Page 11
ES100X/P
ES100X/P Current Transformer Ratings Max. continuous heater current
50 A
Dielectric strength
1,000 VAC (for 1 min)
Vibration resistance
50 Hz (approx. 10G)
Weight
E54-CT1: Approx. 11.5 g; E54-CT3: Approx. 50 g
Accessories (E54-CT3 only)
Contact: 2; Plug: 2
Controller Characteristics Item
ES100X
ES100P
Indication accuracy (see note)
Thermocouple (±0.1% of indication value or ±1°C, whichever greater) ±1 digit max. Platinum resistance thermometer (±0.1% of indication value or ±0.5°C, whichever greater) ±1 digit max. Voltage/current input (±0.1% FS, ±1 digit max.)
ON/OFF control hysteresis
0.01% to 99.99% FS (in units of 0.01%)
Proportional band
0.0% to 999.9% FS (ON/OFF control when 0.0%) 0.1% to 999.9% FS (proportional position model) (in units of 0.1%)
Integral (reset) time
0 to 9,999 s (PD control when 0 s) (in units of 1 s)
Derivative (rate) time
0 to 9,999 s (PI control when 0 s) (in units of 1 s)
Fuzzy intensity
0.0% to 100.0% (Advanced PID control (2-PID) when 0.0%) (in units of 0.1%)
Event set value
Equivalent to –200.0% to 200.0% FS of industrial value or unit
Control period
1 to 120 s (in units of 1 s)
Sampling period
0.1 s min. type 0.2 s (in units of 1 s)
Display refresh period
As large as, twice as large as, 5 times as large as, or 10 times as large as control operation period
PV compensation
Equivalent to –100.0% to 100.0% FS of industrial value or unit
Manual manipulated value
–5.0% to 105.0%
Manipulated value limit
Lower limit: –5.0% to –0.1% max.; upper limit: +0.1% min. to 105.0%
Setting time (1 step)
---
0 to 99 hours 59 minutes or 0 to 99 minutes 59 seconds
Program capacity
---
Total steps 400 max. (99 patterns, 99 steps)
Programming method
---
Break point method (patterns can be decided by the user)
Insulation resistance
20 MΩ min.
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance
Malfunction:10 to 150 Hz, 0.5-mm single amplitude each in X, Y, and Z directions Destruction:10 to 150 Hz, 0.75-mm single amplitude each in X, Y, and Z directions
Shock resistance
Malfunction:20G max., 3 times each in 6 directions Destruction:30G max., 3 times each in 6 directions (20G’s in the forward direction)
Ambient temperature
Operating: –10° to 55°C (with no icing) Storage: –25° to 65°C (with no icing)
Ambient humidity
Operating: 35% to 85%
Memory protection
Lithium cell backup (10 years at normal room temperature)
Enclosure ratings
Front panel: IEC standard IP50 (with water proof cover: IP66, NEMA4) Rear case: IEC standard IP20 Terminals: IEC standard IP00 (with terminal cover: VDE 0106/P100)
Weight
Approx. 800 g
Note:
Indication accuracy varies with the type of sensor and the sensing temperature as follows: K and T sensor (–100°C max.), R, S, and W sensor (200°C max.), and U sensor: ±2°C±1 digit; B sensor (400°C max.): ±6°C±1 digit Indication accuracy without using the built-in cold contact compensation circuit is ±0.1% FS or ±1°C whichever is smaller except for the following sensors: R and S sensor (200°C max.): ±1.5±1 digit; L2 and U sensor: ±1°C±1 digit
Output Unit Characteristics Relay Unit life expectancy
Mechanical: 10,000,000 operations min. Electrical: 100,000 operations min.
11
Page 12
ES100X/P
ES100X/P Heater Burnout Detection Characteristics Max. heater current
50 A, single-phase
Monitor accuracy of input current
±5% FS ±1 digit max.
Heater burnout detection setting range
0.0 to 50.0 A (see note 1)
Heater current monitor range
0.0 to 55.0 A
Min. detectable ON time
200 ms (see note 2)
Note:
1. Heater burnout is not detected when current is set to 0.0 A; the burnout alarm will be automatically turned ON when current is set to 50.0 A. 2. When the control output is ON for less than 200 ms, heater burnout is not detected and heater current is not measured.
Watertight Cover Characteristics Enclosure ratings
Front cover: IEC standard IP66, conforming to NEMA 4
Terminal Cover Characteristics Enclosure ratings
Conforming to VDE0106/P100
Support Software Characteristics (For Windows) Personal computer
Windows-compatible computer with Pentium or higher, and 800 x 600 min. display.
