Digital Controller
E5CK CSM_E5CK_DS_E_3_1
Advanced, Compact Digital Controllers • IP66/NEMA4 (indoor use) front face. • Modular structure, one-stock type. • Heating/cooling control. • Serial communications (RS-232C and RS-485). • Temperature and analog inputs. • High-accuracy: 100 ms sampling (for analog input). • Advanced tuning which includes fuzzy self-tuning. • Conforms to international EMC and safety standards. Refer to E5@K Operation for operating procedures.
Refer to Safety Precautions for All Temperature Controllers.
Model Number Structure ■ Model Number Legend Refer to the following when ordering set models.
E5CK-@@@@ 1 2 3 4 1. Constant Value/Program Blank:Constant value T: Program 2. Control Output 1/Control Output 2 AA: Without Output Unit (field interchangeable) RR: Relay/Relay QR: Pulse (NPN)/Relay CR: Linear (4 to 20 mA)/Relay VR: Linear (0 to 10 V)/Relay QQ: Pulse (NPN)/Pulse (NPN)
3. Auxiliary Output 1: Auxiliary output (1 point) 4. Option 01: RS-232C serial communication 03: RS-485 serial communication B: Event input (1 point) F: Transfer output (4 to 20 mA)
Note: E5CK-VR1 and E5CK-QQ1 are not available, but with options.
Ordering Information ■ List of Models Description Base Unit
Model
Specification
E5CK-AA1 AC100-240
Base Unit
E5CK-AA1-500 AC100-240
Base Unit with terminal cover
E5CK-TAA1 AC100-240
Standard model
E5CK-TAA1-500 AC100-240
Standard model with terminal cover
Note: A single Output Unit and Option Unit can be mounted to each Base Unit. Description Output Unit
Model
Specification
E53-R4R4
Relay/Relay
E53-Q4R4
Pulse (NPN)/Relay
E53-Q4HR4
Pulse (PNP)/Relay
E53-C4R4
Linear (4 to 20 mA)/Relay
E53-C4DR4
Linear (0 to 20 mA)/Relay
E53-V44R4
Linear (0 to 10 V)/Relay
E53-Q4Q4
Pulse (NPN)/Pulse (NPN)
E53-Q4HQ4H
Pulse (PNP)/Pulse (PNP)
1
Page 2
E5CK Description
Model
Option Unit
Specification
E53-CK01
RS-232C
E53-CK03
RS-485
E53-CKB
Event input: 1 point
E53-CKF
Transfer output (4 to 20 mA)
Inspection Report The Digital Controller can be provided together with an inspection report. Refer to the following legend with the suffix “K” when ordering a model provided together with an inspection report. E5CK-AA1-K, E53-CKF-K
■ Accessories (Order Separately) Name
Model
Terminal Cover
E53-COV07
Name
Model
Rubber Packing
Y92S-29
Note: The Rubber Packing is provided with the Digital Controller.
Specifications ■ Ratings Item
100 to 240 VAC type
Supply voltage
100 to 240 VAC, 50/60 Hz
Power consumption
15 VA
Operating voltage range
85% to 110% of rated supply voltage
Input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII Platinum resistance thermometer: JPt100, Pt100 Current input: 4 to 20 mA, 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, 1 to 10 V
Input impedance
Current input: 150 Ω Voltage input: 1 MΩ min.
Control output
According to Output Unit (see Output Unit Ratings and Characteristics)
Auxiliary output
SPST-NO, 1 A at 250 VAC (resistive load)
Control method
ON/OFF or 2-PID control (with auto-tuning)
Setting method
Digital setting using front panel keys
Indication method
7-segment digital display and LEDs
Other functions
According to Option Unit (see Output Unit Ratings and Characteristics)
Note: 1. Do not use the output from an inverter as the power supply. Refer to Safety Precautions for All Temperature Controllers. 2. The E5CK-T does not support fuzzy self-tuning.
