The text of a spec sheet · part 1 of 3
Digital Process Controller Series E5K: Advanced Process Digital Controllers with Fuzzy Logic, pages 1 to 9
Pages 1 to 9 of 27
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron E5CK
Page 1
Digital Process Controller Series
E5†K
Advanced Process Digital Controllers with Fuzzy Logic Field configurable outputs, options. 100 ms sampling (for analog input). D Advanced PID, or fuzzy self-tuning. D Conforms to UL, CSA and CE standards. D Water-resistant front panel meets IP66/NEMA 4X. D Remote set point with optional event input board. D Set point ramp. D Serial communications available. D Front panel programming. D Heat only or heat/cool control. D Auxiliary outputs (SPST) standard; two for E5AK/E5EK, one for E5CK. D 3-year warranty. D D
Ordering Information Note: Order Control Output Boards and Option Boards separately below. Description Standard model Position-proportional model (See Note 3) Standard model Position-proportional model (See Note 3) Standard model Non-standard model with built-in quick auto-tune button (See Nomenclature section for details)
DIN size
Supply voltage
Model
1/4 DIN (96 x 96 mm)
100 to 240 VAC
E5AK-AA2-500
100 to 240 VAC
E5AK-PRR2-500
1/8 DIN (48 x 96 mm)
100 to 240 VAC
E5EK-AA2-500
100 to 240 VAC
E5EK-PRR2-500
1/16 DIN (48 x 48 mm)
100 to 240 VAC
E5CK-AA1-500
100 to 240 VAC
E5CK-AA1-302
Note: 1. When using the heater burnout alarm function with a standard model, the Linear Output Module cannot be used for the control outputs (heat). The Digital Controller provides transfer outputs at 4 to 20 mA for the PV and other values and control outputs at 4 to 20 mA for the current outputs. 2. E5EK-PRR2/E5AK-PRR2 controllers are supplied with dedicated relay output. 3. Position-proportional models are intended for motorized valves (not 4-20 mA modulating valves). These use two relays (“open” and “close”) which will turn a motor clockwise or counter-clockwise, thus opening or closing the valve. 4. Part numbers ending in --500 include a Finger Safe cover.
1
Digital Process Controller E5†K
Page 2
J Optional Output Boards Description
Specifications
Compatible controller
Max. quantity
Model
Relay
SPST, 5 A, 250 VAC
E5AK/E5EK
2
E53-R
SSR (solid state relay)
1 A, 75 to 250 VAC
E5AK/E5EK
2
E53-S
Voltage pulse
NPN, 12 VDC
E5AK/E5EK
2
E53-Q
NPN, 24 VDC
E5AK/E5EK
2
E53-Q3
PNP, 24 VDC
E5AK/E5EK
2
E53-Q4
4 to 20 mA
E5AK/E5EK
2
E53-C3
0 to 20 mA
E5AK/E5EK
2
E53-C3D
0 to 10 VDC
E5AK/E5EK
2
E53-V34
0 to 5 VDC
E5AK/E5EK
2
E53-V35
Relay/Relay
SPST/SPST, 5 A, 250 VAC
E5CK
1
E53-R4R4
Relay/Pulse
SPST, 5 A/NPN, 24 VDC
E5CK
1
E53-Q4R4
SPST, 5 A/PNP, 24 VDC
E5CK
1
E53-Q4HR4
SPST, 5 A/4 to 20 mA
E5CK
1
E53-C4R4
SPST, 5 A/0 to 20 mA
E5CK
1
E53-C4DR4
Relay/Linear voltage
SPST, 5 A/0 to 10 VDC
E5CK
1
E53-V44R4
Pulse/Pulse
NPN/NPN, 24 VDC
E5CK
1
E53-Q4Q4
PNP/PNP, 24 VDC
E5CK
1
E53-Q4HQ4H
RS-232C
E5AK/E5EK
3/1
E53-AK01
RS-232C
E5CK
1
E53-CK01
RS-422
E5AK/E5EK
3/1
E53-AK02
RS-485
E5AK/E5EK
3/1
E53-AK03
E5CK
1
E53-CK03
For remote set point
E5AK/E5EK
3/1
E53-AKB
For remote set point
E5CK
1
E53-CKB
4 to 20 mA
E5AK/E5EK
3/1
E53-AKF
4 to 20 mA
E5CK
1
E53-CKF
Linear current Linear voltage
Relay/Linear current
Computer communications
Event input Transfer output
Note: If the control period is less than 5 seconds, use an SSR (solid state relay) or pulse voltage output.
