SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual: SECTION 1 PC Setup and Other Features, pages 121 to 130
Pages 121 to 130 of 520, from SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron CQM1-CPU21
Page 121
Section
Communications Functions
1-9
Link Errors
If a slave does not received a response from the master within one second, the 1:1 Link Error Flag (AR 0802) and the Communications Error Flag (AR 0804) will be turned ON.
Application Example
This example shows a program for verifying the conditions for executing a oneto-one link using the RS-232C ports. Before executing the program, set the following PC Setup parameters. Master: DM 6645: 3200 (one-to-one link master; Area used: LR 00 to LR 15) Slave: DM 6645: 2000 (one-to-one link slave) The defaults are assumed for all other PC Setup parameters. The words used for the one-to-one link are as shown below. Master
LR00 LR07 LR08
Slave
Area for writing
Area for reading
Area for reading
Area for writing
LR15
LR00 LR07 LR08 LR15
When the program is executed at both the master and the slave, the status of IR 001 of each Unit will be reflected in IR 100 of the other Unit. Likewise, the status of the other Unit’s IR 001 will be reflected in IR 100 of each Unit. IR 001 is an input word and IR 100 is an output word In the Master
25313 (Always ON) MOV(21) 001 LR00
MOV(21) LR08 100
In the Slave
25313 (Always ON) MOV(21) 001 LR08
MOV(21) LR00 100
1-9-8 CPM1/CPM1A One-to-one Link Communications In a one-to-one link, a CPM1/CPM1A is linked to another CPM1/CPM1A, a CQM1, or a C200HS through an RS-232C Adapter and standard RS-232C cable. One of the PCs will serve as the master and the other as the slave. The one-to-one link can connect up to 256 bits (LR 0000 to LR 1515) in the two PCs.
101
Page 122
Section
Communications Functions One-to-one CPM1/CPM1A Links
1-9
The following diagram shows a one-to-one link between two CPM1s PCs. Refer to the CPM1A Operation Manual for the corresponding information on the CPM1A. RS-232C Cable
RS-232C Adapter
RS-232C Adapter CPM1 CPU Unit
CPM1 CPU Unit
The words used for the one-to-one link are as shown below. LR00 Write data Read data
Master
Slave
Area for writing LR07 LR08
LR00 Read data
Area for reading
Area for reading
Area for writing
LR15
LR07 LR08
Write data
LR15
Limitations of One-to-one Links with a CPM1/CPM1A
Only the 16 LR words from LR 00 to LR 15 can be linked in the CPM1/CPM1A, so use only those 16 words in the CQM1 or C200HS when making a one-to-one link with one of those PCs. A one-to-one link cannot be made to a CPM1/CPM1A PC using LR 16 through LR 63 in the CQM1 or C200HS.
PC Setup Settings
The settings relating to 1-to-1 PC communications must be set as shown in the following table.
Word
Bit
DM 6650 00 to 07
Function Port settings1 00: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 01: Settings in DM 6651
Setting (Slave) 00 (Any value is OK)
08 to 11
Link area for one-to-one PC link via peripheral port 0: LR 00 to LR 15
0
0 (Any value is OK)
12 to 15
Communications mode1 0: Host link; 2: 1-to-1 PC link (slave); 3: 1-to-1 PC link (master); 4: NT link
3
2
Note
102
Setting (Master) 00 (Any value is OK)
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be turned ON, and the default setting (0 or 00) will be used. 2. For information on the 1-to-1 link settings for another OMRON PC, refer to that PC’s Operation Manual. 3. For information on CPM1/CPM1A one-to-one link connections and wiring diagrams refer to 3-4-7 Host Link Connections in the CPM1 Operation Manual or CPM1A Operation Manual. For the SRM1 refer to 3-4-4 RS-232C Port Wiring in the SRM1 Master Control Unit Operation Manual. 4. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Host Link Communications format: Standard settings (1 start bit, 7-bit data; even parity, 2 stop bits, 9,600 bps) Transmission delay: No Node number: 00
Page 123
Section
Communications Functions Example Program
