The text of a manual · part 24 of 60
SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual: SECTION 5 Instruction Set, pages 209 to 218
Pages 209 to 218 of 520, from SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron CQM1-CPU21
Page 209
Section
Instruction Tables
5-6
5-6-2 CPM1/CPM1A Function Codes The following table lists the CPM1/CPM1A instructions that have fixed function codes. Each instruction is listed by mnemonic and by instruction name. Use the numbers in the leftmost column as the left digit and the number in the column heading as the right digit of the function code. Right digit
Left digit
0
1
2
3
4
5
6
7
8
0
NOP NO OPERATION
END END
IL INTERLOCK
ILC INTERLOCK CLEAR
JMP JUMP
JME JUMP END
(@) FAL FAILURE ALARM AND RESET
FALS SEVERE FAILURE ALARM
STEP STEP DEFINE
SNXT STEP START
9
1
SFT SHIFT REGISTER
KEEP KEEP
CNTR REVERSIBLE COUNTER
DIFU DIFFERENTIATE UP
DIFD DIFFERENTIATE DOWN
TIMH HIGHSPEED TIMER
(@) WSFT WORD SHIFT
(@) ASFT ASYNCHRONOUS SHIFT REGISTER
---
---
2
CMP COMPARE
(@) MOV MOVE
(@) MVN MOVE NOT
(@) BIN BCD TO BINARY
(@) BCD BINARY TO BCD
(@) ASL SHIFT LEFT
(@) ASR SHIFT RIGHT
(@) ROL ROTATE LEFT
(@) ROR ROTATE RIGHT
(@) COM COMPLEMENT
3
(@) ADD BCD ADD
(@) SUB BCD SUBTRACT
(@) MUL BCD MULTIPLY
(@) DIV BCD DIVIDE
(@) ANDW LOGICAL AND
(@) ORW LOGICAL OR
(@) XORW EXCLUSIVE OR
(@) XNRW EXCLUSIVE NOR
(@) INC INCREMENT
(@) DEC DECREMENT
4
(@) STC SET CARRY
(@) CLC CLEAR CARRY
---
---
---
---
(@) MSG MESSAGE DISPLAY
---
---
---
5
(@) ADB BINARY ADD
(@) SBB BINARY SUBTRACT
(@) MLB BINARY MULTIPLY
(@) DVB BINARY DIVIDE
(@) ADDL DOUBLE BCD ADD
(@) SUBL DOUBLE BCD SUBTRACT
(@) MULL DOUBLE BCD MULTIPLY
(@) DIVL DOUBLE BCD DIVIDE
---
---
6
CMPL DOUBLE COMPARE
(@) INI MODE CONTROL
(@) PRV HIGHSPEED COUNTER PV READ
(@) CTBL COMPARISON TABLE LOAD
---
---
---
(@) BCNT BIT COUNTER
(@) BCMP BLOCK COMPARE
(@) STIM INTERVAL TIMER
7
(@) XFER BLOCK TRANSFER
(@) BSET BLOCK SET
---
(@) XCHG DATA EXCHANGE
(@) SLD ONE DIGIT SHIFT LEFT
(@) SRD ONE DIGIT SHIFT RIGHT
(@) MLPX 4-TO-16 DECODER
(@) DMPX 16-TO-4 ENCODER
(@) SDEC 7-SEGMENT DECODER
---
8
(@) DIST SINGLE WORD DISTRIBUTE
(@) COLL DATA COLLECT
(@) MOVB MOVE BIT
(@) MOVD MOVE DIGIT
(@) SFTR REVERSIBLE SHIFT REGISTER
(@) TCMP TABLE COMPARE
(@) ASC ASCII CONVERT
---
---
(@) INT INTERRUPT CONTROL
9
---
(@) SBS SUBROUTINE ENTRY
SBN SUBROUTINE DEFINE
RET SUBROUTINE RETURN
---
---
---
(@) IORF I/O REFRESH
---
(@) MCRO MACRO
191
Page 210
Section
Instruction Tables
5-6
