (Cannot be used for external I/O.)
Work Area Holding Area
8,192 bits (512 words): Words W000 to W511 (Cannot be used for external I/O.) 8,192 bits (512 words): Words H000 to H511 Bits in this area maintain their ON/OFF status when PLC is turned OFF or operating mode is changed. Words H512 to H1535: These words can be used only for function blocks. They can be used only for function block instances (i.e., they are allocated only for internal variables in function blocks).
*1 The following times are added if EtherNet/IP data tag links are used for the CJ2H-CPU6@-EIP. Normal operation: 100 µs + Number of transfer words x 0.33 µs High-speed interrupt function enabled: 100 µs + Number of transfer words × 0.87 µs The following time must be added when using EtherNet/IP tag data links for the CJ2M-CPU3@. 100 µs + (Number of words transferred × 1.8 µs) The following time must be added when using Pulse I/O Modules with a CJ2M CPU Unit: 10 µs × Number of Pulse I/O Modules *2 This applies when high-speed interrupts are used. *3 Supported only by CJ2M CPU Units with unit version 2.0 or later. A Pulse I/O Module must be mounted.
1-14
CJ2 CPU Unit Hardware User’s Manual
Page 57
1 Overview
CPU64 (-EIP)
Auxiliary Area
CPU65 (-EIP)
CJ2M-
CPU66 (-EIP)
CPU67 (-EIP)
CPU68 (-EIP)
CPU 11/31
CPU 12/32
CPU 13/33
CPU 14/34
CPU 15/35
Read-only: 31,744 bits (1,984 words) • 7,168 bits (448 words): Words A0 to A447 • 24,576 bits (1,536 words): Words A10000 to A11535*4 Read/write: 16,384 bits (1,024 words) in words A448 to A1471*4 16 bits: TR0 to TR15
Timer Area
4,096 timer numbers (T0000 to T4095 (separate from counters))
Counter Area
4,096 counter numbers (C0000 to C4095 (separate from timers))
DM Area
32k words*5
1
• DM Area words for Special I/O Units: D20000 to D29599 (100 words × 96 Units) • DM Area words for CPU Bus Units: D30000 to D31599 (100 words × 16 Units) 32k words/bank × 25 banks max.: E00_00000 to E18_32767 max.*5, *6
32k words/bank × 4 banks max.: E00_00000 to E3_32767 max.*5
32K words × 4 banks
32K words × 4 banks
32K words × 10 banks
32K words × 15 banks
32K words × 25 banks
32K words × 1 bank
32K words × 4 banks
Using EM Area forcesetting/resetting
Banks 0 to 3 hex
Banks 0 to 3 hex
Banks 0 to 9 hex
Banks 0 to E hex
Banks 0 to 18 hex
Bank 0 hex
Banks 0 to 3 hex
Using automatic address allocation specifications
Bank 3 hex
Bank 3 hex
Banks 6 to 9 hex
Banks 7 to E hex
Banks 11 to 18 hex
---
EM Area
Banks for which bits can be forceset/reset*7
Index Registers
IR0 to IR15 These are special registers for storing PLC memory addresses for indirect addressing. (Index Registers can be set so that they are unique in each task or so that they are shared by all tasks.)
Cyclic Task Flag Area
128 flags
Memory Card
128 MB, 256 MB, or 512 MB
Operating Modes
PROGRAM Mode: Programs are not executed. Preparations can be executed prior to program execution in this mode. MONITOR Mode:
Programs are executed, and some operations, such as online editing, and changes to present values in I/O memory, are enabled in this mode.
RUN Mode:
Programs are executed. This is the normal operating mode.
Execution Mode
Normal Mode
Programming Languages
Ladder Logic (LD) Sequential Function Charts (SFC) Structured Text (ST) Instruction Lists (IL)
Function Blocks
Maximum number of definitions
2,048
256
2,048
Maximum number of instances
2,048
256
2,048
---
20K steps
FB Program Area
*4 A960 to A1471 and A10000 to A11535 cannot be accessed by CPU Bus Units, Special I/O Units, PTs, and Support Software that do not specifically support the CJ2 CPU Units. *5 Bits in the EM Area can be addressed either by bit or by word. These bits cannot be addressed by CPU Bus Units, Special I/O Units, PTs, and Support Software that do not specifically support the CJ2 CPU Units. *6 EM banks D to 18 cannot be accessed by CPU Bus Units, Special I/O Units, PTs, and Support Software that do not specifically support the CJ2 CPU Units. *7 With CJ2H CPU Units with unit version 1.2 or later, force-setting/resetting bits in the EM Area is possible either for banks that have been specified for automatic address allocation or for banks specified for the EM Area force-set/reset function. With CJ2M CPU Units, force-setting/resetting bits in the EM Area is possible only for banks specified for the EM Area force-set/reset function.
