SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual: SECTION 6 Host Link Commands, pages 375 to 382

Pages 375 to 382 of 520, from SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual

The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron CQM1-CPU21

Page 375

Section

Host Link Commands Parameters

6-3

Read Data (Response) The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.

6-3-3 HR AREA READ –– RH Reads the contents of the specified number of HR words, starting from the specified word. Command Format @ x 101 x 100

R

Node no.

H

Header code

Note

Response Format @ x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100 Beginning word1

No. of words2

FCS

↵

Terminator

1. Beginning word: 0000 to 0099 in CQM1 PCs, 0000 to 0019 in CPM1/CPM1A/SRM1 PCs 2. No. of words: 0001 to 0100 in CQM1 PCs, 0001 to 0020 in CPM1/CPM1A/SRM1 PCs An end code of 00 indicates normal completion.

x 101 x 100

R

Node no.

H

Header code

Parameters x 161 x 160 x 163 x 162 x 161 x 160

End code

Read data (1 word)

FCS

↵

Terminator

Read data (for number of words read)

Read Data (Response) The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.

6-3-4 PV READ –– RC Reads the contents of the specified number of timer/counter PVs (present values), starting from the specified timer/counter. Command Format @ x 101 x 100

Node no.

C x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100

Header code

Beginning timer/counter1 No. of timers/counters2

R

Note

Response Format @ x 101 x 100

Node no.

FCS

↵

Terminator

1. Beginning T/C: 0000 to 0511 in CQM1 PCs, 0000 to 0127 in CPM1/CPM1A/SRM1 PCs 2. No. of T/Cs: 0001 to 0512 in CQM1 PCs, 0001 to 0128 in CPM1/CPM1A/SRM1 PCs An end code of 00 indicates normal completion.

R

C

Header code x 161 x 160 x 103 x 102 x 101 x 100

End code

Read data (1 word) Read data (for number of words read)

FCS

↵

Terminator

The response will be divided when reading more than 30 words of data.

357

Page 376

Section

Host Link Commands Parameters

6-3

Read Data (Response) The number of present values specified by the command is returned in hexadecimal as a response. The PVs are returned in order, starting with the specified beginning timer/counter.

6-3-5 TC STATUS READ –– RG Reads the status of the Completion Flags of the specified number of timers/ counters, starting from the specified timer/counter. Command Format @ x 101 x 100

G x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100

Header code

Beginning timer/counter1 No. of timers/counters2

R

Node no.

Note

Response Format

FCS

↵

Terminator

1. Beginning T/C: 0000 to 0511 in CQM1 PCs, 0000 to 0127 in CPM1/CPM1A/SRM1 PCs 2. No. of T/Cs: 0001 to 0512 in CQM1 PCs, 0001 to 0128 in CPM1/CPM1A/SRM1 PCs An end code of 00 indicates normal completion. @ x 101 x 100 Node no.

R

G

Header code x 161 x 160 ON/ OFF

End code

FCS

↵

Terminator

Read data (1 timer/counter) Read data (for number of TC read)

The response will be divided when reading the status of more than 123 timer/ counters. Parameters

Read Data (Response) The status of the number of Completion Flags specified by the command is returned as a response. “1” indicates that the Completion Flag is ON.

6-3-6 DM AREA READ –– RD Reads the contents of the specified number of DM words, starting from the specified word. Command Format @ x 101 x 100

R

Node no.

Header code

D x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100

Beginning word*

No. of words (0001 to 6656)

FCS

↵

Terminator

Note Beginning word: 0000 to 6655 in CQM1 PCs, 0000 to 1023 and 6144 to 6655 in CPM1/CPM1A PCs, and 0000 to 2047 and 6144 to 6655 in SRM1 PCs. Response Format @ x 101 x 100

Node no.