5-6-3 SRM1 Function Codes The following table lists the SRM1 instructions that have fixed function codes. Each instruction is listed by mnemonic and by instruction name. Use the numbers in the leftmost column as the left digit and the number in the column heading as the right digit of the function code. Right digit
Left digit
5
6
7
8
0
NOP NO OPERATION
END END
IL INTERLOCK
ILC INTERLOCK CLEAR
JMP JUMP
JME JUMP END
(@) FAL FAILURE ALARM AND RESET
FALS SEVERE FAILURE ALARM
STEP STEP DEFINE
SNXT STEP START
1
SFT SHIFT REGISTER
KEEP KEEP
CNTR REVERSIBLE COUNTER
DIFU DIFFERENTIATE UP
DIFD DIFFERENTIATE DOWN
TIMH HIGHSPEED TIMER
(@) WSFT WORD SHIFT
(@) ASFT ASYNCHRONOUS SHIFT REGISTER
---
---
2
CMP COMPARE
(@) MOV MOVE
(@) MVN MOVE NOT
(@) BIN BCD TO BINARY
(@) BCD BINARY TO BCD
(@) ASL SHIFT LEFT
(@) ASR SHIFT RIGHT
(@) ROL ROTATE LEFT
(@) ROR ROTATE RIGHT
(@) COM COMPLEMENT
3
(@) ADD BCD ADD
(@) SUB BCD SUBTRACT
(@) MUL BCD MULTIPLY
(@) DIV BCD DIVIDE
(@) ANDW LOGICAL AND
(@) ORW LOGICAL OR
(@) XORW EXCLUSIVE OR
(@) XNRW EXCLUSIVE NOR
(@) INC INCREMENT
(@) DEC DECREMENT
4
(@) STC SET CARRY
(@) CLC CLEAR CARRY
---
---
---
---
(@) MSG MESSAGE DISPLAY
---
---
---
5
(@) ADB BINARY ADD
(@) SBB BINARY SUBTRACT
(@) MLB BINARY MULTIPLY
(@) DVB BINARY DIVIDE
(@) ADDL DOUBLE BCD ADD
(@) SUBL DOUBLE BCD SUBTRACT
(@) MULL DOUBLE BCD MULTIPLY
(@) DIVL DOUBLE BCD DIVIDE
---
---
6
CMPL DOUBLE COMPARE
---
---
---
---
---
---
(@) BCNT BIT COUNTER
(@) BCMP BLOCK COMPARE
(@) STIM INTERVAL TIMER
7
(@) XFER BLOCK TRANSFER
(@) BSET BLOCK SET
---
(@) XCHG DATA EXCHANGE
(@) SLD ONE DIGIT SHIFT LEFT
(@) SRD ONE DIGIT SHIFT RIGHT
(@) MLPX 4-TO-16 DECODER
(@) DMPX 16-TO-4 ENCODER
(@) SDEC 7-SEGMENT DECODER
---
8
(@) DIST SINGLE WORD DISTRIBUTE
(@) COLL DATA COLLECT
(@) MOVB MOVE BIT
(@) MOVD MOVE DIGIT
(@) SFTR REVERSIBLE SHIFT REGISTER
(@) TCMP TABLE COMPARE
(@) ASC ASCII CONVERT
---
---
---
9
---
(@) SBS SUBROUTINE ENTRY
SBN SUBROUTINE DEFINE
RET SUBROUTINE RETURN
---
---
---
(@) IORF I/O REFRESH
---
(@) MCRO MACRO
192
0
1
2
3
4
9
Page 211
Section
Instruction Tables
5-6
5-6-4 Alphabetic List by Mnemonic Dashes (“–”) in the Code column indicate expansion instructions, which do not have fixed function codes. “None” indicates instructions for which function codes are not used. Mnemonic
Code
Words
Name
CPU Units
Page
7SEG
88
4
7-SEGMENT DISPLAY OUTPUT
CQM1 only
345
ACC (@)
––
4
ACCELERATION CONTROL
CQM-CPU43-E/-EV1 only
334
ADB (@)
50
4
BINARY ADD
All
289
ADBL (@)
––
4
DOUBLE BINARY ADD only
293
ADD (@)
30
4
BCD ADD
All
278
ADDL (@)
54
4
DOUBLE BCD ADD
All
284
AND
None
1
AND
All
196
AND LD
None
1
AND LOAD
All
197
AND NOT
None
1
AND NOT
All
196
ANDW (@) 34
4
LOGICAL AND
All
309
APR (@)
––
4
ARITHMETIC PROCESS
CQM1 only
305
ASC (@)