J Accessories (Order Separately) Description
Specifications
Current transformer; order only if using heater burnout alarm function
50 A load, 5.8 mm hole dia.
E5AK/E5EK
1
E54-CT1
120 A load, 12 mm hole dia.
E5AK/E5EK
1
E54-CT3
Terminal cover (supplied with Standard models)
Provides finger protection from terminals (VDE0106 part 100)
E5AK
1
E53-COV0809
E5CK
1
E53-COV07
E5EK
1
E53-COV08
For setup and monitoring; requires optional computer communications board
All
1
Thermo Tools (See Note)
Software
Note: Contact Omron for current version information.
2
Digital Process Controller E5†K
Compatible controller
Max. quantity
Model
Page 3
Input Types (selectable with input jumper connector) Thermocouple Input (field selectable) (See Notes) Range
K1
K2
J1
J2
T
E
L1
L2
U
N
R
S
B
W
PLII
°C
--200 to 1,300
0.0 to 500.0
--100 to 850
0.0 to 400.0
--199.9 to 400.0
0 to 600
--100 to 850
0.0 to 400.0
--199.9 to 400.0
--200 to 1,300
0 to 1,700
0 to 1,700
100 to 1,800
0 to 2,300
0 to 1,300
°F
--300 to 2,300
0.0 to 900.0
--100 to 1,500
0.0 to 750.0
--199.9 to 700.0
0 to 1,100
--100 to 1,500
0.0 to 750.0
--199.9 to 700.0
--300 to 2,300
0 to 3,000
0 to 3,000
300 to 3,200
0 to 4,100
0 to 2,300
Note: 1. Setting number is factory-set to 2 (K1). 2. Thermocouple W is W/Re5-26 (tungsten rhenium 5, tungsten rhenium 26). Platinum Resistance Thermometer (RTD’s) JPt100
Input (field selectable) Range
Pt100
°C
--199.9 to 650.0
--199.9 to 650.0
°F
--199.9 to 999.9
--199.9 to 999.9
Current/Voltage Input (field selectable)
Current input 4 to 20 mA
0 to 20 mA
Voltage input 1 to 5 V
0 to 5 V
0 to 10 V
Note: When a current/voltage input is selected, the decimal point is fully adjustable.
Digital Process Controller E5†K
3
Page 4
Specifications J Ratings Model
E5jK Standard
Supply voltage
100--240 VAC, 50/60 Hz 85% to 110% of rated supply voltage
Operating voltage range Power consumption
Input
E5AK
16 VA
E5EK
15 VA
E5CK
10 VA (at 100 VAC) 14 VA (at 240 VAC)
Thermocouple
K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer (RTD)
JPt100, Pt100
Current input
4 to 20 mA, 0 to 20 mA
Voltage input
1 to 5 V, 0 to 5 V, 0 to 10 V
Mean Time Between Failure
15.4 years (135,000 hours)
Control output (See Note 1)
SPST, 3 A at 250 VAC (resistive load) Mechanical life expectancy: 10,000,000 operations min. Electrical life expectancy: 100,000 operations min.
Auxiliary output
Relay
Voltage (pulse)
NPN
20 mA at 12/24 VDC (with short-circuit protection)
PNP
20 mA at 24 VDC (with short-circuit protection)
Linear voltage
0 to 10 VDC
Permissible load impedance: 1 kΩ min. Resolution: Approximately 2600 steps
Linear current
4 to 20 mA
Permissible load impedance: 500 Ω max. Resolution: Approximately 2600 steps
0 to 20 mA
Permissible load impedance: 500 Ω max. Resolution: Approximately 2600 steps
E5AK
3 A at 250 VAC (resistive load)
E5EK
3 A at 250 VAC (resistive load)
E5CK
1A at 250 VAC (resistive load)
SPST-NO
Control method (See Note 2)
ON/OFF, Advanced PID Control (with auto-tuning) or Self-tuning
Setting method
Digital setting using front panel keys or communications features
Indication method -- 7-seg. digital display and LEDs
E5AK: PV = 15 mm, SP = 10.5 mm E5EK: PV = 14 mm, SP = 9.5 mm E5CK: PV = 12 mm, SP = 8 mm
Potentiometer for valve positioning (for E5AK-PRR and E5EK-PRR only)
100 Ω to 2.5 kΩ
Event input
Contact input
ON
1 kΩ max.
