For the Omron CQM1-CPU21
Page 449
Section
Host Link Errors
8-7
Error Log Storage Methods
The error log storage method is set in the PC Setup (DM 6655). Set any of the following methods.
1, 2, 3...
1. You can store the most recent 7 error log records and discard older records. This is achieved by shifting the records as shown below so that the oldest record (record 0) is lost whenever a new record is generated. Lost Error log record 0 Error log record 1 All records shifted Error log record 5 Error log record 6
New record added
2. You can store only the first 7 error log records, and ignore any subsequent errors beyond those 7. 3. You can disable the log so that no records are stored. The default setting is the first method. Refer to Error Log Settings on page 21 for details on the PC Setup for the error log. Clearing the Error Log
8-7
To clear the entire error log, turn ON SR 25214 from a peripheral device. (After the error log has been cleared, SR 25214 will turn OFF again automatically.)
Host Link Errors These error codes are received as the response code (end code) when a command received by the PC from a host computer cannot be processed. The error code format is as shown below. @
X
X
Node no.
X
X
X
X
Header code End code
X
X
FCS
↵
Terminator
The header code will vary according to the command. Some commands (composite commands) contain a subcode.
432
Page 450
Section
Host Link Errors End Contents code 00 Normal completion
Probable cause ---
8-7
Corrective measures --Check the relation between the command and the PC mode.
01
Not executable in RUN mode
The command that was sent cannot be executed when the PC is in RUN mode.
02
Not executable in MONITOR mode
The command that was sent cannot be executed when the PC is in MONITOR mode.
04
Address over (CPM1/CPM1A/SRM1 PCs) Not executable in PROGRAM mode
The user program area’s highest address was exceeded. The command that was sent cannot be executed when the PC is in PROGRAM mode.
Check the program.
13
FCS error
The FCS is wrong. Either the FCS calculation is mistaken or there is adverse influence from noise.
Check the FCS calculation method. If there was influence from noise, transfer the command again.
14
Format error
The command format is wrong.
15
Entry number data error
16
Command not supported
The areas for reading and writing are wrong. The specified command does not exist in the specified address. (Reading the SV, etc.)
Check the format and transfer the command again. Correct the areas and transfer the command again. Check the address and instruction.
18
Frame length error
19
Not executable
23
User memory write-protected
0B
A3
Aborted due to FCS error in transmit data A4 Aborted due to format error in transmit data A5 Aborted due to entry number data error in transmit data A8 Aborted due to frame length error in transmit data Other ---
Power Interruptions
The maximum frame length was exceeded. Items to read not registered for composite command (QQ). CQM1 PCs: Pin 1 on the CQM1 DIP switch is ON. CPM1/CPM1A/SRM1 PCs: The memory is write-protected in the PC Setup. The error was generated while a command extending over more than one frame was being executed.
This code is not presently being used.
Divide the command into multiple frames. Execute QQ to register items to read before attempting batch read. CQM1 PCs: Turn OFF pin 1. CPM1/CPM1A/SRM1 PCs: Change the setting in the PC Setup (DM 6602).
Check for corrupted frames, correct if necessary, and try the transfer again.
Note: The data up to that point has already been written to the appropriate area of the CPU Unit.
Influence from noise was received.
Transfer the command again.
The following responses may be received from the CQM1 if a power interruption occurs, including momentary interruptions. If any of these responses are received during or after a power interruption, repeat the command. Undefined Command Response @00IC4A*↵ No Response If no response is received, abort the last command and resend.
433
Page 451
Section
Troubleshooting Flowcharts
8-8
8-8
Troubleshooting Flowcharts
8-8-1 CPM1 Flowcharts Refer to 5-6 Troubleshooting Flowcharts in the CPM1 Operation Manual.
8-8-2 CPM1A Flowcharts Refer to 5-6 Troubleshooting Flowcharts in the CPM1A Operation Manual.
8-8-3 SRM1 Flowcharts Refer to 5-6 Troubleshooting Flowcharts in the SRM1 Operation Manual.
8-8-4 CQM1 Flowcharts Use the following flowcharts to troubleshoot errors that occur during CQM1 operation. Main Check
Error
Power indicator lit?
Not lit
Check power supply. (See page 435.)
Lit
RUN indicator lit?
Not lit
Check for fatal errors. (See page 436.)
Lit
ERR/ALM indicator flashing?
Flashing
Check for non-fatal errors. (See page 437.)
Not lit
Is I/O sequence normal?
Not normal
Check I/O. (See page 438.)