86
4
ASCII CONVERT
All
262
ASFT(@)
17
4
ASYNCHRONOUS SHIFT REGISTER
All
230
ASL (@)
25
2
ARITHMETIC SHIFT LEFT
All
225
ASR (@)
26
2
ARITHMETIC SHIFT RIGHT
All
226
AVG
––
4
AVERAGE VALUE
CQM1 only
302
BCD (@)
24
3
BINARY TO BCD
All
253
BCDL (@)
59
3
DOUBLE BINARY-TO-DOUBLE BCD
CQM1 only
254
BCMP (@)
68
4
BLOCK COMPARE
All
244
BCNT (@)
67
4
BIT COUNTER
All
320
BIN (@)
23
3
BCD-TO-BINARY
All
252
BINL (@)
58
3
DOUBLE BCD-TO-DOUBLE BINARY
CQM1 only
254
BSET (@)
71
4
BLOCK SET
All
234
CLC (@)
41
1
CLEAR CARRY
All
278
CMP
20
3
COMPARE
All
242
CMPL
60
4
DOUBLE COMPARE
All
246
CNT
None
2
COUNTER
All
210
CNTR
12
3
REVERSIBLE COUNTER
All
211
COLL (@)
81
4
DATA COLLECT
All
237
COLM(@)
––
4
LINE TO COLUMN
CQM1 only
274
COM (@)
29
2
COMPLEMENT
All
308
CPS
––
4
SIGNED BINARY COMPARE only
248
CPSL
––
4
DOUBLE SIGNED BINARY COMPARE only
249
CTBL(@)
63
4
COMPARISON TABLE LOAD
All
215
DBS (@)
––
4
SIGNED BINARY DIVIDE only
298
DBSL (@)
––
4
DOUBLE SIGNED BINARY DIVIDE only
299
DEC (@)
39
2
BCD DECREMENT
All
312
DIFD
14
2
DIFFERENTIATE DOWN
All
200
DIFU
13
2
DIFFERENTIATE UP
All
200
DIST (@)
80
4
SINGLE WORD DISTRIBUTE
All
235
DIV (@)
33
4
BCD DIVIDE
All
282
DIVL (@)
57
4
DOUBLE BCD DIVIDE
All
287
DMPX (@)
77
4
16-TO-4 ENCODER
All
257
DSW
87
4
DIGITAL SWITCH
CQM1 only
346
193
Page 212
Section
Instruction Tables Mnemonic
Code
Words
DVB (@)
53
4
BINARY DIVIDE
All
292
END
01
1
END
All
201
FAL (@)
06
2
FAILURE ALARM AND RESET
All
205
FALS
07
2
SEVERE FAILURE ALARM
All
205
FCS (@)
––
4
FCS CALCULATE
CQM1/SRM1 only
321
FPD
––
4
FAILURE POINT DETECT
CQM1 only
322
HEX (@)
––
4
ASCII-TO-HEXADECIMAL
CQM1/SRM1 only
263
HKY
––
4
HEXADECIMAL KEY INPUT
CQM1 only
347
HMS
––
4
SECONDS TO HOURS
CQM1 only
272
IL
02
1
INTERLOCK
All
201
ILC
03
1
INTERLOCK CLEAR
All
201
INC (@)
38
2
INCREMENT
All
311
INI (@)
61
4
MODE CONTROL
All
220
INT (@)
89
4
INTERRUPT CONTROL
All
326
IORF (@)
97
3
I/O REFRESH
All
318
JME
05
2
JUMP END
All
203
JMP
04
2
JUMP
All
203
KEEP
11
2
KEEP
All
199
LD
None
1
LOAD
All
196
LD NOT
None
1
LOAD NOT
All
196
LINE
––
4
LINE
CQM1 only
273
MAX (@)
––
4
FIND MAXIMUM
CQM1 only
300
MBS (@)
––
4
SIGNED BINARY MULTIPLY only
296
MBSL (@)
––
4
DOUBLE SIGNED BINARY MULTIPLY only
297
MCMP (@) 19
4
MULTI-WORD COMPARE
CQM1 only
301
MCRO (@) 99
4
MACRO
All
319
MIN (@)
––
4
FIND MINIMUM
CQM1 only
301
MLB (@)
52
4
BINARY MULTIPLY
All
291
MLPX (@)
76
4
4-TO-16 DECODER
All
255
MOV (@)
21
3
MOVE
All
232
MOVB (@)
82
4
MOVE BIT
All
239
MOVD (@)
83
4
MOVE DIGIT
All
240
MSG (@)
46
2
MESSAGE
All
317
MUL (@)
32
4
BCD MULTIPLY
All
281
MULL (@)
56
4
DOUBLE BCD MULTIPLY
All
286
MVN (@)
22
3
MOVE NOT
All
232
