Page 11
Configuring the ES100
1. Click on LF9:Options } button. An options Menu appears (Figure 3)., SSS Configuration p. ters a y y 1| |[ro:ortion| [FiecHetr |[zsc-mae | Set by +, -, or SPACE BAR.
Analog input 1 tune I> Ki [ b Analog input 2 2-P1D+fuzzy Option menu, = _ - - - Not used Select system parameters __ - - Standard Hard copy
| About ES/TOOLS Digital IO
[Bank select me SBHz Figure 3
Click on | Select system parameters | button
Double-click on the Optimize Mode: Effect | button.
Double-click on either the Effect] o, Uneffect | button to select the menu option you wish to enable.
Click on the button.
6. You may now configure your ES100 (Figure 4). Once you have completed configuring your ES100, click on the button. A pop-up menu appears to create a new file, then select ENT:OK | The main screen for Setting <offline> will appear.
ol
To configure the software parameters of hardware options that were selected from the New -- Controller Type menu, double-click on a parameter button and select the new value from the pop-up menu., New, - - Configuration parameters ‘CO | || || || | |F9:option]| F16:Help || ESC :Exit ] Set by +,, , or SPACE BAR. lfma log input 1 type > K1 [Program method > Ramp & soak ema log input 2 type > 4-26mA |2-P1D/2-PID+fuzzy > 2-PID+fuzzy [scaling unit > c |Heat-cool/standard > Standard [Decimal point » a [Potentioneter input > Not used [Scaling lower limit > -266 |cascade/standard > Standard [Scaling upper limit > 1380 [Bep con/digital 1/0 > Digital 1-0 [Bank select method > No. [Line noise reduction > SOHz
Figure 4
The list below describes the function of each button selection in the New -- Configuration parameters menu. The New -- Configuration parameters menu allows you to configure the software parameters of hardware options that were selected from the New, - Controller Type menu.
| Analog Input 1 Type } Displays the active input type: Thermocouple, RTD, or Analog.
[Analog Input 2 Type } Displays the active input 2 type: 1-5 VDC or 4-20 mA.
Displays the active unit of measure for your process: F° = Fahr-enheit, K° = Kelvin, m = meter, m/s = meter/second, f/s = feet/second, etc.
Downloaded from www.Manualslib.com manuals search engine
Page 12
Analog Operation Assignment Table
Note:
Note:
Displays the active number of decimal places to be displayed on the controller.
| Scaling Lower Limit | Displays the scale value for the controller to display for the lowest input value. (Note: This should only be changed on an analog type input. Thermocouple and RTD inputs are pre-scaled.)
| Scaling Upper Limit | Displays the scale value for the controller to display for the highest input value. (Note: This should only be changed on an analog type input. Thermocouple and RTD inputs are pre-scaled.)
| Bank Select Method | (Es 190xX only) Displays the operating mode: time mode or bank mode. In time mode, the bank runs for a specific programmed time period. In number mode, the bank selected runs indefinitely.
Program Method | (&S100P only) Displays the operating mode: Ramp/Soak or Soak Step.
[2:PID/2-PID+Fuzzy | Turns the Fuzzy Logic ON/OFF. With this setting you may choose to run the ES100 in PID only or PID using Fuzzy Logic.
| Heat-Cool/Standard | Digniays the active controller operation method: heat/cool or standard.
If heat/cool is selected, ES/TOOLS automatically configures the Analog operation assignment.
[Potentiometer Input | Disnlays the active potentiometer input status: Used (slide wire feedback mode) or Not used (velocity mode; where the position is stored in memory based upon a travel time).
This display will be activated only when using a valve-positioning type controller (ES100_-RRP___ ).
|Cascade/Standard | nisniays the active selection for controller operation: internal cascade or standard.
[BCD Com/Digital /0 | Displays the active I/O selection: Digital I/O (standard) or BCD com (BCD communications).
[Line Noise Reduction | isniays the active power source type: 50 Hz (Euro-pean and Japanese) or 60 Hz (standard U.S.).
1-3 Analog Operation Assignment Table
The Analog Operation Table (Figure 5) displays all of the mathematical functions for each of the ES100’s I/O points including scaling, adding, subtracting, multiplying, square root, etc. You do not need to make any changes to the Analog Operation Assignment Table unless your process requires special mathematical functions such as straight line approximation, etc. While in most cases no changes are needed, it is recommended that you review the table so that you know how the controller is set up to operate. If changes are required, simply select the value you wish to modify by clicking on it with the cursor and select from the pop-up menu.
When done, select to return to the Main Menu.