This example shows ladder programs that copy the status of IR 000 in each CPM1/CPM1A to SR 200 in the other CPM1/CPM1A. Program in the Master
Program in the Slave
25313 (Always ON)
25313 (Always ON) MOV(21)
MOV(21) 000
000
LR00
LR08
MOV(21)
MOV(21) LR08
LR00
200
200
LR00 IR 000
Write
SR 200
1-9
Read
LR00 Writing area
LR07 LR08
Reading area
Reading area
Writing area
LR15
LR07 LR08
Read
SR 200
Write
IR 000
LR15
1-9-9 CPM1/CPM1A NT Link Communications Using the NT link, the CPM1/CPM1A PC can connected to the Programmable Terminal (NT Link Interface) through an RS-232C Adapter. CPM1 PCs RS-232C Adapter
Programmable Terminal
CPM1 CPU Unit CPM1 CPU
RS-232C Cable
CPM1A PCs RS-232C Adapter
OMRON Programmable Terminal
CPM1A CPU Unit
RS-232C Cable
PC Setup Settings Word Bit DM 6650 00 to 07
The settings relating to NT link PC communications must be set as shown in the following table. Function Port settings1 00: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 01: Settings in DM 6651
Setting 00 (Any value is OK)
08 to 11
Link area for one-to-one PC link via peripheral port 0: LR 00 to LR 15
0 (Any value is OK)
12 to 15
Communications mode1 0: Host link; 2: 1-to-1 PC link (slave); 3: 1-to-1 PC link (master); 4: NT link
4
103
Page 124
Section
Communications Functions Note
1-9
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be turned ON, and the default setting (0 or 00) will be used. 2. For information on the NT link settings for another OMRON PC, refer to that PC’s Operation Manual. 3. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode:
Host Link
Communications format:
Standard settings (1 start bit, 7-bit data; even parity, 2 stop bits, 9,600 bps)
Transmission delay:
No
Node number:
00
1-9-10 SRM1 One-to-one Link Communications In a one-to-one link, a SRM1 is linked to another SRM1, CPM1/CPM1A, a CQM1, or a C200HS through an RS-232C Adapter and standard RS-232C cable. One of the PCs will serve as the master and the other as the slave. The one-to-one link can connect up to 256 bits (LR 0000 to LR 1515) in the two PCs. One-to-one SRM1 Links
The following diagram shows a one-to-one link between two SRM1s.
SRM1
SRM1
RS-232C Port
RS-232C Port
The words used for the one-to-one link are as shown below.
LR00 Write data Read data
Area for writing LR07 LR08 LR15
Limitations of One-to-one Links with a SRM1
104
Master
Area for reading
Slave
LR00 Read data
Area for reading Area for writing
LR07 LR08
Write data
LR15
Only the 16 LR words from LR 00 to LR 15 can be linked in the SRM1, so use only those 16 words in the CQM1 or C200HS when making a one-to-one link with one of those PCs. A one-to-one link cannot be made to a SRM1 PC using LR 16 through LR 63 in the CQM1 or C200HS.
Page 125
Section
Communications Functions PC Setup Settings
Word
The settings relating to 1-to-1 PC communications must be set as shown in the following table.
Bit
DM 6645 00 to 03
Function Port settings1 00: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 01: Settings in DM 6651
Setting (Master) Any
Setting (Slave) Any
04 to 07
CTS Control settings 0: Disable 1: Set
0
0
08 to 11
Link area for one-to-one PC link via peripheral port 0: LR 00 to LR 15 Communications mode1 0: Host link; 1: No protocol; 2: 1-to-1 PC link (slave); 3: 1-to-1 PC link (master); 4: NT link
0
0
3
2
12 to 15
1-9
Note
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be turned ON, and the default setting (0 or 00) will be used. 2. For information on the 1-to-1 link settings for another OMRON PC, refer to that PC’s Operation Manual. 3. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range.
Example Program
Communications mode:
Host Link
Communications format:
Standard settings (1 start bit, 7-bit data; even parity, 2 stop bits, 9,600 bps)
Transmission delay:
No
Node number:
00
This example shows ladder programs that copy the status of IR 000 in each SRM1 to SR 200 in the other SRM1.
