Model ES100 Process Controller ESTOOLS Software Programming Manual and Application Road Map, pages 21 to 30

Pages 21 to 30 of 114

The original document is the PDF (2.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Omron ES100X-AAWH01FE

Page 21 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 1-3

2. Inthe Check control menu click on (Figure 11).

E

Fi:Run | F2:Paran | |F3:status | F4:Command] |F9:opt ion || || esc:Exit |

Check control

68/29/94 7580.8 16:68:33

Move point

Monitor rend Setting [/SP 106.60 PY 75.64 MY 8.804

Clear data

Trend mode

Exec A.T.

ypu

Exec F.T. Interval 2 Second Canc A.T.

Undo F.T. Draw mode

Clear + draw

Change SP

EERE RUE

6:62:66 6:66:84 6:16:08

Figure 11

3. From the pop-up menu select Change Cascade OPEN/CLOSED | then so-lect OPEN] Another pop-up menu then confirms switching cascade to open.

4. Select to confirm. 5. Select to return to the Check control menu.

The secondary loop now is independently controlled from the primary loop by the ES100. Figure 12 represents an open cascade loop with the secondary loop isolated. Note that the secondary loop is the only loop being controlled.

| Thermocouple

Cascade disabled

Secondary loop

Cascade . open Primary loop Secondary loop |_, | Flow Temp _ Controller Controller Process Process i Secondary loop Primary loop

Figure 12

16

Downloaded from www.Manualslib.com manuals search engine

Page 22 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 1-3

Setting Secondary Loop PID Values

By isolating the secondary loop from the primary loop, you are able to view/ modify the secondary PID loop default settings.

Note: If you are familiar with your system PID values, use them in place of the default values. If you don’t know your system’s PID values, use the default values.

1. From the Check control menu, select |F2:Param } 2. From the vertical menu on the left side of the screen select [PID param |

Fo f Check control ia | Fi:Run || F2: Param | |F3:status | F4:Command| [F9:option] | || ESC: Exit | Dasvaivos sea al ] l I I

ESC : Cancel Select PID parameter [PID No.=11] ESC :Cancel iP ;

D

MY lower Limit

MV upper limit

PY bias value

Auto select range upper limit

Clear + draw 6.4 6:42:68 6:46:68 6:14:68 Figure 13

3. Enter the bank number and select the button.

4. From the pop-up, double-click on ‘P’ (Figure 13). Note that the default value is 100% which should be adequate for most applications. If a new value is desired, simply type in the new value.

5. Select button.

6. Scroll down and select ‘I’. Note that the default value is 60 seconds which should be adequate for most applications. If a new value is desired, simply type in the new value.

7. Select button.

8. Scroll down and select ‘D’. Note that the default value is 0 seconds which should be adequate for most applications. If a new value is desired, simply type in the new value.

9. Select button.

10. Select the button from the pop-up window. 11. Anew window appears that will let you change PID bank #’s if you wish to. Then select LESC:Cancel_ |’

12. Select the button from the vertical menu on the left side of the screen.

17

Downloaded from www.Manualslib.com manuals search engine

Page 23 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 1-3

Setting the Fixed Value Set Point for the Secondary Loop (FSP2)

Note: If you know what the setpoint of your secondary loop should be, use the following procedure. If you do not know, go to the Manual Output Control method later in this section.

Because the primary loop has been temporarily disconnected from the secondary loop, its output is no longer available as the setpoint of the secondary loop. Therefore, you will need to establish an approximate value for the secondary loop setpoint. This approximate value should be known to the operator/engineer with a knowledge of the system. If it is not known you can use the Manual Output Control method described later in this section. Please note that the unit of the SP2 is a percentage value. The output variable of the primary loop can be set any where between 0% (Fully OFF) and 100% (Fully ON).

1. From the ES/TOOLS menu, select Check control. 2. From the Check control menu, select | F2:Param |

Note: All the options on the left side of the screen will change as shown in Figure 14, Check control Unit No.4 al

| Fi:Run | | F2:Param | [r3:Status | Fa :Comnand] [ro :Option | | | | ESC Exit |

ESC :Cancel Select adjustment parameter Esc:cancet] [aaj param | SP rise rate limit SP fall rate limit

MU change rate Limit

Fixed SP (secondary loop)

IP (secondary loop)

I (secondary loop)

D (secondary loop)

Manual reset (secondary loop)

__], 368

6:62:68 6:66:68 6:16°66

Figure 14

3. Select | Adj param |

4. Scroll down and select Fixed SP (secondary loop) from the pop-up menu.

5. In the pop-up window, type in the percentage of output that you want for the setpoint of your secondary loop, then press the <Enter> key on the keyboard.