Downloaded from www.Manualslib.com manuals search engine
Page 13
Analog Operation Assignment Table
Fo Analog operation assignment iO F1:Details| | || F3: Image || F4:Edit | |F9:option] | F146:Help || ESC Exit | 1 2 3 4 5 6 lassign dest || [rv = |jaor_ - ||- aoa |istP || MoV SUB END MoU ADD END AIL MY - Py VOPC - - YOPC - - AP31 - END END END END END END al >
Figure 5
You have now completed the steps necessary to setup your controller. Now refer to the appropriate section of this manual to continue setting up the ES100 for specific operations.
Downloaded from www.Manualslib.com manuals search engine
Page 14
SECTION 1 Cascade Control
1-1 Definition of Cascade Control ... 10 1-1-1 Conventional Control Method ... 10 1-2 Cascade Control ... 11 1-2-1 ES100 Internal Cascade Control ... 12 1-2-2 Start-Up Procedure ... 13 1-3 Operation and Tuning ... 14 1-3-1 Limit Cycle Tuning ... 15 1-3-2 Tuning the Primary Loop ... 21 1-3-3 Fuzzy Logic Fine Tuning ..............0 000. c cece eee eee 22 1-4 Applications ... 32 1-4-1 Chemical Reactor ... 32 1-4-2 Touchless Clothes Dryer ... 33 1-4-3 Gas Solder Machine ... 34 1-4-4 Vacuum Processing Furnace ... 35
Downloaded from www.Manualslib.com manuals search engine
Page 15
Cascade Control Section 1-2
1-1 Definition of Cascade Control
Cascade control is used in processes where more than one item in the process needs to be controlled to achieve the desired result. An example would be controlling furnace temperature by controlling the fuel supply to the furnace.
1-1-1 Conventional Control Method
In the following example a gas furnace (Figure 1) is controlled with a single controller. The furnace requires a long time for the internal temperature to change, once the gas flow has been adjusted.
When the pressure in the gas line fluctuates, this causes unwanted changes in the flow of gas to the furnace and causes unwanted temperature changes. The change in gas flow cannot be detected by the controller until it is re-flected as a temperature change in the furnace.
Temperature | sensor PV E5AX sp A Furnace Disturbance MV ra Fuel, - PE Valve '«<” Disturbance Fuel flow ' - sp Furnace temperature > sp SP DV TC MV (Furnace) PV © | Controller |» Temperature process 8
Figure 1
10
Downloaded from www.Manualslib.com manuals search engine
Page 16
Cascade Control Section 1-2
1-2 Cascade Control
Unlike conventional control methods which use a single control loop to monitor and regulate, cascade control uses two control loops to control processes where more than one item in the process needs to be controlled to achieve the desired result. An example would be controlling furnace temperature by controlling the fuel supply to the furnace.
In this example (Figure 1), the primary loop controls the temperature inside the furnace, and the secondary loop controls the fuel flow.
Primary loop Temperature controller PV E5AX Temperature SP, - - Secondary loop sensor SP2 E5AX-L PV2
Flow controller
Disturbance
Fuel, - ' A Furnace
To maintain the proper temperature in the furnace, we need to control the amount of gas fed to the furnace to maintain temperature, but we must also try to compensate for fluctuations in the gas line which create unwanted changes in temperature (Figure 2).
‘«S Disturbance c Hl Vo uel TlOoWw > SP
| Response using , Response using
1 cascade control , eo ts a conventional control Furnace \ aan N temperature _' aw, - Figure 2
Cascade control uses two control loops to control a process. In our furnace example, the primary loop is used to control the temperature in the furnace by setting the flow rate of the gas entering the furnace. The secondary loop is used to maintain a steady flow rate by compensating for pressure fluctuation in the gas line (Figure 3).
TC FC SP~ DV | Primary oor [SEE PME Secondary MV Flow process ve Temperature | PV controller loop controller process 1 Secondary loop
DV = PV - SP DV2 =PV2-SP2_ Primary loop
Figure 3
11
Downloaded from www.Manualslib.com manuals search engine
Page 17
Cascade Control Section 1-2
The output of the primary loop controller is used to establish the set point of the secondary controller. The secondary controller acts as a slave (Figure 4) to the primary controller. The primary controller monitors the temperature, and tells the secondary controller which flow rate to maintain.
Temperature controller py lL.
E5AX Temperature | sP, > LK Secondary loop sensor Primary SP2 > loop ayo "| ESAX-L
Flow controller
A Furnace eee ' MV ' |
Fuel, - 1-2-1 ES100 Internal Cascade Control
The ES100 offers a very efficient means of establishing a cascade control system, which eliminates the requirement for a second controller. The ES100 controller has two control loops built into the same controller which is referred to as internal cascade control . The equivalent wiring for an ES100 system is shown in the Figure 5.
