The text of a manual · part 1 of 12
Model ES100 Process Controller ESTOOLS Software Programming Manual and Application Road Map, pages 1 to 10
Pages 1 to 10 of 114
The original document is the PDF (2.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Omron ES100X-AAWH01FE
Page 1
Model ES100 Process Controller ESTOOLS Software Programming Manual and Application Road Map -DQXDU\
Downloaded from www.Manualslib.com manuals search engine
Page 2
Downloaded from www.Manualslib.com manuals search engine
Page 3
Notice:
Omron certifies all of its products either meet or exceed stipulated specifications. Omron is not liable for steo-graphic and/or clerical errors. Omron will not be liable for any design furnished by the buyer and incorporated into equipment. Omron is not to suffer risk due to the suitability or unsuitability or the results of the use of it’s products used in combination with any electrical or electronic components, circuits, systems assemblies or any other materials or substances or environments. Omron will not be liable if any product is altered in any way or suffers consequential damage due to negligence or misuse.
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify warnings in this manual. Always heed the information provided with them.
DANGER! Indicates information that, if not heeded, could result in loss of life or serious injury.
Caution Indicates information that, if not heeded, could result in minor injury or damage to the product.
© OMRON, 1996
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permis-sion of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
Downloaded from www.Manualslib.com manuals search engine
Page 4
TABLE OF CONTENTS
General Information ... 1 1-1 Registering Your Controller with ES/TOOLS ... 2 1-2 Configuring the ES100 ........ 6. teens 4 1-3 Analog Operation Assignment Table ... 6
SECTION 1 Cascade Control ... 9 1-1 Definition of Cascade Control ... 10
1-1-1 Conventional Control Method ... 10 1-2 Cascade Control ...... 00... tenet teens 11 1-2-1 ES100 Internal Cascade Control ... 12 1-2-2 Start-Up Procedure ... 13 1-3 Operation and Tuning ... 14 1-3-1 Limit Cycle Tuning ... 15 1-3-2 Tuning the Primary Loop ... 21 1-3-3 Fuzzy Logic Fine Tuning ... 22 1-4 Applications ... 32 1-4-1 Chemical Reactor ... 32 1-4-2 Touchless Clothes Dryer ... 33 1-4-3 Gas Solder Machine ... 34 1-4-4 Vacuum Processing Furnace ... 35
SECTION 2 Position Proportional Control ... 37
2-1 What is Position Proportional Control ... 38 2-1-1 Closed Control ... 38 2-1-2 Floating Control ... 38 2-1-3 Start-Up Procedure ... 39
2-2 Operation and Tuning .......... 00. e eee tenes A 2-2-1 Operation at Process Value Error ...... 0.0.00 ccc cee ence eens A 2-2-2 Valve Hysteresis and Dead Band ... 42 2-2-3 Configuring the ES100 Front Panel ... 43 2-2-4 Motor Calibration and Travel Time ... 45 2-2-5 Travel Time with Floating Control ... 46 2-2-6 Autotuning ... 47 2-2-7 Fuzzy Logic Fine Tuning ... 48
2-3 Applications ... 50 2-3-1 Bread Baking OVen ... 50 2-3-2 Drying Furnace ... 51
SECTION 3 Heat/Cool Control ... 53
3-1 Definition of Heat/Cool Control ... 54 3-1-1 Dead Band and Overlap Bands ... 56 3-1-2 Start Up Procedure ... 57 3-1-3 System Configuration .......... 0.6 ccc eee 57
3-2 Setting Manipulated Variable for Process Operation ... 57 3-2-1 Setting a Dead Band ... 58 3-2-2 Setting an Overlap Band ... 59 3-2-3 Setting the Cooling Coefficient ... 60
3-3 Setting Manipulated Variable for Process Completion ... 61 3-3-1 Manipulated Variable When NO OUTPUT is Desired ... 61 3-3-2 When Continued Control Output is Desired ..............-..000020005 66
3-4 Autotuning ... 67
Downloaded from www.Manualslib.com manuals search engine
Page 5
3-4-1 Fuzzy Logic Fine Tuning .............. 06.0 c eee eee 68