OFF
100 kΩ min.
No-contact input
ON residual voltage: 1.5 V max.
OFF leakage current: 0.1 mA max. 4 to 20 mA, permissible load impedance: 600 Ω max., resolution: Approximately 2600 steps
Transmission output Remote SP input (for E5AK and E5EK only)
Current input
4 to 20 mA (Input impedance: 150 Ω)
Current Transformer input (for E5AK and E5EK only)
Connect only an Omron Current Transformer (E54-CT1 or E54-CT3)
Other functions
Standard
Manual output, heating/cooling control, SP limiter, loop burnout alarm, SP ramp, MV limiter, MV change rate limiter, input digital filter, input shift, run/stop, protect functions
Option
Multiple SP, run/stop selection, transfer output functions, auto/manual Communications (RS-232C, RS-422, or RS-485), Loop Break Alarm, and Transfer Output.
Standards
UL
File No.: E68481
CSA
File No.: LR59623
CE
File No.: EN50081-2; EN50082-2; IEC 1010-1
Note: 1. All control outputs are insulated from the input circuit. 2. Fuzzy self-tuning is available only when using the Digital Controller in standard control operation with temperature input.
4
Digital Process Controller E5†K
Page 5
J Characteristics Indication accuracy (See Note)
Thermocouple: ±0.3% of indication value or ±1°C, whichever is greater, ±1 digit max. Platinum resistance thermometer: ±0.2% of indication value or ±0.8°C, whichever is greater, ±1 digit max. Analog input: ±0.2% (of indication value) ±1 digit max.
Hysteresis
0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
0.1% to 999.9% FS (in units of 0.1% FS)
Integral (reset) time (I)
0 to 3,999 s (in units of 1 s)
Derivative (rate) time (D)
0 to 3,999 s (in units of 1 s)
Control period
1 to 99 s (in units of 1 s)
Manual reset value
0.0% to 100.0% (in units of 0.1%) --1,999 to 9,999 or --199.9 or 999.9 (decimal point position dependent on input type)
Alarm setting range Sampling period
Temperature input
250 ms scan rate
Analog input
100 ms scan rate 200 MΩ min. (at 500 VDC)
Insulation resistance
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Dielectric strength Malfunction
10 to 55 Hz, 10 m/s2 (approx. 1G) for 10 min each in X, Y, and Z directions
Mechanical
10 to 55 Hz, 20 m/s2 (approx. 2G) for 2 hrs each in X, Y, and Z directions
Malfunction
200 m/s2 min. (approx. 20G), 3 times each in 6 directions (100 m/s2 (approx. 10G) applied to the relay)
Mechanical
300 m/s2 min. (approx. 30G), 3 times each in 6 directions
Operating
--10°C to 55°C (14°F to 131°F ) with no icing; with 3-year warranty period: --10°C to 50°C (14°F to 122°F )
Storage
--25°C to 65°C (--13°F to 149°F ) with no icing
Ambient humidity
Operating
35% to 85% RH
Enclosure ratings
Front panel
NEMA 4X for indoor use (equivalent to IP66)
Rear case
IEC standard IP20
Terminals
IEC standard IP00
Vibration resistance Shock resistance
Ambient temperature
Non-volatile memory (number of writings: 100,000 operations)
Memory protection Weight
EMC
E5AK
Approx. 450 g
E5EK
Approx. 320 g
Mounting bracket
Approx. 65 g
E5CK
Approx. 170 g
Adapter
Approx. 10 g Emission Enclosure: Emission AC Mains: Immunity ESD: Immunity RF-interference:
Immunity Conducted Disturbance: Immunity Burst: Standards -- Approvals
EN55011 Group 1 class A EN55011 Group 1 class A EN61000-4-2: 4 kV contact discharge (level 2) 8 kV air discharge (level 3) ENV50140: 10 V/m (amplitude modulated, 80 MHz to 1 GHz) (level 3) 10 V/m (pulse modulated, 900 MHz) ENV50141: 10 V (0.15 to 80 MHz) (level 3) EN61000-4-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4)
UL1092, CSA22.2 No. 14, CSA22.2 No. 1010-1 Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1) Conforms to VDE0106/part 100 (Finger Protection)
Note: Indication Accuracy -Of the K1, T, and N thermocouples at a temperature of -100°C or less: ±2°C ±1 digit maximum. Of the U, L1, and L2 thermocouples at any temperature: ±2°C ±1 digit maximum. Of the B thermocouple at a temperature of 400°C or less: unrestricted. Of the R and S thermocouples at a temperature of 200°C or less: ±3°C ±1 digit maximum. Of the W thermocouple at any temperature: ±0.3% of the indicated value or ±3°C, (whichever is greater) ±1 digit maximum. Of the PLII thermocouple at any temperature: ±0.3% or ±2°C, whichever is greater ±1 digit maximum.