NEG (@)
––
4
2’S COMPLEMENT only
275
NEGL (@)
––
4
DOUBLE 2’S COMPLEMENT only
276
NOP
00
1
NO OPERATION
All
201
OR
None
1
OR
All
196
OR LD
None
1
OR LOAD
All
197
OR NOT
None
1
OR NOT
All
196
ORW (@)
35
4
LOGICAL OR
All
309
OUT
None
2
OUTPUT
All
197
OUT NOT
None
2
OUTPUT NOT
All
197
PID
––
4
PID CONTROL only
338
PLS2 (@)
––
4
PULSE OUTPUT
CQM1-CPU43-E/-EV1 only
332
PRV (@)
62
4
HIGH-SPEED COUNTER PV READ
All
221
194
Name
CPU Units
5-6 Page
Page 213
Section
Instruction Tables Name
CPU Units
5-6
Mnemonic
Code
Words
Page
PULS (@)
65
4
SET PULSES
CQM1 and CPM1A-CDT/CDT1 only
328
PWM (@)
––
4
PULSE WITH VARIABLE DUTY RATIO
CQM1-CPU43-E/-EV1 only
336
RET
93
1
SUBROUTINE RETURN
All
315
ROL (@)
27
2
ROTATE LEFT
All
226
ROOT (@)
72
3
SQUARE ROOT
CQM1 only
288
ROR (@)
28
2
ROTATE RIGHT
All
227
RSET
None
2
RESET
All
198
RXD (@)
47
4
RECEIVE
CQM1/SRM1 only
340
SBB (@)
51
4
BINARY SUBTRACT
All
290
SBBL (@)
––
4
DOUBLE BINARY SUBTRACT only
294
SBN
92
2
SUBROUTINE DEFINE
All
315
SBS (@)
91
2
SUBROUTINE ENTRY
All
313
SCL (@)
66
4
SCALING
CQM1 only
266
SCL2 (@)
––
4
SIGNED BINARY TO BCD SCALING only
268
SCL3 (@)
––
4
BCD TO SIGNED BINARY SCALING only
269
SDEC (@)
78
4
7-SEGMENT DECODER
All
259
SEC
––
4
HOURS TO SECONDS
CQM1 only
271
SET
None
2
SET
All
198
SFT
10
3
SHIFT REGISTER
All
224
SFTR (@)
84
4
REVERSIBLE SHIFT REGISTER
All
229
SLD (@)
74
3
ONE DIGIT SHIFT LEFT
All
228
SNXT
09
2
STEP START
All
206
SPED (@)
64
4
SPEED OUTPUT
CQM1 and CPM1A-CDT/CDT1 only
330
SRCH (@)
––
4
DATA SEARCH
CQM1 only
337
SRD (@)
75
3
ONE DIGIT SHIFT RIGHT
All
228
STC (@)
40
1
SET CARRY
All
278
STEP
08
2
STEP DEFINE
All
206
STIM (@)
69
4
INTERVAL TIMER
All
213
STUP
––
3
CHANGE RS-232C SETUP
SRM1 only
344
SUB (@)
31
4
BCD SUBTRACT
All
279
SUBL (@)
55
4
DOUBLE BCD SUBTRACT
All
285
SUM (@)
––
4
SUM
CQM1 only
303
TCMP (@)
85
4
TABLE COMPARE
All
243
TIM
None
2
TIMER
All
209
TIMH
15
3
HIGH-SPEED TIMER
All
212
TKY (@)
18
4
TEN KEY INPUT
CQM1 only
347
TRSM
45
1
TRACE MEMORY SAMPLE only
315
TXD (@)
48
4
TRANSMIT
CQM1/SRM1 only
342
WSFT (@)
16
3
WORD SHIFT
All
225
XCHG (@)
73
3
DATA EXCHANGE
All
235
XFER (@)
70
4
BLOCK TRANSFER
All
233
XFRB (@)
––
4
TRANSFER BITS only
241
XNRW (@)
37
4
EXCLUSIVE NOR
All
311
XORW (@) 36
4
EXCLUSIVE OR
All
310
ZCP
––
4
AREA RANGE COMPARE only
250
ZCPL
––
4
DOUBLE AREA RANGE COMPARE only
252
195
Page 214
Section
Ladder Diagram Instructions
5-7
5-7
Ladder Diagram Instructions Ladder diagram instructions include ladder instructions and logic block instructions and correspond to the conditions on the ladder diagram. Logic block instructions are used to relate more complex parts.