Program in the Master
Program in the Slave
25313 (Always ON)
25313 (Always ON) MOV(21)
MOV(21) 000
000
LR00
LR08
MOV(21)
MOV(21) LR08
LR00
200
200
LR00 IR 000 SR 200
Write Read
LR00 Writing area
LR07 LR08 LR15
Reading area
Reading area Writing area
LR07 LR08
Read
SR 200
Write
IR 000
LR15
105
Page 126
Section
Communications Functions
1-9
1-9-11 SRM1 NT Link Communications Using the NT link, the SRM1 PC can be connected to the Programmable Terminal (NT Link Interface.) The RS-232C port can be used to the NT Link. SRM1 Programmable Terminal
NT Link is possible only with the SRM1-C02-V1, which has an RS-232C port. PC Setup Settings Word Bit DM 6645 00 to 03
The settings relating to NT link PC communications must be set as shown in the following table. Function Port settings1 00: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 01: Settings in DM 6646
00 (Any value is OK)
04 to 07
CTS control settings 0: Disable 1: Set
0 (Any value is OK)
08 to 11
Link area for one-to-one PC link via peripheral port 0: LR 00 to LR 15 Communications mode1 0: Host link; 1: No protocol; 2: 1-to-1 PC link (slave); 3: 1-to-1 PC link (master); 4: NT link
0
12 to 15
Note
106
Setting
4
1. If an improper setting is used, a non-fatal error will occur, AR 1302 will be turned ON, and the default setting (0 or 00) will be used. 2. For information on the NT link settings for another OMRON PC, refer to that PC’s Operation Manual. 3. If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Host Link Communications format: Standard settings (1 start bit, 7-bit data; even parity, 2 stop bits, 9,600 bps) Transmission delay: No Node number: 00
Page 127
Section
Communications Functions
1-9
1-9-12 SRM1 No Protocol Communications Peripheral Port Settings
Word
When the peripheral port is used to conduct no protocol communications, the following settings must be made from the peripheral device to DM 6650 to DM 6653 in the SRM1.
Bit
Function
Setting
Peripheral Port Settings The following settings are effective after transfer to the PC. DM 6650 00 to 03 Port settings 0: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 1: Settings in DM 6651
As required
(Other settings will cause a non-fatal error, the default setting (0) will be used, and AR 1302 will turn ON.) 04 to 07 08 to 11 12 to 15
DM 6651
00 to 07 08 to 15
DM 6652
DM 6653
00 to 15
00 to 07
08 to 11
12 to 15
Not used. Not used. Communications mode 0: Host link; 1: No protocol (Other settings will cause a non-fatal error, the default setting (0) will be used, and AR 1302 will turn ON.) Baud rate 00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K Frame format Start Length Stop Parity 00: 1 bit 7 bits 1 bit Even 01: 1 bit 7 bits 1 bit Odd 02: 1 bit 7 bits 1 bit None 03: 1 bit 7 bits 2 bit Even 04: 1 bit 7 bits 2 bit Odd 05: 1 bit 7 bits 2 bit None 06: 1 bit 8 bits 1 bit Even 07: 1 bit 8 bits 1 bit Odd 08: 1 bit 8 bits 1 bit None 09: 1 bit 8 bits 2 bit Even 10: 1 bit 8 bits 2 bit Odd 11: 1 bit 8 bits 2 bit None (Other settings will cause a non-fatal error, the default setting (00) will be used, and AR 1302 will turn ON.) Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms. (Other settings will cause a non-fatal error, the default setting (0000) will be used, and AR 1302 will turn ON.) Node number (Host link) 00 to 31 (BCD) (Other settings will cause a non-fatal error, the default setting (0000) will be used, and AR 1302 will turn ON.) Start code enable (RS-232C, effective when bits 12 to 15 of DM 6650 are set to 1.) 0: Disable 1: Set End code enable (RS-232C, effective when bits 12 to 15 of DM 6650 are set to 1.) 0: Disable (number of bytes received) 1: Set (specified end code) 2: CR, LF
0 0 1: No protocol
As required As required
To match host parameters 00 to 31
As required As required
107
Page 128
Section
Communications Functions Word DM 6654
Bit
Function
Setting
00 to 07
Start code (effective when bits 08 to 11 of DM6650 are set to 1.) 00: 256 bytes 01 to FF: 1 to 255 bytes
As required
08 to 15
End code (no protocol)
As required
When bits 12 to 15 of DM6653 are set to 0: 00: 256 bytes 01 to FF: 1 to 255 bytes
1-9
When bits 12 to 15 of DM6653 are set to 1: Setting: 00 to FF (binary)
Note If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range.