3-5 Applications ... 71 3-5-1 Culture Chamber ... 71 3-5-2 Shampoo Manufacturing Machine .............60..0 cece ee eee eee 72 3-5-3 Drying Machine ... 73 3-5-4 Water Purifying Machine ... 74
SECTION 5 Feed Forward Control ... 89
5-1 What is Feed Forward Control ... 90 5-1-1 Start-up Procedure ... 92 5-1-2 Analog Operation Assignment Table ... 92
5-2 Operation and Tuning ... 93
5-3 Autotuning ... 97 5-3-1 Fuzzy Logic Fine Tuning ...............0 00 cece ee 99
5-4 Application ... 101
Appendix A Control Modes ... 103 Appendix B PID Conversions ...........000se02++ 105 INdOX 2. eee eee eens 107
Revision History ... 109
Downloaded from www.Manualslib.com manuals search engine
Page 6
LY Downloaded from www.Manualslib.com manuals search engine
Page 7
General Information
Omron’s ES100 Digital Process Controller provides advanced, accurate control in a wide variety of process and temperature control applications. This document was developed to help you to take full advantage of the ES100’s extensive programming and control features using ES/TOOLS. ES/TOOLS is a DOS-based program with an intuitive graphical user interface that enables you to quickly program complex control schemes such as Cascade and Proportional control from your personal computer.
Sections 1 through 5 of this manual cover specific control strategies that can be implemented using the ES100. These include Cascade Control, Position Proportional Control, Heat/Cool, Ratio Control, and Feed Forward Control Strategies. We recommend that you have manuals ES100X (H070-E1-1) or ES100P (HO69-E1-1) on hand for reference before you begin.
This manual begins with a general introduction to programming the ES100 using ES/TOOLS software. The following sections will guide you through the initial three-step software setup that prepares ES/TOOLS for use with your controller and specific applications found later in this document. These procedures include:
1. Registration - Prepares the ES/TOOLS for your specific ES100 controller model.
2. Configuration - Configures ES/TOOLS for your application process inputs.
3. Analog Operation Table Setup - Determines which calculations ES/ TOOLS should perform.
You must follow these procedures in the sequence as listed above.
Downloaded from www.Manualslib.com manuals search engine
Page 8
Registering Your Controller with ES/TOOLS
1-1 Registering Your Controller with ES/TOOLS
The first time you use ES/TOOLS to program a new application, you must allow the software to determine which model of ES100 you have. To do this, start
ES/TOOLS and follow the steps below.
[=] ES/TOOLS MENU
QZ. Zz
Setting Check control <Online>
Setting <OFf line>
5 O Ti Transfer Transfer Print <PC, -> ES> <ES, > PC>
[F9:option|| F1@:Help || ESC: Exit ]
Downloaded from www.Manualslib.com manuals search engine
Figure 1
Select a COM port as follows: a. From the ES/TOOLS menu (Figure 1), click on the button.
Then select the Select system parameters | 1 tton, A Communications Menu appears.
b. Double-click on the button.
c. Click on COM1 or COM2 to select the COM port you wish to use on your PC.
d. Click on the button. You will return to the ES/TOOLS Main Menu.
Register the controller as follows:
a. Select the Setting <Offline> icon (see figure 1) by double-clicking on it.
b. At the pop-up menu, double-click on the button. (If you wish to load a saved ES100 configuration, select the button and follow the prompts.)
c. Double-click on the button. The “New, - Controller Type” menu appears (Figure 2).
Page 9
Registering Your Controller with ES/TOOLS, Nev, - Controller Type iO | Fi:Read || F2:List | F3:vers ion | | |F9:option] | F16:Help || ESC: Exit | Set by +, -, or SPACE BAR.
[control ler Type |Es190x-RRP H@4FE Ver. 2.