6. Select button. 7. Select the button from the pop-up menu.

8. Select the button from the vertical menu on the left side of the screen to return to the main menu.

18

Downloaded from www.Manualslib.com manuals search engine

Page 24 read from a scan by OCR; it may hold reading errors

Operation and Tuning

Section 1-3

Displaying Process Trends

Use the following procedure to display loop process values (PV2, SV2 and MV) on your computer. You will need to monitor this display to measure hunting and width to determine PID values for the primary and secondary loops.

From the Check controls menu, select [Trend Setting | From the pop-up menu, select (Figure 15).

1. 2.

3.

Downloaded from www.Manualslib.com manuals search engine

EA Check control Unit No.@8 ir | Fi:Run | | F2:Paranm | [F3:Status | F4 :Comnand] [rs Option | | | | ESC: Exit | 11/2795 2366 Clear data 14122142, Monitor rend Setting Trend Setting ESC:Cancel | Exec A.T. | Data scale == Canc A.T. } (Clear + draw Change SP ] “me 6:62:66 6:66:68 6:16:68 Figure 15

Select (Green, Bold Line). Refer to Figure 16.

i Check control Unit No.@8 ial | Fi:Run | | F2:Param |[F3 ‘Status | F4 :Comnand] [ra :Option | | || ESC Exit | 11/27/95 2300 Clear data 14:22:42, rend Setting Trend item ESC :Cancel Trend mode ] Trend item 1 (Green, Bold line) Trend item 2 (Red, Fine line) | Exec F.T ] Trend item 3 (Purple, Standard line) (Clear + draw a Change SP ] Lae 7“ 6:62:06 4:66:68 6:16:68

From the pop-up menu, select [SP2 |. Select (Red, Fine Line).

From the new pop-up menu, select [PV2 | MvVis automatically set up to display on ES/TOOLS.

Select the button from the pop-up window to return to the main menu.

19

Page 25 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 1-3

Manual Output Control (Optional)

Note: The following procedure can be used to approximate a value for SP2 if required, otherwise, proceed to the next section.

It is possible to incrementally increase the MV until the PV comes as close as possible to the SP that you require. Follow the steps below using small incre-mental increases of MV to reach your SP2.

Example: Your system = Control valve (able to control 0-20 cubic feet of gas/ min), ES100, SP2 is equal to 12.5 f8/m.

Begin running your process in a normal fashion. Use the instructions below to change MV to 10%. Record the MV and PV that you used once the flow of gas has stabilized. If the gas flow is not yet at 12.5 f8/m, increase the MV again using the instructions below. Once you get near the SP2 increase the MV in smaller increments until you are as close as possible to the required SP2.

1. From the Main Menu, select Check control.

Select F4:Command |

Scroll down and select from the pop-up menu. Select from the second pop-up menu.

Select when prompted by ES/TOOLS.

Select and go back to the Check control main. From the Check control menu, go to the left side of the screen and select [Manual |

8. From the pop-up window, set the desired output value between 0 and 100% (0% = Fully OFF; 100% = Fully ON), and select ENT_OK ],

9. Proceed to the Limit Cycle for your secondary loop.

10. Return the controller back to Auto mode.

Starting the Limit Cycle and Loop PID Calculations

1. Make sure that the loop PID constants are set to: P = 100. 1=0, andD=0. From the ES/TOOLS menu select Check control.

Select [F1:RUN |

From the vertical menu on the left side of the screen, select [RUN |

Enter the PID bank number then press the <Enter> key on the keyboard. A confirmation window appears.

Select [ENT: OK }

The controller begins to perform an oscillating control pattern on your process. It is very important to monitor the Hunting Width and Hunting Period as closely as possible. These values will be used to calculate your final PID values (Figure 17).