OS
Windows 95, Windows 98, Windows NT4.0, or Windows 2000
Main memory
16 MB for Windows 95 and Windows 98 24 MB for Windows NT and Windows 2000
Communications method
RS232C; half-duplex
Transmission speed
9,600 bps
Printer
Windows-compatible printer
Communications Communications
RS-232C
RS-422
RS-485
Transmission method
None, half-duplex
4-wire, half-duplex
2-wire, half-duplex
Synchronization method
Start-stop synchronization
---
Baud rate
1,200/2,400/4,800/9,600/19,200 bps
---
Transmission code
ASCII (7-bit) (see note 3)
---
Note:
BCD Data select code method
Transmission output 4 to 20 mA Load: 600 Ω max. resolution: 12-bit
1. The maximum total cable length must not exceed the following limits. RS-422: 500 m, RS-232C: 15 m, RS-485: 500 m 2. A maximum of 32 Temperature Controllers can be connected to one host computer using serial communications (RS-422 or RS-485). 3. 8-digit ASCII codes can be also used.
12
Page 13
ES100X/P
ES100X/P
Operation Sampling Period The sampling period of the ES100-series Digital Temperature Controller is factory-set to 200 ms If only the advanced PID control is used, the sampling period will vary with the Model as follows (with a baud rate of 9,600 bps for the Models incorporating a communications function): Model
Sampling period
Model
Sampling period
ES100X-AAH
100 ms
ES100X-AAHFB
100 ms
ES100X-AAHFD
100 ms
ES100X-AAHFE
100 ms
ES100X-AAWHFB
100 ms
ES100X-AAWHFE
100 ms
ES100X-AAH01FE
100 ms
ES100X-AAH04FE
100 ms
ES100X-AAWH01FE
200 ms
ES100X-AAWH04FE
200 ms
ES100X-RRPFB
100 ms
ES100X-RRPFD
100 ms
ES100X-RRPFE
100 ms
ES100X-RRPWFB
100 ms
ES100X-RRPWFE
100 ms
ES100X-RRP01FE
100 ms
ES100X-RRP04FE
100 ms
ES100X-RRPW01FE
200 ms
ES100X-RRPW04FE
200 ms
ES100P-AAH
100 ms
ES100P-AAHFD
100 ms
ES100P-AAHFE
100 ms
ES100P-AAWHFE
200 ms
ES100P-AAH01FE
200 ms
ES100P-AAH04FE
200 ms
ES100P-AAWH01FE
200 ms
ES100P-AAWH04FE
200 ms
ES100P-RRPFD
200 ms
ES100P-RRPFE
200 ms
ES100P-RRPWFE
200 ms
ES100P-RRP01FE
200 ms
ES100P-RRP04FE
200 ms
ES100P-RRPW01FE
200 ms
ES100P-RRPW04FE
200 ms
The control operation period is an important factor for the following control operations (refer to ES100X/ES100P Operation Manual for details): Heating/cooling control Cascade control Fuzzy control Analog I/O assignment Digital I/O assignment No. of events used No. of times that ON/OFF timer used Input type selector (linearization required or not) Terminal communications baud rate Use of digital I/O (BCD communication) The control operation period can be checked with the monitor (character P229) in the check mode.
Product Inspection Sheet Contact your OMRON representative if Product Inspection Sheet are required.
Dimensions Note:
All units are in millimeters unless otherwise indicated.
ES100X ES100P
13 j96
112
Panel Cutouts
169 160* j91
110 mm min.
120 mm min. 92 mm
*175 mm with a terminal cover
92 mm When mounting more than one Unit
13
Page 14
ES100X/P
ES100X/P Y92A-96N Watertight Cover
20.5 92
2
10
131.8
125.3
92
115.6 28
E53-COV01 Terminal Cover 81.9
88.2 72.8
66.9
23
Installation Factory Allocations of Terminal Functions Basic Model ES100j-AAH 34
17 NOT USED
CT input 16
7
CT 32
15 6 b
22 13
4
3
SUB1 (upper-limit a alarm output) 2 EV1 c 1
31
14
A02
– –
23
+
5 AO1 (control output)
30 21
SUB2 12 (upper-limit alarm output) EV2 11
20
Expansion connector
AI1 analog input 1 (K1)
29
28 19
+ 27
10 18 9
14
33 24
Power supply
+
35
25
8
– 26
The allocation shown in the diagrams is applicable to all Basic Models. Input K1: –200 to 1,300°C Control output: Heating control Auxiliary output: Upper-limit deviation alarm (to be set with EV1 and EV2) If the heating/cooling control mode is selected, AO1 is used for heating and AO2 is for cooling control output. To use AO1 and AO2, purchase Output Units.