358

An end code of 00 indicates normal completion. R

D

Header code x 161 x 160 x 163 x 162 x 161 x 160

End code

Read data (1 word) Read data (for number of words read)

FCS

↵

Terminator

Page 377

Section

Host Link Commands Note

Parameters

6-3

1. Words 1024 to 6143 in CPM1/CPM1A PCs and words 2048 to 6143 in SRM1 PCs cannot be specified. If an attempt to read any of these words is made, a response of 0000 will be returned. 2. The response will be divided when reading more than 30 words of data. Read Data (Response) The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.

Note Be careful about the configuration of the DM area, as it varies depending on the CPU Unit model.

6-3-7 AR AREA READ –– RJ Reads the contents of the specified number of AR words, starting from the specified word. Command Format @ x 101 x 100

Node no.

R

Header code

Note

Response Format @

J x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100 Beginning word1

No. of words2

FCS

↵

Terminator

1. Beginning word: 0000 to 0027 in CQM1 PCs, 0000 to 0015 in CPM1/CPM1A/SRM1 PCs 2. No. of words: 0001 to 0028 in CQM1 PCs, 0001 to 0016 in CPM1/CPM1A/SRM1 PCs An end code of 00 indicates normal completion.

x 101 x 100

R

Node no.

Header code

Parameters

J x 161 x 160 x 163 x 162 x 161 x 160

End code

Read data (1 word )

FCS

↵

Terminator

Read data (for number of words read)

Read Data (Response) The contents of the number of words specified by the command are returned in hexadecimal as a response. The words are returned in order, starting with the specified beginning word.

6-3-8 IR/SR AREA WRITE –– WR Writes data to the IR and SR areas, starting from the specified word. Writing is done word by word. Command Format @ x 101 x 100

W

Node no.

Header code

R

Note x 103 x 102 x 101 x 100 x 163 x 162 x 161 x 160

Beginning word*

Write data (1 word)

FCS

↵

Terminator

Write data (for number of words to write)

1. Beginning word: 0000 to 0252 in CQM1 PCs, 0000 to 0019 and 0200 to 0252 in CPM1/CPM1A/SRM1 PCs. 2. Divide the command when writing more than 30 words of data.

359

Page 378

Section

Host Link Commands Response Format

6-3

An end code of 00 indicates normal completion. @ x 101 x 100

Node no.

R x 161 x 160

Header code

End code

W

FCS

↵

Terminator

Note Words 0020 to 0199 in CPM1/CPM1A/SRM1 PCs cannot be specified. If an attempt to write to any of these words is made, the writing operation will not be executed and normal completion occurs. Parameters

Write Data (Command) Specify in order the contents of the number of words to be written to the IR or SR area in hexadecimal, starting with the specified beginning word. Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 252 is specified as the beginning word for writing,and two words of data are specified, then 253 will become the last word for writing data, and the command will not be executed because SR 253 is beyond the writable range.

6-3-9 LR AREA WRITE –– WL Writes data to the LR area, starting from the specified word. Writing is done word by word. Command Format @ x 101 x 100

W

Node no.

Header code

L x 103 x 102 x 101 x 100 x 163 x 162 x 161 x 160

Beginning word*

Write data (1 word)

FCS

↵

Terminator

Write data (for number of words to write )

Note Beginning word: 0000 to 0063 in CQM1 PCs, 0000 to 0015 in CPM1/CPM1A/SRM1 PCs Response Format

An end code of 00 indicates normal completion. @

Parameters x 101 x 100

W

L x 161 x 160

Node no.

Header code

End code

FCS

↵

Terminator

Write Data (Command) Specify in order the contents of the number of words to be written to the LR area in hexadecimal, starting with the specified beginning word. Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 60 is specified as the beginning word for writing and five words of data are specified, then 64 will become the last word for writing data, and the command will not be executed because LR 64 is beyond area boundary.

6-3-10 HR AREA WRITE –– WH Writes data to the HR area, starting from the specified word. Writing is done word by word.

360

Page 379

Section

Host Link Commands

6-3

Command Format @ x 101 x 100

Node no.