CJ2 CPU Unit Hardware User’s Manual
1-15
1-3-2 Performance Specifications
Temporary Area
1-3 Specifications
CJ2HItems
Page 58
1 Overview
CJ2HItems
Tasks
CPU64 (-EIP)
CPU65 (-EIP)
CPU66 (-EIP)
CJ2MCPU67 (-EIP)
CPU68 (-EIP)
CPU 11/31
CPU 12/32
CPU 13/33
CPU 14/34
CPU 15/35
Type of Tasks
Cyclic tasks Interrupt tasks (Power OFF interrupt tasks, scheduled interrupt tasks, I/O interrupt tasks, external interrupt tasks, and input interrupt tasks*3)
Number of Tasks
Cyclic tasks: 128 Interrupt tasks: 256 (Interrupt tasks can be defined as cyclic tasks to create extra cyclic tasks. Therefore, the total number of cyclic tasks is actually 384 max.)
Symbols (Variables)
Type of Symbols
Local symbols: Can be used only within a single task in the PLC. Global symbols: Can be used in all tasks in the PLC. Network symbols (tags)*8: I/O memory in the CPU Unit can be externally accessed using symbols, depending on parameter settings.
Data Type of Symbols
BOOL (bit) UINT (one-word unsigned binary) UDINT (two-word unsigned binary) ULINT (four-word unsigned binary) INT (one-word signed binary) DINT (two-word signed binary) LINT (four-word signed binary) UINT BCD (one-word unsigned BCD)*9 UDINT BCD (two-word unsigned BCD)*9 ULINT BCD (four-word unsigned BCD)*9 REAL (two-word floating-point) LREAL (four-word floating-point) CHANNEL (word) NUMBER (constant or number) WORD (one-word hexadecimal) DWORD (two-word hexadecimal) LWORD (four-word hexadecimal) STRING (1 to 255 ASCII characters) TIMER (timer)*10 COUNTER (counter)*10 User-defined data types (data structures)*11
Maximum Size of Symbol
32k words
Array Symbols (Array Variables)
One-dimensional arrays
Number of Array Elements
32,000 elements max.
Number of Registrable Network Symbols (Tags)*8
20,000 max.
Length of Network Symbol (Tag) Name*8
255 bytes max.
Encoding of Network Symbols (Tags)*8
UTF-8
2,000 max.
*8 Supported only by the CJ2H-CPU6@-EIP and CJ2M-CPU3@. *9 This data type cannot be used in Function blocks. *10 This data type can be used only in Function blocks. *11 Supported only when CX-Programmer version 9.0 or higher is used.
1-16
CJ2 CPU Unit Hardware User’s Manual
Page 59
1 Overview
Data Tracing
Memory Capacity
CPU64 (-EIP)
CPU65 (-EIP)
8,000 words
CJ2M-
CPU66 (-EIP)
CPU67 (-EIP)
CPU68 (-EIP)
16,000 words
32,000 words
(Up to 32k words x 25 banks when EM is specified in CX-Programmer) Number of Samplings
CPU 11/31
CPU 12/32
CPU 13/33
CPU 14/34
CPU 15/35
8,000 words (Up to 32k words x 4 banks when EM is specified in CX-Programmer)
Bits = 31, one-word data =16, two-word data = 8, four-word data = 4 1 to 2,550 ms (Unit: 1 ms)
Trigger Conditions
ON/OFF of specified bit Data comparison of specified word Data size: 1 word, 2 words, 4 words Comparison Method: Equals (=), Greater Than (>), Greater Than or Equals (≥), Less Than (<), Less Than or Equals (≤), Not Equal (≠)
Delay Value
−32,768 to +32,767 ms Memory Card (128, 256, or 512 Mbytes) (Use the Memory Cards provided by OMRON.) EM file memory (Part of the EM Area can be converted for use as file memory.)