NO a FO DW ar Oo

N

Hunting period (t) ~«

Figure 17

20

Downloaded from www.Manualslib.com manuals search engine

Page 26 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 1-3

Use the table below to calculate your Loop PID values. In the back of this manual, there is a general discussion of PID for your review.

Full PID control: PI control: P control:

P = 1.7 X Proportional P = 3 X Hunting Width (% FS) | P = 3 X Proportional Band Band (% FS) (% FS)

| = 0.5 X Hunting Period | = 1.17 X Hunting Period l=0

(time in minutes) (time in minutes)

D = 0.125 X Hunting D=0 D=0

Period (time in minutes)

When you have completed inserting your calculated secondary loop PID values into the controller (see setting secondary loop PID values earlier in this section). Return to the Check control menu and reconfigure the trending screen to display primary loop process values (PV, SP, and MV). See the displaying process values section earlier in this chapter. The secondary loop is now tuned.

8. Return back to the Check control menu and stop the controller by selecting the button.

1-3-2 Tuning the Primary Loop

Note: Before attempting to tune the primary loop, make sure to close Cascade by following the steps below. 1. From the ES/TOOLS menu, select Check control. From the Check control menu, select [F4:Command |

From the pop-up menu, select Cascade OPEN/CLOSED |

2

3

4. Selection

5. Select [ Cascade CLOSED | 6

7

S | Cascade OPEN | and | Cascade CLOSED | appear

Select when prompted. Select to return to the Check control menu.

You have now reconnected the Primary loop to the Secondary loop so your control configuration will look like Figure 18:

| Thermocouple

Cascade disabled

Secondary loop

Cascade . open Primary loop Secondary loop |_, | Flow Temp _ Controller Controller Process Process - - Secondary loop Primary loop

Figure 18

21

Downloaded from www.Manualslib.com manuals search engine

Page 27 read from a scan by OCR; it may hold reading errors

Operation and Tuning

Section 1-3

Setting primary loop PID values

Before you can set the PID values, you must set the SP (set point) for the primary loop.

1. From the ES/TOOLS menu, select Check control.

2. At the left vertical menu, select Change SP. Enter the desired set point.

3. Select [ENT: OK |

4. Select from the pop-up window.

5. Select [F2: Param )

6. Select from the vertical menu from the left side of the screen. A pop-up menu will appear.

7. Select the PID bank that you are using. Select [ENT: OK }.

8. From the pop-up window, select P, |, and D separately and enter the value you need.

9. Select until you are back to the main menu of the Check Control.

10. Refer back to Starting the Limit Cycle and Loop PID Calculations to complete tuning the primary loop.

You have now completed the setup required for using the Limit Cycle Method of determining PID values. Proceed to Fuzzy Logic Fine Tuning.

1-3-3 Fuzzy Logic Fine Tuning

Note:

If you have already tuned your controller using the Limit Cycle method and want to use the Fuzzy Logic Fine Tuning as an enhancement, then go directly to the Using Run Mode subsection.

Fuzzy Logic Fine Tuning may be substituted for the limit cycle tuning method if a limit cycle adversely effects the process or system safety. It may also be used to complement the Limit Cycle method to enhance your ES100 performance.

Fuzzy Logic Fine Tuning is effective only with PI or PID control strategies. If you are only using P control, you must change the constants manually. The engineer or operator in charge of your process should have an approximate idea of these values in order to complete the tuning process.

Isolating the Secondary Loop

Note:

22

The first step in tuning the secondary loop is to isolate it from the primary loop. Isolate the secondary loop from the primary loop as follows:

You must have the controller powered up and the communication cable installed between the computer and ES100.

1. Select the Check control icon by double-clicking on it. The Check control menu appears

Downloaded from www.Manualslib.com manuals search engine

Page 28 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 1-3

2. In the Check control menu double-click on (Figure 19).

E

Fi:Run | F2:Paran | |F3:status | F4:Command] |F9:opt ion || || ESC: Exit |

Check control

68/29/94 7580.8 16:68:33

Move point

Monitor rend Setting [SP 106.80 Py 75.84 MY 8.804

Clear data

Trend mode

Exec A.T.

ypu

Exec F.T. Interval 2 Second Canc A.T.

Undo F.T. Draw mode

Clear + draw

Change SP

EERE RUE

6:62:66 6:66:84 6:16:08

Figure 19

3. From the pop-up menu select Change Cascade OPEN/CLOSED | then so-lect OPEN] Another pop-up menu then confirms switching cascade to open.