5-7-1 LOAD, LOAD NOT, AND, AND NOT, OR, and OR NOT Ladder Symbols
Operand Data Areas
B
B: Bit
LOAD – LD
IR, SR, AR, HR, TC, LR, TR
B: Bit
B
LOAD NOT – LD NOT
IR, SR, AR, HR, TC, LR
B: Bit
B
AND – AND IR, SR, AR, HR, TC, LR
B: Bit
B
AND NOT – AND NOT
IR, SR, AR, HR, TC, LR
B: Bit
OR – OR
B
OR NOT – OR NOT
B
IR, SR, AR, HR, TC, LR
B: Bit IR, SR, AR, HR, TC, LR
Limitations
There is no limit to the number of any of these instructions, or restrictions in the order in which they must be used, as long as the memory capacity of the PC is not exceeded.
Description
These six basic instructions correspond to the conditions on a ladder diagram. As described in Section 4 Ladder-diagram Programming, the status of the bits assigned to each instruction determines the execution conditions for all other instructions. Each of these instructions and each bit address can be used as many times as required. Each can be used in as many of these instructions as required. The status of the bit operand (B) assigned to LD or LD NOT determines the first execution condition. AND takes the logical AND between the execution condition and the status of its bit operand; AND NOT, the logical AND between the execution condition and the inverse of the status of its bit operand. OR takes the logical OR between the execution condition and the status of its bit operand; OR NOT, the logical OR between the execution condition and the inverse of the status of its bit operand.
Flags
196
There are no flags affected by these instructions.
Page 215
Section
Bit Control Instructions
5-8
5-7-2 AND LOAD and OR LOAD AND LOAD – AND LD Ladder Symbol
00000
00002
00001
00003
OR LOAD – OR LD 00000
00001
00002
00003
Ladder Symbol
Description
When instructions are combined into blocks that cannot be logically combined using only OR and AND operations, AND LD and OR LD are used. Whereas AND and OR operations logically combine a bit status and an execution condition, AND LD and OR LD logically combine two execution conditions, the current one and the last unused one. In order to draw ladder diagrams, it is not necessary to use AND LD and OR LD instructions, nor are they necessary when inputting ladder diagrams directly, as is possible from the SSS. They are required, however, to convert the program to and input it in mnemonic form. In order to reduce the number of programming instructions required, a basic understanding of logic block instructions is required. For an introduction to logic blocks, refer to 4-3-6 Logic Block Instructions.
Flags
There are no flags affected by these instructions.
5-8
Bit Control Instructions There are seven instructions that can be used generally to control individual bit status. These are OUT, OUT NOT, DIFU(13), DIFD(14), SET, RSET, and KEEP(11). These instructions are used to turn bits ON and OFF in different ways.
5-8-1 OUTPUT and OUTPUT NOT – OUT and OUT NOT OUTPUT – OUT
Ladder Symbol
Operand Data Areas B: Bit B
OUTPUT NOT – OUT NOT
Ladder Symbol
IR, SR, AR, HR, LR, TR
Operand Data Areas B: Bit B
IR, SR, AR, HR, LR
Limitations
Any output bit can generally be used in only one instruction that controls its status.
Description
OUT and OUT NOT are used to control the status of the designated bit according to the execution condition.
197
Page 216
Section
Bit Control Instructions
5-8
OUT turns ON the designated bit for an ON execution condition, and turns OFF the designated bit for an OFF execution condition. With a TR bit, OUT appears at a branching point rather than at the end of an instruction line. Refer to 4-3-8 Branching Instruction Lines for details. OUT NOT turns ON the designated bit for a OFF execution condition, and turns OFF the designated bit for an ON execution condition. OUT and OUT NOT can be used to control execution by turning ON and OFF bits that are assigned to conditions on the ladder diagram, thus determining execution conditions for other instructions. This is particularly helpful and allows a complex set of conditions to be used to control the status of a single work bit, and then that work bit can be used to control other instructions. The length of time that a bit is ON or OFF can be controlled by combining the OUT or OUT NOT with TIM. Refer to Examples under 5-15-1 TIMER – TIM for details.
Flags
There are no flags affected by these instructions.