Source/Comment Memory
Program source, comments, program index, and symbol table
CJ2 CPU Unit Hardware User’s Manual
Capacity: 3.5 Mbytes
Capacity: 1 Mbytes
1-17
1 1-3-2 Performance Specifications
Sampling Cycle
File Memory
1-3 Specifications
CJ2HItems
Page 60
1 Overview
CJ2HItem
Communications
CPU64 (-EIP)
CPU65 (-EIP)
CPU66 (-EIP)
CJ2MCPU67 (-EIP)
CPU68 (-EIP)
CPU 11/31
CPU 12/32
CPU 13/33
Logical Ports for Communications
Logical Ports Extended Logical Ports
64 ports (Used for SEND2, RECV2, CMND2, and PMCR2 instructions.)
CIP Communications Specification
Class 3 (Number of Connections)
Number of connections: 64
UCMM (Non-connection Type)
Maximum number of clients that can communicate at the same time: 32 Maximum number of servers that can communicate at the same time: 40
Peripheral (USB) Port Baud Rate Transmission Distance Serial Port
CPU 14/34
CPU 15/35
8 ports (Used for SEND, RECV, CMND, PMCR, TXDU, and RXDU instructions.)
USB 2.0-compliant B-type connector 12 Mbps max. 5 m max. Interface: Conforms to EIA RS-232C.
• CJ2M-CPU1@ interface: Conforms to EIA RS-232C. • CJ2M-CPU3@: No serial ports with default system One of the following Serial Option Boards can be mounted. • CP1W-CIF01 RS-232C Option Board • CP1W-CIF11 RS-422A/485 Option Board (not isolated, max. transmission distance: 50 m) • CP1W-CIF12 RS-422A/485 Option Board (isolated, max. transmission distance: 500 m)
Communications Method
Half-duplex
Synchronization Method
Start-stop
Baud Rate
0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 (kbps)
Transmission Distance
Transmission Specifications
EtherNet/IP Port*12 Media Access Method
CSMA/CD
Modulation
Baseband
Transmission Paths
Star
Baud Rate
100 Mbps (100Base-TX)
Transmission Media
Shielded twisted-pair (STP) cable; Categories: 5, 5e
Transmission Distance
100 m (between Ethernet switch and node)
Number of Cascade Connections
No restrictions if Ethernet switch is used.
CIP Communications: Tag Data Links Communications Specifications
15 m max. ---
---
Number of Connections
256
32
Packet Interval (Refresh period)
0.5 to 10,000 ms (Unit: 0.5 ms) Can be set for each connection. (Data will be refreshed at the set interval, regardless of the number of nodes.)
1 to 10,000 ms (in 0.5-ms increments) Can be set for each connection. (Data will be refreshed at the set interval, regardless of the number of nodes.)
Permissible Communications Band
6,000 packets per second*13
3,000 packets per second*13
Number of Registrable Tags
256
32
Type of Tags
CIO, DM, EM, HR, WR, and network symbols
Number of Tags per Connection
8 (Seven tags if PLC status is included in the segment.)
*12 The EtherNet/IP port is built into the CJ2H-CPU6@-EIP and CJ2M-CPU3@ only. *13 “Packets per second” is the number of communications packets that can be processed per second.
1-18
CJ2 CPU Unit Hardware User’s Manual
Page 61
1 Overview
CPU65 (-EIP)
CPU66 (-EIP)
CJ2MCPU67 (-EIP)
CPU68 (-EIP)
CPU 11/31
CPU 12/32
CPU 13/33
CPU 14/34
CPU 15/35
Maximum Link Data Size per Node
184,832 words
640 words
Maximum Data Size per Connection
252 or 722 words*14 (Data is synchronized within each connection.)
640 words (Data is synchronized within each connection.)*15
Number of Registrable Tag Set
256 (1 connection = 1 segment)
32 (1 connection = 1 segment)
Maximum Tag Set Size
722 words (One word is used when PLC status is included in the segment.)
640 words (One word is used when PLC status is included in the segment.)*15
Maximum Number of Tags Refreshable in a Single Cycle of CPU Unit*16
Output/send (CPU Unit to EtherNet/IP): 256 Input/receive (EtherNet/IP to CPU Unit): 256
Output/send (CPU Unit to EtherNet/IP): 32 Input/receive (EtherNet/IP to CPU Unit): 32
Data Size Refreshable in a Single Cycle of CPU Unit*16
Output/send (CPU to EtherNet/IP): 6,432 words Input/receive (EtherNet/IP to CPU): 6,432 words
Output/send (CPU Unit to EtherNet/IP): 640 words Input/receive (EtherNet/IP to CPU Unit): 640 words
Change of Tag Data Link Parameter Settings during Operation
OK*17
Multi-cast Packet Filter*18
OK
CIP Communications: Explicit Messages
---
Class 3 (Number of Connections)
Number of connections: 128
UCMM (Non-connection Type)
Maximum number of clients that can communicate at the same time: 32 Maximum number of servers that can communicate at the same time: 32
CIP Routing
OK (CIP routing is enabled for the following remote Units: CJ1W-EIP21, CJ2H-CPU6@-EIP, CJ2MCPU3@, and CS1W-EIP21.)