■ Input Ranges Platinum Resistance Thermometer Input (switch selectable) Range
JPt100
Pt100
°C
−199.9 to 650.0
−199.9 to 650.0
°F
−199.9 to 999.9
−199.9 to 999.9
0
1
Resolution (°C/°F) (main setting and alarm)
2
Page 3
E5CK Thermocouple Input (switch selectable) (See note.)
K1
K2
°C
−200 to 1,300
0.0 to 500.0
−100 0.0 to to 850 400.0
−199.9 0 to to 400.0 600
°F
−300 to 2,300
0.0 to 900.0
−100 to 1,500
0.0 to 750.0
3
4
5
Range
Resolution (°C/ 2 °F) (main setting and alarm)
J1
J2
T
E
N
R
S
−100 0.0 to to 850 400.0
−199.9 −200 to 400.0 to 1,300
0 to 1,700
−199.9 0 to to 700.0 1,100
−100 to 1,500
0.0 to 750.0
−199.9 −300 to 700.0 to 2,300
6
8
9
10
7
L1
L2
U
11
B
W
PLII
0 to 1,700
100 to 0 to 1,800 2,300
0 to 1,300
0 to 3,000
0 to 3,000
300 to 0 to 3,200 4,100
0 to 2,300
12
13
14
16
15
Note: Setting number is factory-set to 2 (K1). Thermocouple W is W/Re 5-26 (tungsten rhenium 5, tungsten rhenium 26).
Current/Voltage Input (switch selectable)
Current input 4 to 20 mA
Voltage input
0 to 20 mA
1 to 5 V
0 to 5 V
Range
One of following ranges depending on results of scaling −1999 to 9999 −199.9 to 999.9 −19.99 to 99.99 −1.999 to 9.999
Resolution (°C/°F) (main setting and alarm)
17
18
19
20
0 to 10 V
21
3
Page 4
E5CK ■ Characteristics Indication accuracy (See note.)
Thermocouple: (±0.3% of indication value or ±1°C, whichever greater) ±1 digit max. Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max.
Hysteresis
0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P)
0.1% to 999.9% FS (in units of 0.1% FS)
Integral (reset) time (I)
0 to 3,999 s (in units of 1 s)
Derivative (rate) time (D)
0 to 3,999 s (in units of 1 s)
Control period
1 to 99 s (in units of 1 s)
Manual reset value
0.0% to 100.0% (in units of 0.1%)
Alarm setting range
−1,999 to 9,999 or −199.9 or 999.9 (decimal point position dependent on input type)
Set time
0 to 99 hrs 59 min or 0 to 99 min 59 s
Program capacity
4 patterns, 16 steps (possible to use up to 4 patterns with the communications function.)
Programming method
Time or ramp setting method
Time accuracy
±0.2% (±500 ms) of the set value
Sampling period
Temperature input: Current/voltage input:
Insulation resistance
20 MΩ min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance
Malfunction: 10 to 55 Hz, 10 m/s2 (approx. 1G) for 10 min each in X, Y, and Z directions Destruction: 10 to 55 Hz, 20 m/s2 (approx. 2G) for 2 hrs each in X, Y, and Z directions
Shock resistance
Malfunction: 200 m/s2 min. (approx. 20G), 3 times each in 6 directions (100 m/s2 (approx. 10G) applied to the relay) Destruction: 300 m/s2 min. (30G), 3 times each in 6 directions
Ambient temperature
Operating: Storage:
−10°C to 55°C (with no icing)/3-year warranty period: –10°C to 50°C −25°C to 65°C (with no icing)
Ambient humidity
Operating:
35% to 85%
Degree of protection
Front panel: NEMA4 for indoor use (equivalent to IP66) Rear case: IEC standard IP20 Terminals: IEC standard IP00
Memory protection
Non-volatile memory (number of writings: 100,000 operations)
Weight
Approx. 170 g; Adapter: approx. 10 g
EMC
Emission Enclosure: Emission AC Mains: Immunity ESD:
Approved standards
UL61010C-1, CSA 22.2 No. 61010-1 Conforms to EN61326-1: 2006, EN61010-1 (IEC61010-1) Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is mounted.