Digital Process Controller E5†K
5
Page 6
J Option Board Ratings and Characteristics Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Event inputs
No-contact input: ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max. Communications
Interface
RS-232C and RS-485; RS-422 for E5AK and E5EK only
Transmission method
Half-duplex
Synchronization method
Start-stop synchronization (asynchronous method)
Baud rate
1.2/2.4/4.8/9.6/19.2 kbps
Transfer output
4 to 20 mA: Permissible load impedance: E5AK and E5EK = 600 Ω max. E5CK = 500 Ω max. Resolution: E5AK and E5EK = approx. 2,600 steps E5CK = approx. 2,600 steps RS-232C Peer-to-peer only; maximum cable length = 15 m (49.2 feet) RS-422 and RS-485 32 controller maximum to host computer; maximum cable length = 500 m (1640 feet)
J Current Transformer Ratings Part number
E54-CT1
E54-CT3
Max. continuous heater current
50 amps
120 amps (See Note 1)
Dielectric strength
1,000 VAC (for 1 min)
Vibration resistance
50 Hz, 98 m/s2 (10G)
Weight
Approx. 11.5 g
Approx. 50 g
Accessories
----
Armature: 2; Plug: 2
Note: 1. Use within the max. heater current rating of controller table shown below.
J Heater Burnout Alarm Max. heater current
Single-phase 50 A AC
Heater current value display accuracy
±5% FS ±1 digit max.
Heater burnout alarm setting range
0.1 to 49.9 A (in units of 0.1 A) (See Note 1)
Min. detection ON time
190 ms (See Note 2)
Note: 1. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A. 2. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less than 190 ms.
6
Digital Process Controller E5†K
Page 7
Nomenclature J E5AK Operation Indicators No. 1 display Operation Indicators
No. 2 display
• OUT1
Lit when control output 1 turns ON.
• OUT2
Lit when control output 2 turns ON.
• SUB1 A/M Key Display Key
Lit when the output function assigned to auxiliary output 1 turns ON.
Up Key/Down Key
• SUB2 (for E5AK and E5EK only)
Lit when the output function assigned to auxiliary output 2 turns ON.
• MANU
J E5EK
Lit when the manual operation mode is being used.
• STOP
Lit when control operation has been stopped.
No. 1 display No. 2 display Operation Indicators
Lit during remote communications operation.
• AT
Flashes during auto-tuning. Auto-tuning is completed when this LED stops flashing.
Display Key A/M Key
• RMT
Up Key/Down Key
• RSP (for E5AK and E5EK only) Lit during remote SP operation.
• Bar Graph (for E5AK only)
J E5CK No. 1 display
Operation Indicators A/M Key Display Key
No. 2 display
Up Key/Down Key
J E5CK-302
AT Key Display Key
No. 1 Display Displays the process value or parameter symbols. No. 2 Display Displays the set point, set point during SP ramp, manipulated variable, or parameter settings. A/M Key Press to select the auto operation or manual operation. Up Key/Down Key Press to increase or decrease the value on the No.2 display.
No. 1 display
Operation Indicators
On a standard model (E5AK-AA2), this bar graph indicates the manipulated variable (heat) in 10% increments per single segment. On a position-proportional model (E5AK-PRR2), this bar graph indicates the valve opening in 10% increments per single segment.
No. 2 display
Up Key/Down Key
Display Key Press quickly (for less than 1 s) to shift the display to the next parameter. When this key is pressed for 1 s or more, the menu screen will be displayed in any case.
