The text of a spec sheet · part 2 of 3
Digital Process Controller Series E5K: Advanced Process Digital Controllers with Fuzzy Logic, pages 10 to 18
Pages 10 to 18 of 27
The original document is the PDF (2.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron E5CK
Page 10
J E5CK-302 The E5CK-302 model has the same dimension and cutouts as the E5CK.
J Accessories (Order Separately) Terminal Cover for E5EK
Terminal Cover for E5AK E53-COV0809
22.05 (0.87)
43.2 (1.70)
89 (3.50)
3
3 3
1.5
3 1.5
89 (3.50)
89 (3.50)
43.2 (1.70)
E53-COV08
Terminal Cover for E5CK E53-COV07 44.3 (1.74)
44.3 (1.74)
Current Transformer (E5AK and E5EK only for Heater Burnout Alarm) E54-CT1
E54-CT3 21 (0.83) 15 (0.59)
5.8 dia. (0.23)
2.8 (0.11)
3 25 (0.98) (0.12)
30 (1.18) 7.5 (0.30)
2.36 dia. 12 dia. (0.47)
40 (1.57) x 40 (1.57) 40 (1.57) Two, M3 (depth: 4)
10 (0.39)
15 30 (1.18)
10
Digital Process Controller E5†K
30 (1.18)
Page 11
Installation J Remove Controller From Rear Housing E5AK and E5EK To pull out the internal mechanism from the housing, use a Phillips screwdriver matching the screw on the lower part of the front panel. 1. Turn the screw counterclockwise while pressing the hook on the upper part of the front panel. 2. Carefully pull out the internal mechanism while holding the left and right sides of the front panel. Hook
E5CK Terminals
First, while pressing the hooks on the left and right sides of the front panel, pull the internal mechanism from the housing.
Output Board Housing (case)
Input Type Jumper Connector Option Board
Front Panel
Digital Process Controller E5†K
11
Page 12
J Settings Note: Always turn off the power supply to the Digital Controller before changing any switch settings. On a standard model, set up the Output Modules for control outputs 1 and 2 before mounting the Controller. On a position-proportional model, the Relay Output Module is already set. Do not change that set-up parameter. Do not replace with other Output Modules.
Setting Up and Removing the Output Module Setting Up the Output Module
Removing the Output Module
When setting up the Output Modules, pull out the internal mechanism from the housing and insert the Output Modules into the sockets for control outputs 1 and 2.
To replace the Output Module, use a flat-blade screwdriver to push up the Output Module.
Setting Up the Option/Output Board E5AK 1. Remove the Power Board and Option Boards in the order shown in the following diagram.
Power board
12
2. Insert the Option Boards into the sockets for options 1 to 3. The following diagram shows the relationship between the Option Boards and mounting positions.
Option board 3. Mount the option boards and the power board in the order shown.
Digital Process Controller E5†K
Page 13
E5EK 1. Remove the Power Board in the order shown in the following diagram.
2. Insert the Option Board into the socket for option 1. The following diagram shows the relationship between the Option Board and mounting position.
Power board
3. Mount the option boards and the power board in the order shown.
E5CK
Set up the Option Board
1. Two rectangular holes are provided on the Power Board (right side of Controller). Fit the two protrusions of the output board into these two holes. 2. With the output board fitted into the Power Board, fit the output board into the connector on the control board (left side of Controller).
1. Place the bottom of the Controller facing up, fit the board horizontally into the connector on the power board (right side of controller). 2. With the Power Board connected, fit the board vertically into the connector on the control board (left side of Controller).
1 1 2 2
Digital Process Controller E5†K
13
Page 14
J Mounting Controller E5AK and E5EK 1. Insert the controller into the panel’s mounting hole at the position shown in the figure below. 2. Fit the mounting bracket (accessory) into the mounting slots on the top and bottom of the rear case.
E5CK 1. Insert the E5CK Controller into the cutout on the panel, as shown in the figure here. 2. Push the adapter along the Controller body from the terminals up to the panel, and fasten temporarily. 3. Tighten the two mounting screws on the adapter. When tightening screws, tighten the two screws alternately keeping the torque to approximately 0.29 to 0.39 N S m, or 3 to 4 kgf S cm. Adapter Panel Watertight gasket
14
Digital Process Controller E5†K
3. Tighten the mounting bracket screws on the upper and lower parts in small increments alternately and equally until the ratchet start to slide.
