SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual: SECTION 8 Troubleshooting, pages 449 to 457

Pages 449 to 457 of 520, from SYSMAC CQM1/CPM1/CPM1A/SRM1 Programmable Controllers Programming Manual

The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron CQM1-CPU21

Page 449

Section

Host Link Errors

8-7

Error Log Storage Methods

The error log storage method is set in the PC Setup (DM 6655). Set any of the following methods.

1, 2, 3...

1. You can store the most recent 7 error log records and discard older records. This is achieved by shifting the records as shown below so that the oldest record (record 0) is lost whenever a new record is generated. Lost Error log record 0 Error log record 1 All records shifted Error log record 5 Error log record 6

New record added

2. You can store only the first 7 error log records, and ignore any subsequent errors beyond those 7. 3. You can disable the log so that no records are stored. The default setting is the first method. Refer to Error Log Settings on page 21 for details on the PC Setup for the error log. Clearing the Error Log

8-7

To clear the entire error log, turn ON SR 25214 from a peripheral device. (After the error log has been cleared, SR 25214 will turn OFF again automatically.)

Host Link Errors These error codes are received as the response code (end code) when a command received by the PC from a host computer cannot be processed. The error code format is as shown below. @

X

X

Node no.

X

X

X

X

Header code End code

X

X

FCS

↵

Terminator

The header code will vary according to the command. Some commands (composite commands) contain a subcode.

432

Page 450

Section

Host Link Errors End Contents code 00 Normal completion

Probable cause ---

8-7

Corrective measures --Check the relation between the command and the PC mode.

01

Not executable in RUN mode

The command that was sent cannot be executed when the PC is in RUN mode.

02

Not executable in MONITOR mode

The command that was sent cannot be executed when the PC is in MONITOR mode.

04

Address over (CPM1/CPM1A/SRM1 PCs) Not executable in PROGRAM mode

The user program area’s highest address was exceeded. The command that was sent cannot be executed when the PC is in PROGRAM mode.

Check the program.

13

FCS error

The FCS is wrong. Either the FCS calculation is mistaken or there is adverse influence from noise.

Check the FCS calculation method. If there was influence from noise, transfer the command again.

14

Format error

The command format is wrong.

15

Entry number data error

16

Command not supported

The areas for reading and writing are wrong. The specified command does not exist in the specified address. (Reading the SV, etc.)

Check the format and transfer the command again. Correct the areas and transfer the command again. Check the address and instruction.

18

Frame length error

19

Not executable

23

User memory write-protected

0B

A3

Aborted due to FCS error in transmit data A4 Aborted due to format error in transmit data A5 Aborted due to entry number data error in transmit data A8 Aborted due to frame length error in transmit data Other ---

Power Interruptions

The maximum frame length was exceeded. Items to read not registered for composite command (QQ). CQM1 PCs: Pin 1 on the CQM1 DIP switch is ON. CPM1/CPM1A/SRM1 PCs: The memory is write-protected in the PC Setup. The error was generated while a command extending over more than one frame was being executed.

This code is not presently being used.

Divide the command into multiple frames. Execute QQ to register items to read before attempting batch read. CQM1 PCs: Turn OFF pin 1. CPM1/CPM1A/SRM1 PCs: Change the setting in the PC Setup (DM 6602).

Check for corrupted frames, correct if necessary, and try the transfer again.

Note: The data up to that point has already been written to the appropriate area of the CPU Unit.

Influence from noise was received.

Transfer the command again.

The following responses may be received from the CQM1 if a power interruption occurs, including momentary interruptions. If any of these responses are received during or after a power interruption, repeat the command. Undefined Command Response @00IC4A*↵ No Response If no response is received, abort the last command and resend.

433

Page 451

Section

Troubleshooting Flowcharts

8-8

8-8

Troubleshooting Flowcharts

8-8-1 CPM1 Flowcharts Refer to 5-6 Troubleshooting Flowcharts in the CPM1 Operation Manual.

8-8-2 CPM1A Flowcharts Refer to 5-6 Troubleshooting Flowcharts in the CPM1A Operation Manual.

8-8-3 SRM1 Flowcharts Refer to 5-6 Troubleshooting Flowcharts in the SRM1 Operation Manual.

8-8-4 CQM1 Flowcharts Use the following flowcharts to troubleshoot errors that occur during CQM1 operation. Main Check

Error

Power indicator lit?

Not lit

Check power supply. (See page 435.)

Lit

RUN indicator lit?

Not lit

Check for fatal errors. (See page 436.)

Lit

ERR/ALM indicator flashing?