FINS Communications
Maximum number of clients that can communicate at the same time: 16 Maximum number of servers that can communicate at the same time: 16
---
FINS/UDP
OK
FINS/TCP
16 connections max.
EtherNet/IP Conformance Test
Conforms to A5.
EtherNet/IP Interface
10Base-T/100Base-TX Auto Negotiation/Fixed Setting
*14 Large Forward Open (CIP optional specification) must be supported in order for 505 to 1,444 bytes to be used as the data size. Application is supported between CS/CJ-series PLCs. When connecting to devices from other manufacturers, make sure that the devices support the Large Forward Open specification. *15 Unit version 2.0 of built-in EtherNet/IP section: 20 words *16 If the maximum number is exceeded, refreshing will require more than one CPU Unit cycle. *17 When changing parameters, however, the EtherNet/IP port where the change is made will be restarted. In addition, a timeout will temporarily occur at the other node that was communicating with that port, and it will then recover automatically. *18 The EtherNet/IP port supports an IGMP client, so unnecessary multicast packets are filtered by using an Ethernet switch that supports IGMP snooping.
CJ2 CPU Unit Hardware User’s Manual
1-19
1 1-3-2 Performance Specifications
Communications Specifications
Communications
CPU64 (-EIP)
1-3 Specifications
CJ2HItem
Page 62
1 Overview
CJ2HItem
Pulse I/O*3
External interface
CPU64 (-EIP) ---
Pulse Inputs
CPU65 (-EIP)
CPU66 (-EIP)
CJ2MCPU67 (-EIP)
CPU68 (-EIP)
CPU 11/31
CPU 12/32
CPU 13/33
CPU 14/34
CPU 15/35
CJ2M-MD211 or CJ2M-MD212 Pulse I/O Module with 40-pin MIL connector Can be used as normal inputs, interrupt inputs, quick-response inputs, or high-speed counter inputs. (Functions of each input must be selected in the PLC Setup.) Input method: Line-driver input or 24-VDC input (selected by wiring)
Normal inputs
20 max. (10 per Pulse I/O Module) Input constants: Set in the PLC Setup (0, 0.5, 1, 2, 4, 8, 16, or 32 ms). Default: 8 ms
Interrupt inputs and quickresponse inputs
8 max. (4 per Pulse I/O Module) Input signal minimum ON pulse width: 30 µs
High-speed counter inputs
4 max. (2 per Pulse I/O Module) Input method: Differential-phase (×4) pulses, pulse + direction, up/down pulses, or increment pulse Maximum response frequency: 50 kHz for differential phases or 100 kHz for single phase Counting mode: Linear mode or circular (ring) mode Count value: 32 bits Counter reset: Phase Z + software reset or software reset Control method: Target-value comparison or range comparison Gate function: Supported
Pulse Outputs
Can be used as normal outputs, pulse outputs, or PWM outputs. (Functions of each output must be selected in the PLC Setup.) Output method: Sinking or sourcing transistor outputs (The method is determined by Pulse I/O Module model.)
Normal outputs Pulse outputs
---
12 max. (6 per Pulse I/O Module) 4 max. (2 per Pulse I/O Module) Output method: CW/CCW or pulse + direction (The method is determined by the I/O wiring and the instructions used in the ladder program.) Output frequency: 1 pps to 100 kpps (in increments of 1 pps) Output Mode: Continuous mode (for speed control) or independent mode (for position control) Output pulses: Relative coordinates: 0000 0000 to 7FFF FFFF hex (0 to 2,147,483,647 pulses) Absolute coordinates: 8000 0000 to 7FFF FFFF hex (−2,147,483,648 to 2,147,483,647) Acceleration/deceleration curves: Linear or Scurve Origin search function: Supported
PWM outputs
4 max. (2 per Pulse I/O Module) Output frequency: 0.1 to 6,553.5 Hz (in 0.1-Hz increments) or 1 to 32,800 Hz (in 1-Hz increments) Duty ratio: 0.0% to 100.0% (in 0.1% increments)
1-20
CJ2 CPU Unit Hardware User’s Manual