250 ms 100 ms
EN55011 Group 1 class A EN55011 Group 1 class A EN61000-4-2: 4 kV contact discharge (level 2) 8 kV air discharge (level 3) Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated, 80 MHz to 1 GHz) (level 3) 10 V/m (pulse modulated, 900 MHz) Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: EN61000-4-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4)
Note: The indication accuracy of the K1, T, and N thermocouples at a temperature of −100°C or less is ±2°C ±1 digit maximum. The indication accuracy of the U, L1, and L2 thermocouples at any temperature is ±2°C ±1 digit maximum. The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted. The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum. The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is greater) ±1 digit maximum. The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or ±2°C, whichever is greater) ±1 digit maximum.
4
Page 5
E5CK ■ Output Unit Ratings and Characteristics Model
Control output 1/Control output 2
E53-R4R4
Relay / Relay
E53-Q4R4
Voltage (NPN) / Relay
E53-Q4HR4
Voltage (PNP) / Relay
E53-C4R4
4 to 20 mA / Relay
E53-C4DR4
0 to 20 mA / Relay
E53-V44R4
0 to 10 mA / Relay
E53-Q4Q4
Voltage (NPN) / Voltage (NPN)
E53-Q4HQ4H
Voltage (PNP) / Voltage (PNP)
Output Type
Specifications
Relay Voltage (NPN) Voltage (PNP)
250 VAC. 3 A 12 VDC, 20 mA (with short-circuit protection) 12 VDC, 20 mA (with short-circuit protection)
0 to 10 V
0 to 10 VDC, Permissible load impedance: 1 kΩ min., Resolution: Approx. 2600 4 to 20 mA, Permissible load impedance: 500 Ω max., Resolution: Approx. 2600
4 to 20 mA
■ Option Unit Ratings and Characteristics Model E53-CKB
Event input
E53-CK01
Communications
E53-CK03 E53-CKF
Specifications Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. No-contact input: ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max. RS-232C RS-485
Transfer output
Transmission method: Half-duplex Synchronization method: Start-stop synchronization (asynchronous method) Baud rate: 1.2/2.4/4.8/9.6/19.2 kbps 4 to 20 mA DC: Permissible load impedance: 500 Ω max. Resolution: approx. 2,600
Note: Event input is used for switching the target value, run or stop command, or automatic and manual mode with an external signal input.
5
Page 6
E5CK
Nomenclature Operation Indicators
No. 1 Display
• OUT1 Lights when the pulse output function assigned to control output 1 turns ON. • OUT2 Lights when the pulse output function assigned to control output 2 turns ON. • SUB1 Lights when the output function assigned to auxiliary output 1 turns ON. • MANU Lights when the manual operation mode. • STOP Lights during operation has stopped. • RMT Lights during remote operation. • AT Flashes during auto-tuning.
Displays the process value or parameter symbols. No. 2 Display Displays the set point, set point during SP ramp, manipulated variable, or parameter settings.
Up Key/Down Key Press to increase or decrease the value on the No.2 display. Display Key A/M Key Press to select the auto operation or manual operation.
Press for less than 1 s to shift the display to the next parameter. When this key is pressed for 1 s or more, the menu screen will be displayed in any case.
Dimensions Note: All units are in millimeters unless otherwise indicated.
E5CK
13
100
44.8 × 44.8 48
58 53 × 53
Panel Cutouts 65 min.
60 min.
45+0.6 0
45+0.6 0
Note: 1. Recommended panel thickness is 1 to 5 mm. 2. Maintain the specified vertical and horizontal mounting space between each Unit. Units must not be closely mounted vertically or horizontally.
6
Page 7
E5CK Terminal Cover E53-COV07
(With rivet)
Unit Label (Order Separately) Y92S-L1
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice.
7
Page 8
Read and Understand This Catalog Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: • Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog. • Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. • Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
ERRORS AND OMISSIONS The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
2009.4 In the interest of product improvement, specifications are subject to change without notice.