• AT
Press key for automatic tuning.
• A/M
This feature is located in level one. (Replaced AT feature in level one).
Digital Process Controller E5†K
7
Page 8
Operation J Operating Parameters Mode Selection Press the Display Key for 1 sec. min. to switch to modes other than the manual or protect mode. The figure below (Menu Display) shows all modes in the order that they are displayed. Some parameters are not displayed, depending on the protect mode setting and the option boards used.
Menu Display
To Access Protect Mode Press and hold the A/M Key and the Display Key for more than 1 second. To Return to the Main PV/SP Display from the Protect Mode Press and hold the A/M Key and the Display Key for more than 1 second. To Access Manual Mode Press and hold the A/M Key for more than 1 second.
1 second min.
Level 0 mode
To switch parameters within a mode, use the Display Key. Press the display key for less than one second to move between parameters.
Level 1 mode
Note:
1 second min.
1. In Level 0 mode, Level 1 mode, and Level 2 mode: The controller will maintain control of the process.
Level 2 mode
Setup mode
Expansion mode
2. In Setup mode, Expansion mode, Option mode, and Calibration mode: Control of the process is not maintained. The outputs are inactive.
Option mode
3. Option Mode will be accessible only when an option board is installed in the controller.
Calibration mode
J Parameters And Menus -- For Setting The Controller Protect Mode
Limits use of the menu and A/M Keys. The protect function prevents unwanted modification of parameters and can also be used to prevent switching between the auto and manual operation.
Manual Mode
Sets the controller to manual operation mode. You can only manually adjust the manipulated variable (MV) in this mode.
Level 0 Mode
For normal operation. Change: the set point during operation, and start or stop Controller operation; and, (only in this mode) monitor the process value, ramp SP, and manipulated variable.
Level 1 Mode
For adjusting primary control parameters. Execute: AT (auto-tuning); set alarm values; set the control period; and, set PID parameters.
Level 2 Mode
For adjusting secondary control parameters. Set parameters for: limiting the manipulated variable and set point; switch between the remote and local modes; set the loop break alarm (LBA), alarm hysteresis, and the digital filter value of inputs.
Setup Mode
For setting the basic specifications. Set parameters for: input type, scaling, output assignments and direct/reverse operation.
Expansion Mode
For setting expanded functions. Set: ST (self-tuning), SP setting limiter. Select: advanced PID or ON/OFF control. Specify the standby sequence resetting method. Initialize parameters; and, set the time for automatic return to the monitoring display.
Option Mode
For setting option functions. Set: the communications conditions; transfer: output and event input parameters to match the type of Option Board installed in the Controller. This mode will be accessible only when an option board is installed in the controller.
Calibration Mode For calibrating inputs and transfer output.
Calibrate the selected input type. Transfer output can be calibrated only when the Communications Unit (E53-CKF) has been installed in the Controller.
8
Digital Process Controller E5†K
Page 9
Dimensions Unit: mm (inch)
J E5AK 13.5 (0.53)
110 min.
100 (3.94)
91 (3.58) x 91 (3.58) 112 (4.41)
96 (3.78) x 96 (3.78)
Panel Cutouts
120 min.
Note: 1. Recommended panel thickness is 1 to 8 mm. 2. Maintain the specified vertical and horizontal mounting space between each Unit. Units must not be closely mounted vertically or horizontally.
J E5EK 13.5 (0.53)
48 (1.89)
Panel Cutouts
91 (3.58) 112 (4.41)
96 (3.78)
Note:
60 min.
100 (3.94)
120 min.
1. Recommended panel thickness is 1 to 8 mm. 2. Maintain the specified vertical and horizontal mounting space between each Unit. Units must not be closely mounted vertically or horizontally.
J E5CK 13 (0.51)
100 (3.94)
48 (1.89)
58 (2.28) 53 (2.09) x 53 (2.09)
Panel Cutouts
44.8 (1.76) x 44.8 (1.76)
65 min.
Note: 60 min.
45 +0.6 0
1. Recommended panel thickness is 1 to 5 mm. 2. Maintain the specified vertical and horizontal mounting space between each Unit. Units must not be closely mounted, either vertically or horizontally.
45 +0.6 0
Digital Process Controller E5†K
9