Temperature sensor
PV yy &S100
Furnace MV
@ ~<
Flow sensor Valve
PV2
Figure 5
12
Downloaded from www.Manualslib.com manuals search engine
Page 18
Cascade Control Section 1-2
Any type of ES100_-__ W_____can be used to perform cascade control. The W signifies the controller has two analog inputs. Figure 6 shows a wiring diagram for our furnace example. Analog input 1 is operating as the primary input, and analog input 2 is acting as our secondary input. Analog output 1 operates as the primary control output to the valve actuator.
| © _ Power co (4s) : ! Valve supply 26 TT @s) ' | = a | | : : @ input (1) a 4-20 mA @ ; Flow Sensor ® + @ ! _ +@ CO Gs) .@ Thermocouple Al2 On - *Gs) | | an ° ee Oe | -@b 420mA0 Figure 6
1-2-2 Start-Up Procedure
Note: For the following procedures, the ES100 must be powered up and connected to the COM port of the computer running ES/TOOLS via an RS-232 cable.
1. If you haven’t already done so, follow the registration and configuration set up guidelines at the beginning of this manual.
2. From the ES/TOOLS Menu, double-click on the Setting <Offline> icon. The Setting Menu <Offline> will appear (Figure 7)., Setting Menu <Offline> I | F1:File || || || | |Fo:option|| || Esc:Exit | | Controller type [ ES1@6X-AA WHO4FE Ver. 1.** J | | Configuration Parameters |, - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Paraneter Sp conditions | bper at PV error| Control params | | Output | | Front panel ] Power ON oper | Event | | Secondary loop | Conmunicat ions | | | | } |
Bank Assignment | Bank (SP) | | Digital oper | Analog oper is [File nane [cascabE.Es1 || Comment | | Figure 7
13
Downloaded from www.Manualslib.com manuals search engine
Page 19
Operation and Tuning Section 1-3
3. Double-click on the button. The Analog operations assignment menu will appear (Figure 8).
Note: Only the first six entries are shown in the Analog operation assignment window. Use the scroll bar to view table entries 6, 7, 8, 9 and up.
FA Analog operation assignment (| F1:Detai ts] | || F3: Image || F4:Edit | |F9:option] | Fi :Help || ESC I Exit ] 1 2 3 4 b=) 6 lassign dest ||| PU a01 - AOS STP RSP
MoV MoU END MoU Moy MoV
AIL NY - py AP31 AIZ
END END END END END END
<l »
Figure 8
Analog assignment 6, 7, 8, and 9 make the internal connections. These connections allow the following functions to be performed.
¢ Analog input 2 to be used as the PV of the secondary loop.
¢ The output of loop 1 to act as a setpoint (CSP) of loop 2.
¢ Analog assignment Column 7 moves PV2 to an internal buffer which we can then display on the front panel of the controller.
The controller is configured for cascade control operation by default. No changes are necessary to this table unless special functions are needed. Proceed to Operation and Tuning.
1-3 Operation and Tuning
It is necessary to remember that in cascade control configurations there are essentially two separate PID control loops. The ES100’s autotuning feature can not be invoked when setting up the controller for Cascade Control operation. Therefore, the secondary loop must be tuned manually or by using the Fuzzy Logic Fine Tuning method, as described in Section 1-2-3.
Note: In cascade control applications, it is required to accurately tune the secondary loop first.
There are two different methods of tuning the secondary loop. They are:
1. Limit Cycle Tuning, Section 1-2-1 2. Fuzzy Logic Fine Tuning, Section 1-2-3
14
Downloaded from www.Manualslib.com manuals search engine
Page 20
Operation and Tuning Section 1-3
1-3-1 Limit Cycle Tuning
Caution: Limit Cycle Tuning may be used as long as your process will not be negatively affected by the generation of a limit cycle. If your process or system safety will be compromised by the generation of a limit cycle, refer to the Fuzzy Logic Fine Tuning Method later in this section.
The Limit Cycle method of tuning a Cascade Control loop forces the process into a repeating oscillation, or hunting state. It is achieved by using a proportional band equal to one hundred percent of full scale.
Hunting period (t) ~«
Figure 9
By forcing your process into an oscillating state of operation, you are able to observe the Peak-to-Peak temperature that it will achieve as well as how fast it will react to the oscillation. By forcing the process to oscillate, you are allowing it to attain its natural or resonant state, represented by ‘t’ in Figure 9. The period ‘t’ will be used to calculate the P, | and D values that will provide you with the optimum performance of the ES100.
Isolating the secondary Loop Note: You must have the controller powered up and the communication cable installed between the computer and ES100. This procedure also requires that ES/TOOLS be in the “optimize-uneffect” mode (see Section 1-2).
The first step in tuning the secondary loop is to isolate it from the primary loop. Isolate the secondary loop from the primary loop as follows:
1. Select the Check control icon from the ES/TOOLS menu by double-clicking on it (Figure 10). The Check control menu appears
[| ES/TOOLS MENU peer ee ee ew
Setting Setting <OfFf line> <Online> eI a T Transfer Transfer Print
<PC -> ES> <ES -> PC>
|F9:option || F10:Help || ESC: Exit ]
Figure 10
15