W

H

Header code x 103 x 102 x 101 x 100 x 163 x 162 x 161 x 160

Beginning word*

↵

Write data (1 word)

FCS

Terminator

Write data (for no. of words to write)

Note Beginning word: 0000 to 0063 in CQM1 PCs, 0000 to 0019 in CPM1/CPM1A/SRM1 PCs Response Format

An end code of 00 indicates normal completion. @ x 101 x 100

Node no.

Parameters

H x 161 x 160

Header code

End code

W

↵

FCS

Terminator

Write Data (Command) Specify in order the contents of the number of words to be written to the HR area in hexadecimal, starting with the specified beginning word. Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 98 is specified as the beginning word for writing, and three words of data are specified, then 100 will become the last word for writing data, and the command will not be executed because HR 100 is beyond area boundary.

6-3-11 PV WRITE –– WC Writes the PVs (present values) of timers/counters starting from the specified timer/counter. Command Format @ x 101 x 100

W

Node no.

Header code

C x 103 x 102 x 101 x 100 x 103 x 102 x 101 x 100

Beginning timer/counter*

Write data (1 timer/counter)

↵

Terminator

FCS

Write data (for no. of PV to write)

Note

Response Format

1. Beginning T/C: 0000 to 0511 in CQM1 PCs, 0000 to 0127 in CPM1/ CPM1A/SRM1 PCs 2. Divide the command when writing more than 29 words of data. An end code of 00 indicates normal completion. @ x 101 x 100

Node no.

Parameters

C x 161 x 160

Header code

End code

W

FCS

↵

Terminator

Write Data (Command) Specify in decimal numbers (BCD) the present values for the number of timers/ counters that are to be written, starting from the beginning timer/counter. Note

1. When this command is used to write data to the PV area, the Completion Flags for the timers/counters that are written will be turned OFF.

361

Page 380

Section

Host Link Commands

6-3

2. If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 510 is specified as the beginning word for writing, and three words of data are specified, then 512 will become the last word for writing data, and the command will not be executed because TC 512 is beyond area boundary.

6-3-12 TC STATUS WRITE –– WG Writes the status of the Completion Flags for timers and counters in the TC area, starting from the specified timer/counter (number). Writing is done number by number. Command Format @ x 101 x 100

W

Node no.

G

Header code x 103 x 102 x 101 x 100 ON/ OFF

↵

Beginning timer/counter*

Terminator

FCS Write data (1 timer/counter) Write data (for number of TC to write)

Note

Response Format

1. Beginning T/C: 0000 to 0511 in CQM1 PCs, 0000 to 0127 in CPM1/CPM1A/SRM1 PCs 2. Divide the command when writing the status of more than 118 timer/counters. An end code of 00 indicates normal completion. @

Parameters x 101 x 100

W

G x 161 x 160

Node no.

Header code

End code

FCS

↵

Terminator

Write Data (Command) Specify the status of the Completion Flags, for the number of timers/counters to be written, in order (from the beginning word) as ON (i.e., “1”) or OFF (i.e., “0”). When a Completion Flag is ON, it indicates that the time or count is up. Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 510 is specified as the beginning word for writing, and three words of data are specified, then 512 will become the last word for writing data, and the command will not be executed because TC 512 is beyond area boundary.

6-3-13 DM AREA WRITE –– WD Writes data to the DM area, starting from the specified word. Writing is done word by word. Command Format @ x 101 x 100 Node no.

W

D

Header code

Note

362 x 103 x 102 x 101 x 100 x 163 x 162 x 161 x 160 Beginning word*

Write data (1 word)

FCS

↵

Terminator

Write data (for number of words to write)

1. Beginning word: 0000 to 6143 in CQM1 PCs, 0000 to 1023 and 6144 to 6655 in CPM1/CPM1A PCs, and 0000 to 2047 and 6144 to 6655 in SRM1 PCs

Page 381

Section

Host Link Commands

6-3

2. Divide the command when writing more than 29 words of data. Response Format

An end code of 00 indicates normal completion. @ x 101 x 100

Node no.