4. Select to confirm. 5. Select to return to the Check control menu.

The secondary loop now is independently controlled from the primary loop by the ES100. Figure 20 represents an open cascade loop with the secondary loop isolated. Note that the secondary loop is the only loop being controlled.

| Thermocouple

Cascade disabled an]

Cascade open Primary loop O / Secondary loop Flow Temp ~~ Controller Controller -™| Process Process a Secondary loop Primary loop

Figure 20

23

Downloaded from www.Manualslib.com manuals search engine

Page 29 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 1-3

Setting Secondary Loop PID Values

By isolating the secondary loop from the primary loop, you are able to view/ modify the secondary PID loop default settings.

Note: If you are familiar with your system PID values, use them in place of the default values, if you don’t know them simply use the defaults.

Note: You must have the controller powered up and the communication cable installed between the computer and ES100.

1. From the Check control menu, select |F2:Param | 2. From the vertical menu on the left side of the screen select | PID param }

Fo Check control ial

| Fi:Run || F2:Param ||F3:status] F4:Comnand] |F9: option] | || Esc :Exit |

| eT I I l l

ESC ‘Cancel

Select PID parameter [PID No.=11] PID param ESC :Cancel

Adj param

IP k ZZ strngth] I D

MY lower limit

MY upper limit

PV bias value

Auto select range upper limit

Clear + draw

6:42:68 6:46:68 6:14:68

Figure 21

3. From the pop-up, double-click on ‘P’ (Figure 21). Note that the default value is 100% which should be adequate for most applications. If a new value is desired, simply type in the new value.

4. Select button.

5. Scroll down and select ‘I’. Note that the default value is 60 seconds which should be adequate for most applications. If a new value is desired, simply type in the new value.

6. Select button.

7. Scroll down and select ‘D’. Note that the default value is 0 seconds which should be adequate for most applications. If a new value is desired, simply type in the new value.

8. Select button.

9. Select the button from the pop-up window. 10. Anew window appears that will let you change PID bank #’s if you wish to. Then select LESC:Cancel_ |,

11. Select the button from the vertical menu on the left side of the screen.

24

Downloaded from www.Manualslib.com manuals search engine

Page 30 read from a scan by OCR; it may hold reading errors

Operation and Tuning Section 1-3

Setting the Fixed Value Set Point for the Secondary Loop (FSP2)

Note: If you know what the setpoint of your secondary loop should be, use the following procedure. If you do not know, go to the Manual Output Control method later in this section.

Because the primary loop has been temporarily disconnected from the secondary loop, its output is no longer available as the setpoint of the secondary loop. Therefore, you will need to establish an approximate value for the secondary loop setpoint. This approximate value should be known to the operator/engineer with a knowledge of the system. If it is not known you can use the Manual Output Control method described later in this section. Please note that the unit of the SP2 is a percentage value. The output variable of the primary loop can be set any where between 0% (Fully OFF) and 100% (Fully ON).

1. From the ES/TOOLS menu select Check control.

2. From the Check control menu, select [_F2:Param

Note: All the options on the left side of the screen will change as shown in Figure 22., Check control Unit No.4 al

| Fi:Run | | F2:Param | [r3:Status | Fa :Comnand] [ro :Option | | | | ESC Exit |

ESC :Cancel Select adjustment parameter Esc:cancet] [aaj param | SP rise rate limit SP fall rate limit

MU change rate Limit

Fixed SP (secondary loop)

IP (secondary loop)

I (secondary loop)

D (secondary loop)

Manual reset (secondary loop)

__], 368

6:62:68 6:66:68 6:16°66

Figure 22 3. Select Adi param |,

4. Scroll down and select Fixed SP Secondary loop from the pop-up menu.

5. In the pop-up window, type in the percentage of output that you want for the setpoint of your secondary loop, and select <Enter> on the keyboard.

Select button. Select button. Select the button from the pop-up menu.

Select the button from the vertical menu on the left side of the screen to return to the main menu.

Displaying Process Trends

Use the following procedure to display loop process values (PV2, SV2 and MV) on your computer. You will need to monitor this display to measure hunting and width to determine PID values for the primary and secondary loops.

o oN

25