Control ler (X) RS-422/485 (64)
Ce | Pos i - prop (RRP) Ext vo |] Expanded I/OCE)
lanalog 12 _|| None Pulse Cor Unused)
[Heat alarm |} EnabletH [controt 02 |} Pulse Cor Unused) Figure 2
You may now use one of three methods to register your controller with ES/ TOOLS. The first method (recommended) allows the software to automatically determine the controller type and hardware options of the controller currently to ES/TOOLS. The second method lets you choose the controller type from a list. The third method allows you to build a controller type based on the hardware options of the controller. This method is useful for setting up configurations for different controllers and different applications.
Method 1 - Automatic
Note: Method number 1 displays the exact controller type and hardware options available for the controller currently connected to ES/TOOLS.
1. Connect an RS-232 cable from the front panel of the ES100 to COM port on your computer that you selected earlier.
2. Double-click on [Fi:Read |, confirmation window appears. Select the button. The software will attempt to automatically determine which ES100 controller type you have and display the controller part number on the screen.
3. When finished, click on the button. A pop-up menu appears. Select LENT:OK J the Configuration parameters menu will appear.
Method 2 - Select from a list
1. Double-click on the button. A list of ES100 part numbers appears.
2. Select the appropriate part number from the list by double-clicking on it or by scrolling down to highlight it and pressing <Enter>. The controller type should now appear on the screen along with its associated hardware options.
3. When finished, click on the button. A pop-up menu appears. Select LENT-OK | the Configuration parameters menu will appear.
Method 3 - Build your own controller type
1. In the “New - Controller Type” menu, use the buttons to select the appropriate features of your ES100. To assist you, a list of buttons along with brief descriptions appears below. When finished, a corresponding controller type part number should appear on the screen. To modify feature options simply double-click on the button and select a new option from the pop-up menu.
Downloaded from www.Manualslib.com manuals search engine
Page 10
Configuring the ES100
2. When down, double-click on the button.
Caution: As you change the hardware options the part number shown in the “Controller Type” dialog box will also change. When using this registration method it is possible to create a controller type that does not exist. Therefore, it is important to verify that you have built an appropriate part number. Failure to verify a part number will result in the inability to download a program. To verify, simply select then select ENTOK] pop-up window will alert you that the part number does not exist.
The following defines the available selections in the New -- Controller Type menu.
Displays the controller type: (P) Ramp/Soak controller; (X) Eight-bank memory.
Displays control method type; Heat/Cool (standard) or Posi-Prop (RRP) Valve Positioning.
Enables a second input if the controller is equipped with one.
Enables a heater burnout alarm if the controller is equipped with one.
Displays controller communication type:“None”, RS-232C (01), or RS-422/485 (04). Note that (01) or (04) are added to the part number and are not part of the communications protocol.
Enables the Transfer Output if the controller is equipped with one. The choices are Enable (F) or None.
Displays the type of digital 1/O you have on your controller. Digital | (B) corresponds to three rear terminal inputs only; Digital I/O (D) corresponds to three inputs and two outputs on the rear terminal; Expanded I/O (E) corresponds to eight inputs and eight outputs connected to the controller by an external cable.
Displays the type of control output to be used in Control Output 1, Current or “Pulse/Unused”. Current is used for all linear analog outputs, (i.e. 4-20 mA, 0-20 mA, 1-5 VDC, 0-10 VDC). “Pulse/Unused?” is used for all time proportional outputs (i.e. mechanical relay, SSR, transistor/voltage).
Displays the type of control output to be used in Control Output 2. Current or “Pulse/Unused”. Current is used for all linear analog outputs, (i.e. 4-20 mA, 0-20 mA, 1-5 VDC, 0-10 VDC). “Pulse/Unused” is used for all time proportional outputs (i.e. mechanical relay, SSR, transistor/voltage).
1-2 Configuring the ES100 Note: This procedure is available from ES/TOOLS menu.
The Configuration menu may be viewed in two ways. The default option is Optimize Mode - EFFECT. This configuration menu option displays most of the available options. There are some parameters that will not show but may need to be altered (i.e. technical parameters such as PID, Fuzzy Logic Setting). The second option, Optimize Mode - UNEFFECT, displays all possible configuration fields for all ES100 controller types. It is useful for fine tuning parameters or reconfiguring the controller’s features at a later date.
Downloaded from www.Manualslib.com manuals search engine