Page 15
ES100X/P
ES100X/P Terminal Functions (Fixed) of Models other than Basic Models Proportional Positioning Control ES100j-RRPjjjjj
Digital Input (Bank selectable) for ES100X ES100X-jjjjjjjB c
14 5 Open output Relay output
33
Close output Relay output
Digital I/O (Possible to Relocate) of Models other than Basic Models w 32
13
4 o
Initial setting: Used to select a bank. The terminals operate as follows: DI1[BNK0] BNK0: 20 23 BNK1: 21 2 BNK2: 2 DI2[BNK1] 22
31 DI3 [BNK2]
Upper Link RS-232C ES100j-jjjj01jj SD
20
17
Digital I/O (Bank selectable) for ES100X ES100X-jjjjjjjD
NOT USED 25 RD
16
Initial setting: Used to select a bank. The terminals operate as follows: BNK0: 20 BNK1: 21 BNK2: 22
NOT USED 24 SG
21
15
Upper Link RS422/485 ES100j-jjjj04jj
DI1[BNK0] 23
422RDB /485+
DI2[BNK1]
17 422SDB 25
422RDA /485– SG
22
DI3 [BNK2]
16
21
422SDA 24
SUB power supply 19
15 20
Terminal Functions (Possible to Relocate) of Models other than Basic Models
SUB3
10
SUB4
9
24 V IN COM
18
Input 2 (4 to 20 mA Remote Setting) ES100j-jjWjjjjj Initial setting: Use an input of 4 to 20 mA for remote setting. The setting will be effective in the SP mode. + 10 4 to 20 mA
NOT USED 19 1 to 5 V
–
+ 18
9
AI2
Transmission Output (AI1 Process Value) ES100j-jjjjjjFj Initial setting: The value measured by analog input 1 will be output in a range of 4 to 20 mA. 4 to 20 mA + 34
– A03
35
15
Page 16
ES100X/P
ES100X/P Expansion Digital I/O for ES100X ES100X-jjjjjjjE Digital input power supply
Expansion Digital I/O for ES100P ES100P-jjjjjjjE
–
Digital input power supply 1
24 V IN +
3
24 V IN
4
+
DI1 [BNK0]
5
DI3 [BNK2]
1
2
3
4
6
DI2 [BNK1]
DI1 [RUN]
5
6
DI2 [RST]
7
8
DI4
DI3 [HOLD]
7
8
DI4
DI5
9
10
DI6
DI5
9
10
DI6
DI7
11
12
DI8
DI7
11
12
DI8
DI9
13
14
DI10
DI9
13
14
DI10
DI11
15
16
DI12
DI11
15
16
DI12
DI13
17
18
DI14
DI13
17
18
DI14
DI15 Auxiliary output power supply –
19
20
N. C
DI15 Auxiliary output power supply –
19
20
N. C
21
22
21
22
23
24
24 V IN +
23
24 V IN
24
+
SUBOUT3
25
26
SUBOUT4
SUBOUT3 (time signal 1)
25
26
SUBOUT5
27
28
SUBOUT6
SUBOUT5
27
28
SUBOUT6
SUBOUT7
29
30
SUBOUT8
SUBOUT7
29
30
SUBOUT8
SUBOUT9
31
32
SUBOUT10
SUBOUT9
31
32
SUBOUT10
34
N. C
N. C
33
34
N. C
N. C
33
Digital I/O (Operation Instruction and Time Signal) for ES100P ES100P-jjjjjjjD Initial setting: The RUN, RST, and HOLD input are used to operate the program. Time signals set by programs are output from the terminals. DI1[RUN]
DI2[RST]
23
22
DI3 [HOLD] 21
20
16
–
2
SUB3 (time signal 1) SUB4 (time signal 2)
10
SUB power supply
19 24 V IN COM
9
18
SUBOUT4 (time signal 2)
DI1 through DI8 are digital input terminals and SUBOUT3 through SUBOUT10 are digital auxiliary output terminals, both sets of which can be allocated as instructed by the user’s software. The terminals without allocation prior to shipping can be freely allocated as required by the user. DI9 through DI15 are special terminals for BCD communication.
Page 17
ES100X/P
ES100X/P
ES100 Documentation Name
Catalog no.
ES100P Digital Controller User’s Manual
H069
ES100X Digital Controller User’s Manual
H070
ES100 ES/TOOLS Support Software for Windows User’s Manual
H115
ES100 Digital Controller User’s Manual (Communications Guide)
H072
17
Page 18
ES100X/P omrRonNn ES100X/P
18
Page 19
ES100X/P omRON ES100X/P
19
Page 20
ES100X/P
ES100X/P
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H058-E1-3
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation Industrial Automation Company Measuring and Supervisory Controls Department Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 Japan Tel: (81)75-344-7080/Fax: (81)75-344-7189
20