5-8-2 SET and RESET – SET and RSET Ladder Symbols
Operand Data Areas
SET B
B: Bit IR, SR, AR, HR, LR
RSET B
B: Bit IR, SR, AR, HR, LR
Description
SET turns the operand bit ON when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF. RSET turns the operand bit OFF when the execution condition is ON, and does not affect the status of the operand bit when the execution condition is OFF. The operation of SET differs from that of OUT because the OUT instruction turns the operand bit OFF when its execution condition is OFF. Likewise, RSET differs from OUT NOT because OUT NOT turns the operand bit ON when its execution condition is OFF.
Precautions
The status of operand bits for SET and RSET programmed between IL(02) and ILC(03) or JMP(04) and JME(05) will not change when the interlock or jump condition is met (i.e., when IL(02) or JMP(04) is executed with an OFF execution condition).
Flags
There are no flags affected by these instructions.
Examples
The following examples demonstrate the difference between OUT and SET/ RSET. In the first example (Diagram A), IR 10000 will be turned ON or OFF whenever IR 00000 goes ON or OFF.
198
Page 217
Section
Bit Control Instructions
5-8
In the second example (Diagram B), IR 10000 will be turned ON when IR 00001 goes ON and will remain ON (even if IR 00001 goes OFF) until IR 00002 goes ON.
00000 10000
Diagram A
Address
Instruction
00000 00001
LD OUT
Address
Instruction
00000 00001 00002 00003
LD SET LD RSET
Operands 00000 10000
00001 SET 10000 00002 RSET 10000
Diagram B
Operands 00001 10000 00002 10000
5-8-3 KEEP – KEEP(11) Ladder Symbol
Operand Data Areas S
B: Bit
KEEP(11) B R
IR, SR, AR, HR, LR
Limitations
Any output bit can generally be used in only one instruction that controls its status.
Description
KEEP(11) is used to maintain the status of the designated bit based on two execution conditions. These execution conditions are labeled S and R. S is the set input; R, the reset input. KEEP(11) operates like a latching relay that is set by S and reset by R. When S turns ON, the designated bit will go ON and stay ON until reset, regardless of whether S stays ON or goes OFF. When R turns ON, the designated bit will go OFF and stay OFF until reset, regardless of whether R stays ON or goes OFF. The relationship between execution conditions and KEEP(11) bit status is shown below.
S execution condition R execution condition
Status of B
Flags
There are no flags affected by this instruction.
199
Page 218
Section
Bit Control Instructions Precautions
5-8
Exercise caution when using a KEEP reset line that is controlled by an external normally closed device. Never use an input bit in an inverse condition on the reset (R) for KEEP(11) when the input device uses an AC power supply. The delay in shutting down the PC’s DC power supply (relative to the AC power supply to the input device) can cause the designated bit of KEEP(11) to be reset. This situation is shown below. Input Unit A
S KEEP(11)
NEVER
B
A R
Bits used in KEEP are not reset in interlocks. Refer to the 5-11 INTERLOCK – and INTERLOCK CLEAR IL(02) and ILC(03) for details.
5-8-4 DIFFERENTIATE UP and DOWN – DIFU(13) and DIFD(14) Ladder Symbols
Operand Data Areas
DIFU(13) B
B: Bit IR, SR, AR, HR, LR
DIFD(14) B
B: Bit IR, SR, AR, HR, LR
Limitations
Any output bit can generally be used in only one instruction that controls its status.
Description
DIFU(13) and DIFD(14) are used to turn the designated bit ON for one cycle only. Whenever executed, DIFU(13) compares its current execution with the previous execution condition. If the previous execution condition was OFF and the current one is ON, DIFU(13) will turn ON the designated bit. If the previous execution condition was ON and the current execution condition is either ON or OFF, DIFU(13) will either turn the designated bit OFF or leave it OFF (i.e., if the designated bit is already OFF). The designated bit will thus never be ON for longer than one cycle, assuming it is executed each cycle (see Precautions, below). Whenever executed, DIFD(14) compares its current execution with the previous execution condition. If the previous execution condition was ON and the current one is OFF, DIFD(14) will turn ON the designated bit. If the previous execution condition was OFF and the current execution condition is either ON or OFF, DIFD(14) will either turn the designated bit OFF or leave it OFF. The designated bit will thus never be ON for longer than one cycle, assuming it is executed each cycle (see Precautions, below). These instructions are used when differentiated instructions (i.e., those prefixed with an @) are not available and single-cycle execution of a particular instruction is desired. They can also be used with non-differentiated forms of instructions that have differentiated forms when their use will simplify programming. Examples of these are shown below.
Flags
200
There are no flags affected by these instructions.