D x 161 x 160

Header code

End code

W

FCS

↵

Terminator

Note DM 1024 to DM 6143 in CPM1/CPM1A PCs and DM 2048 to DM 6143 in SRM1 PCs cannot be specified. If an attempt to write to any of these words is made, the writing operation will not be executed for these words and the command will end normally Parameters

Write Data (Command) Specify in order the contents of the number of words to be written to the DM area in hexadecimal, starting with the specified beginning word. Note

1. If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 6142 is specified as the beginning word for writing, and three words of data are specified, then 6144 will become the last word for writing data, and the command will not be executed because DM 6144 is beyond the writable range. 2. Be careful about the configuration of the DM area, as it varies depending on the CPU Unit model.

6-3-14 AR AREA WRITE –– WJ Writes data to the AR area, starting from the specified word. Writing is done word by word. Command Format @ x 101 x 100

Node no.

W

J

Header code x 103 x 102 x 101 x 100 x 163 x 162 x 161 x 160

Beginning word*

Write data (1 word)

↵

Terminator

FCS

Write data (for the number of words to write)

Note Beginning word: 0000 to 0027 in CQM1 PCs, 0000 to 0015 in CPM1/CPM1A and SRM1 PCs Response Format

An end code of 00 indicates normal completion. @ x 101 x 100 Node no.

Parameters

J x 161 x 160

Header code

End code

W

: FCS

↵

Terminator

Write Data (Command) Specify in order the contents of the number of words to be written to the AR area in hexadecimal, starting with the specified beginning word. Note If data is specified for writing which exceeds the allowable range, an error will be generated and the writing operation will not be executed. If, for example, 26 is specified as the beginning word for writing, and three words of data are specified, then 28 will become the last word for writing data, and the command will not be executed because AR 28 is beyond the writable range.

363

Page 382

Section

Host Link Commands

6-3

6-3-15 SV READ 1 –– R# Searches for the first instance of a TIM, TIMH(15), CNT, and CNTR(12) instruction with the specified TC number in the user’s program and reads the PV, which assumed to be set as a constant. The SV that is read is a 4-digit decimal number (BCD). The program is searched from the beginning, which may take as much as 10 seconds to produce a response. Command Format @ x 101 x 100 Node no.

R

#

OP1 OP2 OP3 OP4 x 103 x 102 x 101 x 100

Header code

Name

TC number*

↵

Terminator

FCS

Note TC number: 0000 to 0511 in CQM1 PCs, 0000 to 0127 in CPM1/CPM1A/SRM1 PCs Response Format @ x 101 x 100

R

Node no.

Header code

Parameters

# x 161 x 160 x 103 x 102 x 101 x 100

End code

↵

SV

FCS

Terminator

Name, TC Number (Command) Specify the instruction for reading the SV in “Name.” Make this setting in 4 characters. In “TC number,” specify the timer/counter number used for the instruction. Instruction name OP1

OP2

OP3

Classification

T

I

M

OP4 (Space)

T

I

M

H

HIGH-SPEED TIMER

C

N

T

(Space)

COUNTER

C

N

T

R

REVERSIBLE COUNTER

TIMER

SV (Response) The constant SV is returned. Note

1. The instruction specified under “Name” must be in four characters. 2. If the same instruction is used more than once in a program, only the first one will be read. 3. Use this command only when it is definite that a constant SV has been set. 4. The response end code will indicate an error (16) if the SV wasn’t entered as a constant.

6-3-16 SV READ 2 –– R$ Reads the constant SV or the word address where the SV is stored. The SV that is read is a 4-digit decimal number (BCD) written as the second operand for the TIM, TIMH(15), CNT, or CNTR(12) instruction at the specified program address in the user’s program. This can only be done with a program of less than 10K. Command Format @ x 101 x 100

Node no.

364

R

$

Header code x 103 x 102 x 101 x 100 OP1 OP2 OP3 OP4 x 103 x 102 x 101 x 100

Program address

Name

TC number*

FCS

↵

Terminator