Normal
Operating environment normal?
Not normal
Check operating environment. (See page 440.)
Normal Replace the CPU Unit.
Note Always turn off the power to the PC before replacing Units, batteries, wiring, or cables.
434
Page 452
Section
Troubleshooting Flowcharts
8-8
Power Supply Check Power indicator not lit.
Is power being supplied?
Connect power supply.
No
Yes
Not lit
Is voltage adequate? (See note.)
No
Is Power indicator lit?
Lit
Set supply voltage within acceptable limits.
Yes
Are there any loose terminal screws or broken wires?
No
Is Power indicator lit?
Yes
Tighten screws or replace wires.
Yes
No Not lit
Replace the Power Supply Unit.
Is Power indicator lit?
Lit
End
Note The allowable voltage ranges for the CQM1 are as shown below. CQM1-PA203/PA206: 85 to 264 VAC CQM1-PD026: 20 to 28 VDC
435
Page 453
Section
Troubleshooting Flowcharts Fatal Error Check
8-8
The following flowchart can be used to troubleshoot fatal errors that occur while the Power indicator is lit. RUN indicator not lit.
No
Is the ERR/ALM indicator lit? Yes Yes Determine the cause of the error with a Peripheral Device.
Is PC mode displayed on Peripheral Device?
Is PC mode displayed on Peripheral Device?
No
No
Correct the power supply.
Yes
Is a fatal error displayed?
Yes
No
Identify the error, eliminate its cause, and clear the error.
Switch to RUN or MONITOR mode.
Is the RUN indicator lit?
No
Yes End
436
Replace the CPU Unit.
Page 454
Section
Troubleshooting Flowcharts Non-fatal Error Check
8-8
Although the PC will continue operating during non-fatal errors, the cause of the error should be determined and removed as quickly as possible to ensure proper operation. It may to necessary to stop PC operation to remove certain non-fatal errors. ERR/ALM indicator flashing.
Determine the cause of the error with a Peripheral Device.
Is a non-fatal error indicated?
Yes
No
Is the ERR/ALM indicator flashing?
Identify the error (See page 427.), eliminate its cause, and clear the error.
Flashing
Not lit
End
Replace the CPU Unit.
437
Page 455
Section
Troubleshooting Flowcharts I/O Check
8-8
The I/O check flowchart is based on the following ladder diagram section. (LS1) 00002
(LS2) 00003 10500
SOL1
10500
SOL1 malfunction.
Start (See note) No
Is the IR 10500 output indicator operating normally? Yes Check the voltage at the IR 10500 terminals.
Wire correctly.
Replace terminal connector.
No Operation O.K.?
No
Yes
Monitor the ON/OFF status of IR 10500 with a Peripheral Device.
No Is terminal block making proper contact?
Is output wiring correct?
Yes Operation O.K.? Yes
Yes
No
A To next page
Disconnect the external wires and check the conductivity of each wire.
Yes
Check output device SOL1.
Operation O.K.?
No
Replace the Output Unit.
Note The CPM1 PC doesn’t have the IR 10500 output indicator. Substitute with one from IR 01000 to IR 01915.
438
Page 456
Section
Troubleshooting Flowcharts
A
Are the IR 00002 and IR 00003 input indicators operating normally?
From previous page
8-8
No
Yes
Check the voltage at the IR 00002 and IR 00003 terminals.
Check the voltage at the IR 00002 and IR 00003 terminals.
Yes
Are the terminal screws loose? No
Operation O.K.?
Operation O.K.?
No
No
Yes
Is terminal block making proper contact? No
Yes No
Yes
Check operation by using a dummy input signal to turn the input ON and OFF.
Is input wiring correct? No
Wire correctly. No
Yes
Tighten the terminal screws
Replace terminal connector.
Operation O.K.? Yes
Replace the Input Unit.
Check input devices LS1 and LS2.
Return to “start.”
Replace the Output Unit.
439
Page 457
Section
Troubleshooting Flowcharts Environmental Conditions Check Environmental conditions check
No
Consider using a fan or cooler.
Is the ambient temperature above 0°C? Yes
No
Consider using a heater.
Is the ambient humidity between 10% and 90%?
No
Consider using an air conditioner.
Is the ambient temperature below 55°C? Yes
Yes
Is noise being controlled?
No
Yes
Is the installation environment okay? Yes End.
440
No
Install surge protectors or other noise-reducing equipment at noise sources.
Consider constructing an instrument panel or cabinet.
8-8