RS-232C Port Settings
Word
Bit
Communications mode:
Host Link
Communications format:
Standard settings (1 start bit, 7-bit data; even parity, 2 stop bits, 9,600 bps)
Transmission delay:
No
Node number:
00
When the RS-232C port is used to conduct no protocol communications, the following settings must be made from the peripheral device to DM6645 to DM6649 in the SRM1. Function
Setting
RS-232C Port Settings The following settings are effective after transfer to the PC. DM 6645 00 to 03 Port settings 0: Standard (1 start bit, 7-bit data, even parity, 2 stop bits, 9,600 bps) 1: Settings in DM 6646 04 to 07 08 to 11 12 to 15
DM 6646
00 to 07 08 to 15
DM 6647
108
00 to 15
CTS control settings 0: Disable; 1: Set Link words for 1:1 link 0: LR 00 to LR 15; Other: Not effective Communications mode 0: Host link; 1: RS-232C (no protocol); 2: 1:1 data link slave; 3: 1:1 data link master; 4: NT Link Baud rate 00: 1.2K, 01: 2.4K, 02: 4.8K, 03: 9.6K, 04: 19.2K Frame format Start Length Stop Parity 00: 1 bit 7 bits 1 bit Even 01: 1 bit 7 bits 1 bit Odd 02: 1 bit 7 bits 1 bit None 03: 1 bit 7 bits 2 bit Even 04: 1 bit 7 bits 2 bit Odd 05: 1 bit 7 bits 2 bit None 06: 1 bit 8 bits 1 bit Even 07: 1 bit 8 bits 1 bit Odd 08: 1 bit 8 bits 1 bit None 09: 1 bit 8 bits 2 bit Even 10: 1 bit 8 bits 2 bit Odd 11: 1 bit 8 bits 2 bit None Transmission delay (Host Link) 0000 to 9999 (BCD): Set in units of 10 ms, e.g., setting of 0001 equals 10 ms
As required 0
0 1: No protocol As required As required
As required
Page 129
Section
Communications Functions Word DM 6648
Bit
Function
00 to 07
Node number (Host link, effective when bits 12 to 15 of DM 6645 are set to 0.) 00 to 31 (BCD) Start code enable (RS-232C, effective when bits 12 to 15 of DM 6645 are set to 1.) 0: Disable; 1: Set End code enable (RS-232C, effective when bits 12 to 15 of DM 6645 are set to 1.) 0: Disable (number of bytes received) 1: Set (specified end code) 2: CR, LF Start code (RS-232C) 00: 256 bytes 01 to FF: 1 to 255 bytes
08 to 11 12 to 15
DM 6649
00 to 07
08 to 15
1-9
Setting As required As required
End code enable (RS-232C) 00 to FF (BIN)
Note If an out-of-range value is set, the following communications conditions will result. In that case, reset the value so that it is within the permissible range. Communications mode: Communications format:
Transmission delay: Node number:
Host Link Standard settings (1 start bit, 7-bit data; even parity, 2 stop bits, 9,600 bps) No 00
109
Page 130
Section
Communications Functions
1-9
1-9-13 Transmission Data Configuration When no-protocol communications are used, TXD(48) is used to send data and RXD(47) to receive data. The maximum amount of data that can be either sent or received is 259 bytes, including the start/end code. • No Start or End Code: Data (256 bytes max.)
• Only a Start Code: ST
Data (256 bytes max.)
• Only an End Code: Data (256 bytes max.)
ED
• Both an Start and End Code: ST
Data (256 bytes max.)
ED
• End Code of CR, LF: Data (256 bytes max.)
CR
LF
CR
LF
• Start Code 00-FF/End Code CR,LF: ST
Note
Data (256 bytes max.)
1. The start and end codes are set in DM 6648 to DM 6649 and DM 6653 to DM 6654 of the PC Setup. 2. When there are several start and end codes, the first part of each will be effective. 3. When the end code duplicates the transmission data and the transmission is stopped part way through, use CR or LF as the end code. 4. The start and end codes are not stored.
1-9-14 Transmission Flags When sending data from the SRM1, check that the Transmission Enable Flag is ON for executing the TXD(48) instruction. The Transmission Enable Flag will turn OFF while the data is being transmitted and will turn ON again when transmission is complete. After the SRM1 has received data, the Receive Enable Flag turns ON. When the RXD instruction is executed, the data received will be written to the specified words and the Reception Complete Flag will turn OFF. Flag
Peripheral port
RS-232C port
Transmission Enable Flag
AR 0813
AR 0805
Reception Complete Flag
AR 0814
AR 0806
Note The timing from data reception starting to completion for the SRM1 is as indicated below. Reception Start: Without start code: With start code:
110
Normal reception status After start code is received.