Page 15
J Mounting Terminal Cover E5AK and E5EK
E5CK
1. Fasten the terminals covers as follows by using the plastic pins. Plastic pins are provided with the terminal covers.
1. The E5CK-AA1-500 Controller is provided with a Terminal Cover (E53-COV07). Fasten the Terminal Cover as follows by using the plastic pin.
E5CK
E53--COV07
J Wiring Terminals for E5AK E5AK Terminal Arrangement AC100--240V~ 50/60 Hz OPTION 2
Wiring In the following wiring diagrams, the left side of the terminal numbers indicate the inside of the Controller. OPTION 1
Power Supply Input power to terminal numbers 9 and 10. Power specifications are as follows: 100 to 240 VAC, 50/60 Hz, approx. 16 VA
OPTION 3
SENSOR INPUT
TRSF: Transfer output EV1 to 4: Event input PTMR: Potentiometer RSP: Remote SP input
Digital Process Controller E5†K
15
Page 16
Wiring Terminals for E5EK
Power supply
E5EK Terminal Arrangement
Input power to terminal numbers 9 and 10. Power specifications are as follows: 100 to 240 VAC, 50/60 Hz, approx. 15 VA
AC100--240V~ 50/60 Hz OPTION 1
SENSOR INPUT
TRSF: EV1/2: PTMR: RSP:
Transfer output Event input Potentiometer Remote SP input
J Wiring Terminals for E5CK E5CK Terminal Arrangement
Wiring Precautions •
OUT1
• •
100--240VAC 5
SUB1
11
12
10
4
9
3
8
2
7
1
13
14
OUT2
To protect the Controller and its lines from external noise, use the wire ducts to separate input leads and power lines. Use solderless terminals when wiring the Controller. Tighten the terminal screws using a torque no greater than 0.78 N S m, or 8 kgf S cm max. DO NOT tighten the terminal screws too tightly.
Power Supply INPUT
6
OPTION
Input 100 to 240 VAC to terminal numbers 4 and 5. 5
11
12
4
9
3
8
2 1
16
Digital Process Controller E5†K
10
7 13
14
6
Page 17
J Input Wiring E5AK Connect the sensor input to terminal numbers 11 to 14 and 33 as follows according to the input type.
E5EK Connect the sensor input to terminal numbers 11 to 14 and 23 as follows according to the input type.
E5CK Connect the sensor input to terminal numbers 6 to 8 as indicated here, according to the input type. 5
11
12
10
4
9
3
8
2
7
1
13
14
+ Input type
6
8
8
7
7
6
6
Thermocouple
V
+
Platinum resistance thermometer (RTD)
8 7 6
Voltage input
8
-
7 mA
6
+
Current input
Internal jumper setting
TC ⋅ PT
V
I
Match the inputs with the internal jumper settings for each input type. For thermocouple or platinum resistance thermometer inputs, set the internal jumper to a common position (TC/PT) as the temperature input.
Digital Process Controller E5†K
17
Page 18
J Control Output E5AK Control Output Terminal numbers 7 and 8 are for control output 1 (OUT1), and terminal numbers 5 and 6 are for control output 2 (OUT2). The following diagrams show the available Output Modules and their internal circuits.
E5EK Control Output Terminal numbers 7 and 8 are for control output 1 (OUT1), and terminal numbers 5 and 6 are for control output 2 (OUT2). The following diagrams show the available Output Modules and their internal circuits.
With E53-Vjj Output Modules, approx. 2 V is output for one second after the power is interrupted.
E5AK-PRR2/E5EK-PRR2 Controllers The E5AK-PRR2 and E5EK-PRR2 Controllers are supplied with relay output. This relay output is not compatible with any other module. When replacing the Output Module, use the E53-R. The following diagrams show the relationship between terminals and open/close relay settings.
8
6
7
5
Open
Close
18
Digital Process Controller E5†K