Flashing

Check for non-fatal errors. (See page 437.)

Not lit

Is I/O sequence normal?

Not normal

Check I/O. (See page 438.)

Normal

Operating environment normal?

Not normal

Check operating environment. (See page 440.)

Normal Replace the CPU Unit.

Note Always turn off the power to the PC before replacing Units, batteries, wiring, or cables.

434

Page 452

Section

Troubleshooting Flowcharts

8-8

Power Supply Check Power indicator not lit.

Is power being supplied?

Connect power supply.

No

Yes

Not lit

Is voltage adequate? (See note.)

No

Is Power indicator lit?

Lit

Set supply voltage within acceptable limits.

Yes

Are there any loose terminal screws or broken wires?

No

Is Power indicator lit?

Yes

Tighten screws or replace wires.

Yes

No Not lit

Replace the Power Supply Unit.

Is Power indicator lit?

Lit

End

Note The allowable voltage ranges for the CQM1 are as shown below. CQM1-PA203/PA206: 85 to 264 VAC CQM1-PD026: 20 to 28 VDC

435

Page 453

Section

Troubleshooting Flowcharts Fatal Error Check

8-8

The following flowchart can be used to troubleshoot fatal errors that occur while the Power indicator is lit. RUN indicator not lit.

No

Is the ERR/ALM indicator lit? Yes Yes Determine the cause of the error with a Peripheral Device.

Is PC mode displayed on Peripheral Device?

Is PC mode displayed on Peripheral Device?

No

No

Correct the power supply.

Yes

Is a fatal error displayed?

Yes

No

Identify the error, eliminate its cause, and clear the error.

Switch to RUN or MONITOR mode.

Is the RUN indicator lit?

No

Yes End

436

Replace the CPU Unit.

Page 454

Section

Troubleshooting Flowcharts Non-fatal Error Check

8-8

Although the PC will continue operating during non-fatal errors, the cause of the error should be determined and removed as quickly as possible to ensure proper operation. It may to necessary to stop PC operation to remove certain non-fatal errors. ERR/ALM indicator flashing.

Determine the cause of the error with a Peripheral Device.

Is a non-fatal error indicated?

Yes

No

Is the ERR/ALM indicator flashing?

Identify the error (See page 427.), eliminate its cause, and clear the error.

Flashing

Not lit

End

Replace the CPU Unit.

437

Page 455

Section

Troubleshooting Flowcharts I/O Check

8-8

The I/O check flowchart is based on the following ladder diagram section. (LS1) 00002

(LS2) 00003 10500

SOL1

10500

SOL1 malfunction.

Start (See note) No

Is the IR 10500 output indicator operating normally? Yes Check the voltage at the IR 10500 terminals.

Wire correctly.

Replace terminal connector.

No Operation O.K.?

No

Yes

Monitor the ON/OFF status of IR 10500 with a Peripheral Device.

No Is terminal block making proper contact?

Is output wiring correct?

Yes Operation O.K.? Yes

Yes

No

A To next page

Disconnect the external wires and check the conductivity of each wire.

Yes

Check output device SOL1.

Operation O.K.?

No

Replace the Output Unit.

Note The CPM1 PC doesn’t have the IR 10500 output indicator. Substitute with one from IR 01000 to IR 01915.

438

Page 456

Section

Troubleshooting Flowcharts

A

Are the IR 00002 and IR 00003 input indicators operating normally?

From previous page

8-8

No

Yes

Check the voltage at the IR 00002 and IR 00003 terminals.

Check the voltage at the IR 00002 and IR 00003 terminals.

Yes

Are the terminal screws loose? No

Operation O.K.?

Operation O.K.?

No

No

Yes

Is terminal block making proper contact? No

Yes No

Yes

Check operation by using a dummy input signal to turn the input ON and OFF.

Is input wiring correct? No

Wire correctly. No

Yes

Tighten the terminal screws

Replace terminal connector.

Operation O.K.? Yes

Replace the Input Unit.

Check input devices LS1 and LS2.

Return to “start.”

Replace the Output Unit.

439

Page 457

Section

Troubleshooting Flowcharts Environmental Conditions Check Environmental conditions check

No

Consider using a fan or cooler.

Is the ambient temperature above 0°C? Yes

No

Consider using a heater.

Is the ambient humidity between 10% and 90%?

No

Consider using an air conditioner.

Is the ambient temperature below 55°C? Yes

Yes

Is noise being controlled?

No

Yes

Is the installation environment okay? Yes End.

440

No

Install surge protectors or other noise-reducing equipment at noise sources.

Consider constructing an instrument panel or cabinet.

8-8